WIRING
(see attached wiring diagram)
This unit comes preconfigured with selected voltage and beam angle. Once mounted, wire cord
according to diagram with correct
voltage on nameplate!
WIRING
1.
Connect supply wires to luminaire wire leads (or terminal blocks) using methods that comply
with all applicable codes. Tighten all electrical connections.
2.
Close cover module, making sure that all wires are safely inside driver. Tighten captive closing
screw.
3.
Close all unused conduit entries with conduit plugs. To ensure water-tightness, lubricate
conduit plugs with lubricant before installing, and secure wrench-tight with at least five (5) full
threads engaged (42-52 ft.-
lb. for 3/4” plugs, and 58-68 ft.-lb. for 1” plugs).
4.
Turn power on and aim.
MAINTENANCE
1.
Perform visual, electrical, and mechanical inspections on a regular basis. The environment and
frequency of use should determine this. However, it is recommended that checks be made at
least once a year. We recommend an Electrical Preventive Maintenance Program as
described in the National Fire
2.
Protection Association Bulletin NFPA No. 70B: Recommended Practice for Electrical
Equipment Maintenance (www.nfpa.org).
3.
The lens should be cleaned periodically to ensure continued lighting performance. To clean,
wipe the lens with a clean, damp cloth. If this is not sufficient, use a mild soap or a liquid
cleaner such as Collinite NCF or Duco #7. Do not use an abrasive, strong alkaline, or acid
cleaner. Damage may result.
4.
Visually check for undue heating evidenced by discoloration of wires or other components,
damaged parts, or leakage evidenced by water or corrosion in the interior. Replace all worn,
damaged, or malfunctioning components, and clean gasket seals before putting the luminaire
back into service.
5.
Electrically check to make sure that all connections are clean and tight.
6.
Mechanically check that all parts are properly assembled.
THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. SHOULD FURTHER
INFORMATION NOT COVERED BY THESE INSTRUCTIONS BE REQUIRED, PLEASE CONTACT LARSON ELECTRONICS BY EMAIL AT
OR BY PHONE
AT 1-800-369-6671 FOR FURTHER ASSISTANCE.
PLEASE VISIT LARSONELECTRONICS.COM FOR
WARRANTY
AND
RETURN
INFORMATION.
WARNING:
CHECK NAMEPLATE
FOR PROPER VOLTAGE. DAMAGE
FROM IMPROPER VOLTAGE WILL
VOID WARRANTY.