Accuracy Testing 

MAXsys Elite Meter

 

 

The accuracy testing for the Elite meter is done through the transmit “LED” of the optical port 
on the face of the meter. The optical port is located on the lower left hand side of the meter face 
and the left “LED” is the transmit LED and is located on the left side of the port. The LED has 9 
modes of operation. Optical communications (type 7 protocol), Watt hour, Var hour, 
Compensated Watt hours Comp. 1, Compensated Var hours Comp. 1, Compensated Watt hours 
Comp. 2, Compensated Var hours Comp. 2, Compensated Watt hours Comp. 3 and Compensated 
Var hours Comp. 3.  The modes can be changed using MAXcom under the test mode screen. The 
meter does not need to be put into test mode to change the LED modes. The mode of operation 
can be seen on the meter display using the menu system. The user would enter the menu system 
using the buttons (E) on the face of the meter. They would then select “communications” from 
the list of menu items. This will take the user to a sub menu where they can select the optical 
port. To select the optical port the user will select the “more ports” option that will bring up 
another menu with “optical port”. After selecting “optical port” the screen will display the “Cal 
Pulse” mode . 
 
When testing for meter accuracy it is recommended that no test should be run for less than 30 
seconds. The 30 second test is recommended to reduce timing errors between the test equipment 
and the meter. The following examples are for a Form9S, 120 volt meter with a Kh of 1.0 being 
tested a rated voltage and a test current of 2.5 and 0.25 amps. 
 
Full Load  

10 Rev. 

40 seconds 

Power Factor  05 Rev. 

40 seconds 

Light Load 

02 Rev. 

80 seconds 

 
When testing TLC accuracy the values meter is normally tested at the rated secondary value of 
the instrument transformer. 
The following examples are for a Form 9S, 120 volt meter with a Kh of 1.0 that is connect to 
instrument transformers, VTR=7200:120 and CTR=1200:5. The tests are normally run at rate 
voltage (120 volts) and a test current of % and 0.5 amps. 
 
Full Load 

20 Rev. 

40 seconds 

Power Factor  10 Rev. 

40 seconds 

Light Load 

04 Rev. 

80 seconds 

 
 

 

 

 

 

 

Summary of Contents for MAXsys E850 Elite

Page 1: ...ems This will take the user to a sub menu where they can select the optical port To select the optical port the user will select the more ports option that will bring up another menu with optical port After selecting optical port the screen will display the Cal Pulse mode When testing for meter accuracy it is recommended that no test should be run for less than 30 seconds The 30 second test is rec...

Page 2: ...eferred is to use the MAXcom software this will prevent you from accidently doing a demand reset The other method is to remove the cover and press and simultaneously hold the S1 Mode Select button on the lower left side of the DPM display card and then press and hold the demand reset button until the meter goes into test mode Do Not press the demand reset first Method 1 Using Maxcom Software 1 Sta...

Page 3: ... will indicate the meter has entered into test mode Click Start Test in the software 11 Set up the test equipment and apply the test load 12 Click Start Test a The test mode displays will appear on the face meter If the test seconds is at the top of the list it can be seen counting up Note There will be no demand values until the test has completed or the test has been stopped by clicking Stop Tes...

Page 4: ... press and hold the S1 Mode Select button on the lower left side of the DPM display card and then press and hold the demand reset button until the meter goes into test mode Do Not press the demand reset first 5 This will put the meter into test mode Note This will stop the meter from up dating the active billing registers a The display on the meter will indicate the meter has entered into test mod...

Page 5: ... using the buttons on the face of the meter 10 You can run another test be pressing the demand reset a This will clear the old test data and the test will start 11 When you have completed your testing a Remove the testing equipment 12 Take the meter out of test mode by simultaneously press and hold the S1 Mode Select button on the lower left side of the DPM display card and then press and hold the...

Reviews: