![background image](http://html1.mh-extra.com/html/larson-electronics/epl-24-50led/epl-24-50led_instructions_3718697002.webp)
Larson Electronics LLC www.LarsonElectronics.com [email protected]
9419 E US HWY 175, Kemp, TX 75143 - P: (800) 369-6671 - F: (903) 498-3364
The use of accessory equipment is not recommended by the manufacture and may cause an
unsafe condition.
Do not use this equipment for other than intended use.
The technical data indicated on the luminaire are to be observed.
Changes to eh design and modifications of the luminaire are not permitted
Only genuine replacement parts are to be used when unforeseen maintenance is required.
Consult the factory at www.magnalight.com or an authorized representative.
For supply connections use wire rated for at least 90°C.
CONDUIT THROUGH MOUNT
For maximum long term reliability and light output, the light must be installed in free air.
o
The Linear fixture design incorporates an over-temperature control circuit that reduces
input power should internal temperatures reach a maximum level. In this event, light
output may be reduced.
The Linear is threaded for 3/4" NPT, at the center and each end of the Power Supply Housing, in
order to be assembled to conduit.
o
Attach conduit as shown in figure 2. Use conductive pipe sealant for all fittings and
conduit.
o
WARNING:
If there is moisture present, or chance of it, in the conduit system then
necessary precautions should be taken by the installer to prevent the moisture from
entering thru the cable or conduit and entering the fixture. Failure to comply with the
above could void the warranty.
o
Fixture is factory wired for both pendant and through wiring. Remove the Power Supply
Cover to attach incoming power to the white wire and black wire leads with wire nuts at
the end of the fixture. Attach ground wire to the green ground lead supplied at the end
of the fixture. Repeat this procedure for the opposite end. Ensure that the O-rings are
properly seated in the grooves; reattach the cover using the screws previously removed.
Tighten all screws to 15 in/lbs (1.75NewtonM’s)
o
Connect incoming power as follows:
Green to safety ground using green ground lead supplied at the end of the fixture
Neutral to white
Line to black
Restore power and verify operation