background image

18

Checking the Normal PCB Operation

THE ELECTRONIC ICE BANK CONTROL (EIBC)

 

 

Terminal block has AC line voltage and should be covered with tape. Tape should cover bare electrical connections to 

prevent electrical shock.

WARNING

1. 

Turn power OFF or insure that power has been               

disconnected from dispenser

2. 

Check condition of 0.5 amp fuse at location shown in      

diagram to the right. If fuse is blown, trace cause of short 

in valve wire harness and associated 24 VAC lines and 

replace fuse. If fuse is good, continue with next step.

3.  Disconnect leads from the terminal block that connect to the 

PCB, noting their specific location for reconnection.

4.  Disconnect both the Ice Bank probe (J2) and the            

Carbonator probe (J3) (if equipped) connections from 

board.

5. 

Use a short copper wire, paper clip, or other means to short 

the Ice Bank probe terminals (J2) on the PCB by touching 

all three (3) pins together.

6.  Set Ohm test meter to measure continuity.
7. 

Reconnect power or turn dispenser ON.

8. 

Observe time and check continuity of the PCB screw lug 

connections:

9.  Turn electrical power OFF for 15 seconds and then back ON again to reset Carbonator timer. Again, measure continuity of the 

PCB screw lug connections

• 

Terminal 3 to 4 (Carbonator): During the first 2.5 to 

3.5 minutes there should be continuity. After 2.5 to 3.5 

minutes, there should be NO continuity.

• 

Terminal 2 to 1 (Compressor): During first 4 to 6 

minutes, there should be NO continuity. After 4 to 6 

minutes, there should be continuity. There should be 

NO continuity from 2 to 1. 

• 

You should be able to hear a “click” sound of the relay   

closing when the time delay ends.

• 

Terminal 3 to 4: There should be continuity. Use a short copper wire, paper clip, or other means to short the Carbonator 

probe terminals (J3) on the PCB by touching all three (3) pins together. This should be done before the 2.5 to 3.5 minute 

time limit has elapsed. Measure the continuity again between Terminal 3 to 4: There should be 

NO

 continuity.

10. 

If all the above work as noted, then the board is functioning properly. Remove tape and reconnect board. If any non-conformities 

are found, the PCB must be replaced (PN 52-1423/01).

Summary of Contents for CED Series 1500

Page 1: ...trademark of Lancer 2016 by Lancer all rights reserved 1500 Lancer Corporation 6655 Lancer Blvd San Antonio Texas 78219 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lan...

Page 2: ...A 24 25 Refrigeration Deck Assembly Export 26 27 Wiring Diagram USA 28 Control Housing Connections 28 Wiring Diagram International 29 Plumbing Diagram 5 Valve and 6 Valve 29 SAFETY NOTICES READ ALL SA...

Page 3: ...as a substitute for unplugging the dispenser from the power source to service the unit Only qualified personnel should service internal components of electrical control housing WARNING Make sure that...

Page 4: ...cm A Bonnet B Splash Plate C Cup Rest D Drip Tray A B C D This unit emits a sound pressure level below 70 dB DIMENSIONS Width 19 2 inches 487 mm Depth 24 inches 610 mm Height w out legs 25 4 inches 64...

Page 5: ...Lancer PN 82 3401 or MC 163172 Water Regulator recommended CONSIDER THE FOLLOWING BEFORE INSTALLATION Location of Water Supply Lines Location of Drain Location of Electrical Outlet Location of Heating...

Page 6: ...ing Preparing a Counter Location Failure to maintain specified clearance will cause the compressor to overheat and will result in compressor failure ATTENTION 6 15 1 The dispenser is designed to sit o...

Page 7: ...illed water mixture 8 Flush water supply line thoroughly The water bath compartment must be filled with water before plugging in the unit otherwise the compressor fan may not operate properly ATTENTIO...

Page 8: ...yrup pumps and install another tee fitting 5 Attach line from carbonator CO2 inlet to tee fitting between syrup pumps and CO2 supply A Tee Fitting B Line to Syrup Pump C Fitting D Line to CO2 Supply A...

Page 9: ...egulator Adjustment Screw A B C 4 Turn on water source then purge water to fill carbonator tank by opening carbonator relief valve Close relief valve once water begins to comes out of relief valve 5 A...

Page 10: ...water flow rate 5 oz in 4 sec Use a screwdriver to adjust if needed 4 Remove nozzle by twisting counter clockwise and pulling down then remove diffuser by pulling down 5 Install Lancer yellow syrup s...

Page 11: ...NING AND SANITIZING Lancer equipment new or reconditioned is shipped from the factory cleaned and sanitized in accordance with NSF guidelines The operator of the equipment must provide continuous main...

Page 12: ...water 3 Activate each valve to fill the lines with warm water and flush out syrup remaining in the lines 4 Prepare Cleaning Solution described on previous page 5 Place syrup lines with BIB connectors...

Page 13: ...flow control 5 Bad syrup pump 1 Adjust CO2 pressure to 80 PSI 0 550 MPA minimum 70 PSI 0 480 MPA for BIB pumps 2 Replace CO2 tank refill 3 Open shutoff fully 4 Remove syrup flow control form upper bo...

Page 14: ...3 Melt ice bank Remove all water Refill Locate possible syrup leak area and repair 4 Reposition water cage 5 Find leak and recharge unit If unit is not frozen 6 Turn water ON and shut unit OFF 7 Turn...

Page 15: ...t water supply 3 Refrigeration system not running 4 Refrigerant leak 5 Condenser fan motor not working 6 Dirty condenser 7 Dispenser capacity exceeded 1 Check clearances around sides top and inlet of...

Page 16: ...ow 90 of rated voltage 2 Refer to wiring diagram and correct 3 Replace starting relay Be sure to use correct relay Failure to use correct relay will cause compressor failure Compressor starts and runs...

Page 17: ...lace syrup supply 3 Fasten connector tightly 4 Straighten or replace lines 5 Replace BIB pump BIB pump operated but no flow 1 Leak in syrup inlet or outlet line 2 Defective BIB pump check valve 1 Repl...

Page 18: ...enser ON 8 Observe time and check continuity of the PCB screw lug connections 9 Turn electrical power OFF for 15 seconds and then back ON again to reset Carbonator timer Again measure continuity of th...

Page 19: ...onment from improper disposal recycle the unit by locating an authorized recycler or contact the retailer where the product was purchased Comply with local regulations regarding disposal of the refrig...

Page 20: ...20 Cabinet Assembly High Performance ILLUSTRATIONS AND PART LISTINGS 3 29 2 1 32 31 7 6 11 8 9 10 27 16 33 34 23 24 22 18 20 19 21 13 15 17 15 14 12 5 37 25 26 36 35 4 6 30 28 8...

Page 21: ...onnector Housing 21 23 0389 Faucet Plate 6V 23 0394 Faucet Plate 5V 23 0771 Faucet Plate 4V 22 30 6644 Splash Plate without Logo 30 6644 01 Splash Plate with Logo 23 23 0159 Cup Rest 24 54 0017 Drip T...

Page 22: ...22 Cabinet Assembly 1500E and Pre Mix 27 23 5 4 6 4 7 2 32 12 33 34 35 22 1 24 12 12 30 31 12 20 19 12 13 11 26 21 3 28 11 8 29 14 17 18 16 15 14 10 9 25 6...

Page 23: ...Premix Valve 19 0258 Valve Premix Becker 18 30 6644 Splash Plate without Logo 30 6644 01 Splash Plate with Logo 19 23 0159 Cup Rest 20 54 0017 Drip Tray 21 12 0097 Key Lock Switch 22 52 0891 Harness A...

Page 24: ...RTA NT WA TER BAT H FIL L HO LE BL BL W BL W BL TO JUNCTION BOX 39 37 T O 3 2 4 25 38 6 5 26 1 27 2 3 16 28F 19 TO 42 TO 18 18 TO 11 28G 17 43 23 9 44 15 30 41 29G 29 32 TO 4 TO 18 5 22 40 40A 40B 12...

Page 25: ...otor Fan 115V 60Hz 9W 28D 30 5845 Bracket Fan Motor 28E 07 0354 Fan Blade 28F 06 0433 01 Label 115V 60Hz 9W 28G 04 0059 Screw 8 36 x 0 375 29 52 1259 Agitator Motor Assy 115V 60Hz 25W 29A 91 0084 Moto...

Page 26: ...IMPOR TANT FILL WATER BATH UNTIL TANK OVERF LOW TUBE WATER FLOWS FROM TO TRANSFORMER LOAD TO COMPRESSOR TO TRANSFORMER LINE TO VALVES TO KEYLOCK 39 6 3 37 25 4 37 38 1 5 26 T O 3 2 2 TO 18 28A 28E 28B...

Page 27: ...D 30 5845 Bracket Fan Motor 28E 07 0354 Fan Blade 28F 06 0670 Label 230V 50 60Hz 06 0433 01 Label 115V 60Hz 28G 04 0059 Screw 8 36 x 0 375 29 52 1259 Agitator Motor Assy 115V 60Hz 52 1379 Agitator Mot...

Page 28: ...ITATOR MOTOR WHITE BLACK GREEN KILL SWITCH JCT COMPRESSOR LANCER ICE BANK CONTROL PROBE L RELAY S M M S FAN MOTOR C OVERLOAD WHEN STARTING UNIT OR IF CURRENT IS INTERRUPTED THERE IS A FIVE 5 MINUTE DE...

Page 29: ...3 TERM2 TERM1 B B W AGITATOR MOTOR COMPRESSOR DESCRIPTION CHASSIS GROUND CONTROL BOX CHAMFER PIN 1 PLAIN BLK RIBBED BLK 3 1 G G B W G B G ICE PROBE OPTIONAL MERCHANDISER FAN MOTOR LABEL WIRING DIAGRAM...

Page 30: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: