As product is dispensed, ice is depleted, the ice bank control senses that the ice is melting and 

turns the compressor and condenser fan on. When the ice bank is rebuilt, the ice bank control turns 

the compressor and condenser fan motor off. The compressor will periodically run to maintain the 

ice bank even though no drinks were dispensed. If power to the unit was disrupted while the 

 

 

compressor was running, the compressor will not restart immediately when power is re-established.

 

 

There is a restart delay circuit [approximately five minutes] built into the ice bank control to prevent 

the compressor from starting under pressure. This feature protects the compressor from premature 

failure.

 

 

Ice water is circulated through the cooling coil at the rear of the product compartment with a pump 

at the bottom of the ice bath. Cool air is circulated in the product compartment by four small fans 

mounted to a cooling coil in the container compartment.

 

4.4  ELECTRICAL SYSTEM

F

GROUNDING WARNING

 THE DISPENSER MUST BE PROPERLY ELECTRICALLY GROUNDED TO AVOID 

SERIOUS INJURY OR FATAL ELECTRICAL SHOCK.  THE POWER CORD HAS A THREE-PRONG GROUNDED 

PLUG. IF A THREE-HOLE GROUNDED ELECTRICAL OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD TO 

GROUND THE UNIT. FOLLOW ALL LOCAL ELECTRICAL CODES WHEN MAKING CONNECTIONS. EACH 

DISPENSER MUST HAVE A SEPARATE ELECTRICAL CIRCUIT. DO NOT USE EXTENSION CORDS. DO NOT 

CONNECT MULTIPLE ELECTRICAL DEVICES ON THE SAME OUTLET.

ADVERTENCIA, PUESTA A TIERRA 

 ES NECESARIO PONER A TIERRA ELÉCTRICAMENTE EL 

DISPENSADOR PARA EVITAR LESIONES GRAVES E INCLUSO ELECTROCHOQUES FATALES. EL CABLE DE 

ALIMENTACIÓN TIENE UN ENCHUFE PUESTO A TIERRA DE 3 CLAVIJAS. SI NO SE DISPONE DE UN TOMA 

ELÉCTRICO CONECTADO A TIERRA DE TRES AGUJEROS, USE UN MÉTODO APROBADO PARA PONER A TIERRA 

LA UNIDAD. AL HACER LAS CONEXIONES, RESPETE TODOS LOS CÓDIGOS ELÉCTRICOS LOCALES. CADA 

DISPENSADOR DEBE TENER UN CIRCUITO ELÉCTRICO INDEPENDIENTE. NO USE CABLES DE EXTENSIÓN. NO 

CONECTE VARIOS DISPOSITIVOS ELÉCTRICOS AL MISMO TOMACORRIENTE.

EXIGENCES DE MISE À LA TERRE

 LA DISTRIBUTRICE DOIT ÊTRE MISE À LA TERRE ÉLECTRIQUEMENT 

CORRECTEMENT POUR ÉVITER DES BLESSURES GRAVES OU UNE DÉCHARGE ÉLECTRIQUE MORTELLE. LE 

CORDON D’ALIMENTATION A UNE FICHE À TROIS BRANCHES MISE À LA TERRE. SI AUCUNE PRISE DE 

COURANT ÉLECTRIQUE À TROIS TROUS N’EST DISPONIBLE, UTILISEZ UNE MÉTHODE APPROUVÉE POUR 

METTRE L’UNITÉ À LA TERRE. RESPECTEZ TOUS LES CODES ÉLECTRIQUES LOCAUX LORSQUE VOUS FAITES 

DES CONNEXIONS. CHAQUE DISTRIBUTRICE DOIT AVOIR UN CIRCUIT ÉLECTRIQUE SÉPARÉ. N’UTILISEZ PAS 

DE CORDONS PROLONGATEURS. NE BRANCHEZ PAS PLUSIEURS APPAREILS ÉLECTRIQUES À LA MÊME PRISE 

DE COURANT.

17

 

 

The unit’s power cord plugs directly into the power supply located on the front left corner of the 

 

 

dispenser behind the splash plate. Jumper harnesses from the power supply provides 32 VDC to 

the CPU and line voltage to the refrigeration deck.

 

 

The dispenser’s electronic systems control all of the dispenser functions. The refrigeration system 

is controlled by an electronic ice bank controller located on the compressor deck. A printed circuit 

board, located in the doors, operates the front display panel and relays control signals to the control 

box. All other functions are controlled by the electronic control box located behind the splash plate.

  

A.   Water Solenoid/Flow Meter

 

 

 

When the dispense mode is activated, the solenoid valve opens and water flows through a   

 

digital flow meter which sends a signal to the microprocessor. The microprocessor continuously  

 

monitors the flow rate and adjusts the concentrate drive motor to correct for any variations in  

 

flow rate due to pressure variations.

  

B.   Electronic Ice Bank Controller

 

 

 

The ice bank controller housing is mounted on the compressor deck. It connects to a probe that  

 

is mounted to the evaporator coil. The probe allows the controller to measure the difference in  

 

resistance between water and ice, and shuts the compressor off when the ice bank grows    

 

enough to cover the probe. The printed circuit board inside the housing uses an edge connector

 

 

 

so that it can be easily serviced.

  

C.   Product Compartment Temperature Sensor

 

 

 

A temperature sensor is located below the cooling coil inside the product component. Product  

 

compartment temperature is displayed on the product compartment door.

Summary of Contents for MOO

Page 1: ...l Support Warranty 800 729 1550 custserv lancercorp com lancercorp com Manual PN 28 0716 01 10 07 10 FOR QUALIFIED INSTALLER ONLY MOO Milk Dispenser 115V 60Hz Operation Manual PN 28 0716 01 Lancer is...

Page 2: ...CAUTIONS 6 9 1 INSTALLATION 10 1 1 UNPACKING 10 1 2 SELECTING A COUNTER LOCATION 10 1 3 INSTALLING THE DISPENSER 10 11 1 4 KEYLOCK SWITCH 11 1 5 PURGING AIR FROM THE WATER SYSTEM 11 2 OPERATING THE U...

Page 3: ...CTRONICS BOARD REMOVAL 22 6 15 WRAPPER REMOVAL 22 7 TROUBLESHOOTING 22 26 8 DISPENSER DISPOSAL 26 9 ILLUSTRATIONS PARTS LISTINGS WIRING AND WATER FLOW DIAGRAMS 26 9 1 COMPRESSOR DECK ASSEMBLY 28 29 9...

Page 4: ...PSI 0 241 MPA Max operating pressure 90 PSI 0 621 MPA FITTINGS Plain water inlet 3 8 barb hose fitting Water pipe connections and fixtures directly connected to a potable water supply must all be size...

Page 5: ...stall the dispenser Include space for a top mounted ice machine if necessary Does the top mounted ice machine have a minimum clearance on all sides Located away from direct sunlight or overhead lighti...

Page 6: ...los ni os sin supervisi n Esta unidad no ha sido dise ada para suministrar productos l cteos La temperatura ambiente operativa m nima m xima para el dispensador es de 40 F a 90 F 4 C a 32 C No opere l...

Page 7: ...e corriente o sistema de proteccion similar 4 Hay una demora de 5 minutos que evita que el compresor y el abanico del condensador arranquen hasta pasado ese tiempo Si hay algun corte en la corriente e...

Page 8: ...enance The resettable breaker switch should not be used as a substitute for unplugging the dispenser from the power source to service the unit Only qualified personnel should service internal componen...

Page 9: ...mperantes El suministro de agua debe estar protegido por una separaci n de aire un dispositivo de prevenci n del contraflujo situado antes del sistema de inyecci n de CO2 u otro m todo aprobado para c...

Page 10: ...ox open Remove power cord and set aside E Run hose through front of unit to access panel in back Pull through See Figure 1 F Cut other end of hose to length Slide oetiker clamp onto hose Insert approp...

Page 11: ...system remains on but the unit will not dispense product 2 ON In this position the refrigeration system remains on and the unit dispenses product 3 FLUSH In this position the refrigeration system rem...

Page 12: ...OUT FEATURE Once the package is changed turn the key to the FLUSH position and touch the in the bottom left hand corner of each touch pad affected until CHANGE PACKAGE appears Turn the keyswitch to ON...

Page 13: ...will display 3 is the left pump 1 is the right pump Toggle using the and button To select press the PUSH button 2 To Reset Pump Revolutions 3 View Version Shows the software version 4 Press PUSH to r...

Page 14: ...e prepared Other Supplies Needed Sanitary gloves Clean cloth towels Extra nozzle Bucket WARNING IF A POWDER SANITIZER IS USED DISSOLVE IT THOROUGHLY WITH HOT WATER PRIOR TO ADDING TO THE SYRUP SYSTEM...

Page 15: ...emove drip tray and cuprest Wash in warm water using a mild detergent Rinse with warm water and reinstall I Ensure draintube into drip tray is properly seated Close door WARNING DO NOT SOAK NOZZLES IN...

Page 16: ...ater 4 3 REFRIGERATION SYSTEM The unit has a lift out refrigeration deck The compressor condenser fan and agitation motors evaporator and ice bank control system are mounted on a common deck plate The...

Page 17: ...E MISE LA TERRE LA DISTRIBUTRICE DOIT TRE MISE LA TERRE LECTRIQUEMENT CORRECTEMENT POUR VITER DES BLESSURES GRAVES OU UNE D CHARGE LECTRIQUE MORTELLE LE CORDON D ALIMENTATION A UNE FICHE TROIS BRANCHE...

Page 18: ...the water from the system C Remove the splash plate Slide the locking clip on the Shut Off Valve to release the inlet fitting and remove the inlet fitting from the valve leaving the valve connected t...

Page 19: ...e gas spring and slide the pin out of the clevis that anchors the gas spring to the door Rotate the gas spring down and out of your way C Remove pin that secures the gas spring to the top clevis same...

