Also, Set all Switchpoints to “OFF” in the Rates Schedule 

 

 

 

 

 

Meter Installation   

 

Step 1.

 

    Installing S4e UtiliNet Meter 

 

If existing meter is present, follow company procedures for meter removal and installation. (Note: Meter removal 

and installation should only be performed by a properly trained technician.)   
 

During communication the LCD will flash P/R in the alphanumeric segments. 

 

Bulletin Number: 20031201 Rev A 

S4e-UtiliNet User Manual 

Page 9 of 13

 

 

Summary of Contents for S4e UtiliNet

Page 1: ... this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Landis Gyr Inc 2003 Landis Gyr Inc All rights reserved For further information contact Landis Gyr Inc 2800 Duncan Road Lafayette IN 47904 USA Tel 800 777 2774 Fax 765 742 0936 DOCUMENT HISTORY Bulletin Revision Date Description Level Issued ...

Page 2: ...Y WARNINGS 3 FCC INFORMATION 4 INTRODUCTION 4 SYSTEM OVERVIEW 5 S4E METER OVERVIEW 6 UTILINET MODULE OVERVIEW 6 CONFIGURATION OF THE UTILINET MODULE 7 METER SETUP 7 METER INSTALLATION 9 TROUBLE SHOOTING GUIDE 10 USE OF EXTERNAL ANTENNAS 10 TECHNICAL FEATURES OF THE S4E UTILINET 12 ...

Page 3: ...r Remove the meter from service prior to installing the antenna isolation kit and or remote external antennas Be aware that dangerous voltages exist at several points within the meter when this product is installed on a meter socket Always disconnect power before meter disassembly soldering or replacing components The S4e meter is connected directly to line potential Due to the possibility of the ...

Page 4: ...uipment uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off...

Page 5: ...large deployments System Overview The S4e UtiliNet system looks as follows Bulletin Number 20031201 Rev A S4e UtiliNet User Manual Page 5 of 13 Data acquisition can be provided by a hosted service for small to large meter deployments or an own and operate solution The UtiliNet network provides secure packet based data transfer The Landis Gyr designed UtiliNet module supports the following system s...

Page 6: ...ve measurement Demand or TOU RXR 32K Active and reactive measurement with 32K byte load profile recorder RXR 128K Active and reactive measurement with 128K byte load profile recorder An optional input output board provides up to 2 form C solid state relays and up to one external inputs for recording pulses from a remote source The 4 relay option board is not available with the S4e UtiliNet meter O...

Page 7: ...gramming requirements for the S4 using 1132Prog The load control relay activates the relay upon power up This relay triggers the UtiliNet module to power up If the meter is not programmed as shown below the UtiliNet module will not operate as expected A special tool Utilinet Radio Tool was developed to query and reboot the UtiliNet module Relays Set Relay 4 to Load Control LC Used in Normal Mode a...

Page 8: ...Landis Gyr TOU Rates Schedule Set AX RX Only to Yes and Schedule Relay to Yes Bulletin Number 20031201 Rev A S4e UtiliNet User Manual Page 8 of 13 ...

Page 9: ...f existing meter is present follow company procedures for meter removal and installation Note Meter removal and installation should only be performed by a properly trained technician During communication the LCD will flash P R in the alphanumeric segments Bulletin Number 20031201 Rev A S4e UtiliNet User Manual Page 9 of 13 ...

Page 10: ...ernal antenna However some meter locations have less than optimal RF reception Many meter services are ungrounded Examples of these types of services include single phase form 2S as well as floating 3 wire delta services 12S and 45S 5S To improve the reliability and safety of these floating services Landis Gyr has developed an interface for remotely mounted antennas that allows RF reception under ...

Page 11: ...Landis Gyr Meter OEM2232 Bracket Cable OEM2284 Signal Internal Antenna Bulletin Number 20031201 Rev A S4e UtiliNet User Manual Page 11 of 13 ...

Page 12: ...ing Temperature Meter 40 to 85 C under cover UtiliNet Radio 40 to 60 C under cover Humidity Meter Less than or equal to 95 relative humidity non condensing UtiliNet rated 650 C at 90 relative humidity non condensing Meter Rated Accuracy at Unity Power Factor Transformer Rated Self Contained Meters 0 2 K Base Meters 0 5 Over voltage Withstand Temporary 5 sec 150 rated voltage Continuous 5 hours 120...

Page 13: ... Coordinates Receiver Type Double Conversion Superheterodyne 1st IF 45 MHz 2nd IF 455 kHz Dynamic Range 104 to 20 dBm Packet Error Rate 1x10 2 1x10 6 BER IF Selectivity 6 dB down 30 kHz 45 MHz IF Rejection 90 dB Frequency Stability 2 5 ppm 0 00025 30 to 75 5 ppm 0 0005 40 to 85 Transmitter RF Output Min at antenna conn 17 dBm 50 mW RF Output Typical 20 dBm 100 mW Out of Band Spurious Radiation 55 ...