![background image](http://html.mh-extra.com/html/larson-electronics/cgb-c1d1-mchl-series/cgb-c1d1-mchl-series_instruction-manual_676581006.webp)
Larson Electronics, LLC
Phone:
877-348-9680
Fax: (903) 498-3364
www.larsonelectronics.com
INSTALLATION INSTRUCTIONS FOR
CGB-C1D1-MCHL
Series
1
2
3
4
5
7
1.
RapidEx Resin
2.
Resin Tube
3.
Entry Component
4.
Sealant Tape or Inner
Jacket
5.
Resin Dam
6.
End Stop
7.
Grounding Spring
8.
Jacket Seal
9.
Outer Nut
9
6
8
1. Cable preparation — Without Inner Jacket
Strip back the jacket armor to suit the equipment
geometry.
---
---
Tape
Cable Fillers
Cable Cores
2.
Cut Tape to length
Length = groove in hexagon to front of outer
nut
1.
Using the measure guide, wrap electrical tape around
the fillers and cores of the cables to the required
length
3.
After the tape has been applied, cut
the cable fillers to the edge of the
tape.
Outer Jacket
1. Cable preparation — With Inner Jacket
Strip back the jacket armor to suit the equipment
geometry.
Cut inner jacket to length
Length = groove in hexagon to front of outer nut
Using the measure guide, cut the cable inner
jacket (and any cable fillers) to the required
length. If inner jacket is too large for the Resin
Dam, cut off and replace with electrical tape.
---
---
---
---
Cut outer jacket to length
Length = Groove in hexagon to rear of outer nut
2. Using the armor measure guide, expose the armor further by stripping back the cable jacket.
NOTE: When the outer jacket is at
its maximum, cut distance may
have to be increased by up to 10%.
5
of
7
CGB-C1D1-MCHL
Series