Page 20: ...location resting it on the bottom surface of the ice NOTE For this step request assistance if necessary Lift the deck relatively straight to prevent the ice bank from wedging against the sides of the...

Page 21: ...ly to the manifold outlet by sliding the retainer to the locked position 4 Reconnect the waterproof connectors 5 Replace the back plate fan assembly making sure that 1 the wire leads are not pinched b...

Page 22: ...ITION OFF CELA TRANSFORME LA PUISSANCE PRINCIPALE DU CIRCUIT PLANCHES HORS ET EMP CHE D ARC AU NIVEAU DU CONNECTEUR ET EMP CHE BORD DOMMAGE POUR LES CONSEILS E Turn the five plastic standoffs one half...

Page 23: ...fective ice bank control PCB H Defective compressor A Connect unit power cord to electrical outlet B Reset circuit breaker or replace fuse If problem persists 1 check unit for electrical short 2 elect...

Page 24: ...eck C Replace condenser fan motor D Clean condenser E Check for obstructions at air intake exhaust F Replace agitator motor DISPENSING SYSTEM TROUBLESHOOTING The Dispensing System is controlled by the...

Page 25: ...Remove fan plate and check connections at water calibration valve Rectify if necessary 3 Swap suspect water calibration valve with a known working assembly and retest If valve now functions replace wa...

Page 26: ...ith other pump head If pump head works properly after swapping the problem lies with the pump drive Proceed to next step If pump head does not work properly after swapping the problem lies with the pu...

Page 27: ...NOTES 27...

Page 28: ...RESSOR DECK ASSEMBLY ICE BANK CONTROL BOX WIRING AGITATOR WHITE POWER FAN TO COMP BLK 7 53 16 42 20 22 21 26 25 24 23 43 2 35 40 36 11 19 4 19 45 31 30 29 33 12 15 13 5 19 37 14 10 18 17 50 18 19 51 4...

Page 29: ...05 Relay 24 12 0004 Overload 25 13 0006 Cover Terminal 26 03 0040 Bail Strap 27 52 1633 Probe Ice Bank Control 28 04 0633 Screw 8 19 x 0 437 SS 29 47 1408 Tube Suction 30 51 0061 Accumulator 31 50 021...

Page 30: ...9 2 WATER CIRCUIT TANK ASSEMBLY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 30...

Page 31: ...Tank Front 6 01 0797 Nut Compress Align 3 8 Tube 7 50 0264 Insulation Tank Left 8 50 0266 Insulaton Tank Back 9 50 0263 Insulaton Tank Right 10 05 0955 Support Coil Water 11 04 0723 Stud Locator 12 1...

Page 32: ...9 3 INSULATED TANK ASSEMBLY 1 2 3 4 5 6 7 8 8 8 9 1 10 11 12 13 14 14 15 16 17 18 19 20 14 21 22 23 24 25 26 27 32...

Page 33: ...et 12 48 1053 Tube Assy Fitting Elbow Water in 13 52 3132 Power Supply Box Assembly 14 04 0504 Screw 8 18 x 375 PHD W ELW 15 51 6133 Weldment Bracket Power Supply 16 04 0297 Nut Hex 8 32 Keps SS 17 51...

Page 34: ...9 4 INTERNAL CABINET ASSEMBLY 1 2 3 4 5 6 7 8 9 6 10 11 12 10 13 14 34...

Page 35: ...crew 8 32 x 500 PHD PH MS 6 04 0470 Screw 6 19 x 500 PHD PH SL 7 05 2554 Retainer Seal 8 04 1531 Dowel 3 8 OD x 1 4 LG 9 48 2599 Tube Assy Interface Valve 10 02 0089 O Ring 11 52 3103 Harness Assy Pro...

Page 36: ...9 5 PUMP PLATFORM ASSEMBLY 1 2 3 4 5 6 8 9 10 7 36...

Page 37: ...x 438 BH PH 3 04 0406 Screw 6 32 x 375 PH PH MS 4 51 6228 Weldment Chimney Plate 5 54 0429 Base Assy MTG Wave Pump 6 82 3896 Platform Sub Assembly Wave Pump 7 86 0167 Pump Motor Housing Drive Assembly...

Page 38: ...9 6 WRAPPER DOOR DRIP TRAY ASSEMBLY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 38...

Page 39: ...y Switch 7 04 0750 Screw 6 32 x 812 PHD PH Rolok 8 82 1726 Top Cover Assy 9 30 6279 Bracket 10 04 0504 Screw 8 18 x 375 PHD 11 04 0788 Screw 6 32 x 438 BHD PH 12 05 2190 Plug Fascia 13 81 0307 Pin Doo...

Page 40: ...WATER MODULE 1 COOLING FAN 1 2 WAVE PUMP 2 WATER MODULE 2 COOLING FAN 3 4 CPU POS 2 POS 1 REAR INDICATORS 32VDC INPUT RIGHT DOOR LEFT DOOR KEY SWITCH TEMP FOR FUTURE USE TEMP SENSOR RIGHT DOOR LEFT DO...

Page 41: ......

Page 42: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: