background image

EPL-48-2L

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

2

 of 

5

 

WIRING 
Standard pigtail(flying leads) wiring 

We strongly encourage a licensed electrician install this product

, in all locations especially in outdoor areas 

where weatherproofing may be required. Universal voltage driver permits operation at 1

2

0V  -  277V AC, 50 or 60Hz

.

Warning: 

Check product label for correct input voltage!

 

Attach supply line wires to the appropriate light fixture wires as shown 

in the diagram 

 

Secure each pair of wires according to the diagram. Utilize a junction box or 

similar  device  and  take  precautionary  steps  for  weatherproofing  all 

connections if installed in a location where water may come in contact with the 

unit. Ensure the unit is properly grounded and that wiring is done according to 

all local and national electrical/building codes. 

ADJUSTABLE SURFACE MOUNTING BRACKETS

Each bracket is cinched to the bracket mounting peg on each side of the light. The angle of the bracket is set by tightening 

two cap screws on either side of the bracket. The cap screws act as a set screw. The bracket itself is mounted via a single 

bolt hole at the top the bracket. There are two brackets, one on each end of the light. Once the brackets are mounted to a 

surface (ceiling, floor or wall), the light fixture can be removed from the brackets by loosening the cap screws that hold the 

bracket to the mounting peg.

SUSPENSION MOUNTING

Pendant mount fixtures hang from the ceiling and are suspended by rigid pipe. Each fixture features a 1/2” NPT junction box 

on one end, and a 1/2” NPT adjustable L-bracket on the other end of the fixture. Operators bring rigid pipe down to the 

threaded mounting hubs. Wiring is fed down through the rigid pipe to the junction box and tied in to the fixture’s lead wires, 

completing the electrical connection. The adjustable L-shape mounting bracket provides support for the opposite end of the 

fixture.

INSTALLATION PRECAUTIONS

 

Do not install fixture in any classified location where the marked operating temperature exceeds the ignition
temperature of the hazardous atmospheres.

Consult fixture nameplate for the suitability ambient temperature shown on the nameplate.

Refer to fixture nameplate for minimum supply wire temperature rating.

Verify that the supply voltage agrees with fixture rating as indicated on nameplate.

All local and national electrical/building codes must be followed when installing this lighting fixture. For
code interpretation, consult your local authority.

Product must be used only with glass tubes intact and all cap threads fully engaged. Do not use if glass tubes
are cracked or damaged.

Reviews: