If the enclosure must be opened for servicing, to check or replace internal devices and
apparatus, the following procedures should be followed.
WARNING: Before servicing the fixture, be certain the electrical power is OFF and
remove the unit is removed from the Hazardous Environment. This fixture contains
an “Internal Voltage Source” and remains energized when disconnected from direct
line power sources.
•
Remove all cover bolts. Clean and inspect. Replace any corroded, bent or otherwise
damaged bolts with new, factory authorized bolts obtained from an authorized
distributor.
•
Open enclosure. Do not use hammer, screwdriver, or any prying tool to open cover,
except as shown in Figure 4.
•
Inspect cover hinges. If hinges are damaged or do not function properly, contact a factory authorized service
representative for hinge replacement and installation.
•
Inspect machined flange (flame path) surfaces. Surfaces must be smooth, free of nicks, scratches, dirt or any
foreign particle build-up that would prevent a proper seal. Should surface be damaged contact factory. Never
attempt to rework surfaces by sanding, grinding, ect. Surfaces must seat fully against each other to provide proper
explosion-proof joint.
•
Inspect water exclusion gasket. If gasket is damaged, do not attempt field replacement or repair.
•
Contact a factory authorized representative for a replacement cover. When removing gasketed cover for
replacement, do not detach hinge body from cover.
•
Remove cover and hinge body from enclosure by removing the hinge pins. (see figure
5) The damaged gasket can be removed from the cover and the cover without gasket can be
safely used in Class I & II hazardous (classified) locations, however the enclosure may not be
raintight or hosedown tight.
•
Clean flange surface by wiping with a clean, lint-free cloth. Apply a light coating of
lubricant to flange surfaces and close cover. Install and tighten all cover bolts to 30 ft. lbs. Make
certain no cover bolts are omitted. Use only factory authorized bolts. Check the flame joint with
a .0015” feeler gauge. The gauge must not enter the flame joint more that 1/8” at any point.
Missing bolts or an improper flame joint can result in an explosion, creating a potential for
physical injury and property damage.
LAMP REPLACEMENT
•
Turn OFF the supplying circuit before opening fixture for re-lamping. To re-lamp loosen the locking screw and
remove the globe support assembly.
•
The globe support assembly disengages after approximately 3 turns. *Replace the lamp with one of the correct
size and type. Refer to the fixture nameplate for this information. When relamping, be careful not to damage the
threaded areas of the fixture, as they maintain the fixture’s explosion proof properties. Clean the threads and
apply a thin coating of lubricant before reassembling.
•
To maintain maximum light output, the fixture should be cleaned periodically. Maintenance procedures sometimes
require fixtures to be hosed down for good housekeeping.
•
The supply circuit must be turned OFF and the fixture globe must be allowed to cool to the ambient room
temperature before cleaning. Only mild, non-abrasive cleaning agents should be used. These periodic cleaning
procedures are important to prevent the accumulation of dust and dirt which will impair the light output of the
fixture. The glass globe should be regularly inspected for scratches and chips and, if damaged, the entire globe
support assembly must be replaced.