Page 37
Buttons
67 Button „F-Off“
[S11] switches off humidity monitoring, e.g. to run dry the system (see page 23).
- Signal-LED „F-on“ (
54
) turns off.
Pressing the button for 5 seconds reactivates the humidity monitoring.
- Signal-LED „F-on“ (
54
) illuminates again.
68 Button „external Signalization“
[S12] must be activated in order to forward upcoming signals of a mobile
emergency pressurisation system. The signalling lines of the mobile system must be connected to clamp 1
and 2 of the terminal strip [X1] of the stationary system. „External Signalization“ can be activated only if a
system signal of the stationary system is pending.
- Signal-LED „Ext. Signalization“ (
57
) illuminates.
The external signalisation of the mobile emergency pressurisation system „Ext. Signal in“ affects the signal
relay K-A of the stationary system. Therefore the stationary system should be shut-off by the motor protec-
tive switch (Q4) (
5
).
When the the stationary system is switched on again, the monitoring of the mobile emergency system is
shut-down automatically.
- Signal-LED „Ext. Signalization“ (
57
) turns off.
Then the system signals of the stationary system affect the signal relay K-A
.
69 Button „Reset maintenance“
[S10] must be pressed down for 5 seconds to reset the operating hour
meter to the default value of 400 hours.
This process is irreversible!
- Signal-LED „W“ (
63
) turns off, if it has been already activated.
70 Button „Test“ W Signal, A Signal
[S9] may be pressed to check an optionally connected external signali-
sation.
- Relais „K-W“ activates and Relais „K-A“ deactivates.
- Signal LEDs „W“ (
63
) and „A“ (
64
)
illuminate
.
- Alarm „A“ must occur in the remote control center if a signal line is connected.
Fuses
A
Fuse „AC“
safeguards the AC circuit (supply voltage).
Type: 0,315 A, medium time lag
B
Fuse „DC“
safeguards the DC circuit (signal voltage).
Type: 2 A, medium time lag
A
59
60
61
62
70
69
63
64
65 66
52
53
48
54 55
67
49
51 56
68 57
89
B 47
Relay
with labeling acc. to wiring diagram
KY1
Summary of Contents for RTS 1000D
Page 43: ...Page 43 Compressor VD 7 2 RTS 1000D and VD 28 2 RTS 2600D B...
Page 45: ...Page 45 Compressor VD 50 4 RTS 5200D...
Page 57: ...Compressor VD 7 2 and VD 28 2 Page 57...
Page 59: ...Page 59 Compressor VD 50 4...
Page 61: ...Page 61 Pneumatics diagram RTS 1000D RTS 2600D and RTS 5200D no 073445 072...
Page 63: ...Page 63 Circuit and wiring diagram RTS 1000D RTS 2600D und RTS 5200D no 073659 000...
Page 65: ...Page 65 Circuit and wiring diagram RTS 1000D RTS 2600D und RTS 5200D no 073586 000...
Page 66: ...Page 66...
Page 67: ...Page 67...