EPL-48-2L

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

3

 of 

5

 

Caution: 

Only use lamp size, type and /or wattage as shown on fixture nameplate. 

INSTRUCTIONS FOR INSTALLING

 

We strongly recommend that only a licensed electrician install this product.

 

WARNING: 

Make sure that the power is disconnected before installing. This fixture is extremely heavy and must be 

mounted to a surface that can structurally support the load. 

NOTE: 

This fixture requires a minimum of 50 inches of clearance from re-lamp end for lamp replacement. An optional 

drop mounting kit that will allow for end to end row mounting is available, please consult factory. 

WARNING:  Do not let fixture hang on one bracket at any time. Failing to comply can result in breakage of 
end casting or mounting bracket, allowing the fixture to fall, which can cause serious injury or death.

 

The mounting brackets are shipped installed on the
fixture.

Install the brackets to wall or ceiling with two 3/8" bolts
(not supplied) at center measurements.

Fixture is now ready for mounting.

For pendant mounts, see reference image.

It is strongly suggested to use two licensed electricians to proceed with the final mounting of the fixture to avoid any 
possible personnel injury or damage to the fixture as the unit weights up to 46lbs (21.0 kg) and will be slightly awkward 
to hold in position and attach to brackets mounted on wall or ceiling. Depending on mounting height and scaffolding, a 
hydraulic man

–lift or two good quality ladders should be used. 

INSTRUCTIONS FOR WIRING LAMP

 

This lamp includes 50ft SOOW cable whip pre-attached from factory.

Once mounted, run cable to compatible receptacle outputting the correct voltage.
Check product label to ensure voltage is correct. This lamp is shipped with
selected voltage from factory which includes either 347-480V AC 50/60Hz.

Wire diagram included for maintenance reference.

WARNING: 

Fixture must be grounded as required per paragraph 410-21 and article 250 of the National Electric Code 

and/or rule 30-500. Failure to properly ground this fixture will create an electrical shock, which can cause serious injury 
or death. 

PENDANT (-PND) 

SURFACE (-SFC) 

WARNING 

4

To avoid risk of fire, explosion or electric shock, this product should be maintained by a qualified electrician only, in 
accordance with all applicable codes and regulations. 

4

To avoid electric shock: Be certain electrical power is OFF before and during maintenance. 

INSTRUCTIONS FOR RELAMP

 