background image

8

 

Following sanitization, rinse with end-use product  

 

until there is no aftertaste. Do not use a fresh water    

 

rinse. This is a NSF requirement. Residual sanitizing    

 

solution left in the system creates a health hazard.

CAUTION

11. 

Disconnect CO

2

 line and syrup line from tank filled with 

cleaning solution then reattach lines to tank filled with water 

and pressurize.

12. 

Activate valve to flush cleaning solution from the line.

13. 

Disconnect CO

2

 line and syrup line from tank filled with water 

then fill a seperate tank with sanitizing solution.

14.  Connect both CO

2

 and syrup lines to tank filled with          

sanitizing solution and pressurize.

15. 

Activate valve to fill line with sanitizing solution then let stand 

for ten (10) minutes.

16.  Disconnect lines from the sanitizer tank and reattach to    

syrup tank and pressurize. 

THE ELECTRONIC ICE BANK CONTROL (EIBC)

Checking for Normal PCB Operation

9. 

Turn electrical power OFF for 15 seconds and then back ON again to reset Carbonator timer. Again, measure continuity of the PCB 

screw lug connections

• 

Terminal 3 to 4 (Carbonator): During the first 2.5 to 3.5 minutes there should be continuity. After 2.5 to 3.5 minutes, there 

should be NO continuity.

• 

Terminal 2 to 1 (Compressor): During first 4 to 6 minutes, there should be NO continuity. After 4 to 6 minutes, there should be 

continuity. There should be NO continuity from 2 to 1. 

• 

You should be able to hear a “click” sound of the relay   closing when the time delay ends.

10. 

If all the above work as noted, then the board is functioning properly. Remove tape and reconnect board. If any non-conformities 

are found, the PCB must be replaced (PN 52-1423/01).

• 

Terminal 3 to 4: There should be continuity. Use a short copper wire, paper clip, or other means to short the Carbonator probe 

terminals (J3) on the PCB by touching all three (3) pins together. This should be done before the 2.5 to 3.5 minute time limit 

has elapsed. Measure the continuity again between Terminal 3 to 4: There should be 

NO

 continuity.

 

Terminal block has AC line voltage and should be 

covered with tape. Tape should cover bare electrical 

connections to prevent electrical shock.

WARNING

1.  Turn power OFF or insure that power has been disconnected 

from dispenser

2.  Check condition of 0.5 amp fuse at location shown in          

diagram to the right. If fuse is blown, trace cause of short in 

valve wire harness and associated 24 VAC lines and replace 

fuse. If fuse is good, continue with next step.

3. 

Disconnect leads from the terminal block that connect to the 

PCB, noting their specific location for reconnection.

4. 

Disconnect both the Ice Bank probe (J2) and the carbonator 

probe (J3) (if equipped) connections from board.

5.  Use a short copper wire, paper clip, or other means to short 

the Ice Bank probe terminals (J2) on the PCB by touching all 

three (3) pins together.

6. 

Set Ohm test meter to measure continuity.

7. 

Reconnect power or turn dispenser ON.

8.  Observe time and check continuity of the PCB screw lug 

connections:

 

17.  Draw drinks and refill line with end use product to flush    

sanitizing solution from the line. 

18. 

Taste the drink to verify that there is no off-taste. If off-taste 

is found, flush syrup system again. 

19. 

Repeat procedure for each valve/syrup tank. 

Summary of Contents for 2500 REMOTE series

Page 1: ...trained personnel Applicable safety precautions must be observed Instruction warnings on the product being used must be followed Intended Use Check the dispenser name plate label located behind the sp...

Page 2: ...TINGS Water from Carbonator Inlet 3 8 barb Plain Water Inlet 3 8 barb Brand Syrup Inlets 3 8 barb ELECTRICAL 230 240 VAC 50 60 Hz 2 6 Amps PLAIN WATER SUPPLY Min Flowing Pressure 25 PSI 0 172 MPA Max...

Page 3: ...lled water and stir 1 The unit is designed to sit on a flat supported surface capable of supporting a minimum weight of 400 lbs 182 kg Select a location that is in close proximity to a properly ground...

Page 4: ...ing to length between the pump CO2 inlets then connect tubing to all pumps Installation to Dispenser 1 Determine the appropriate length of insulated python tubing required allowing additional length a...

Page 5: ...k CO2 inlet 2 Using tubing cutters cut line from CO2 inlet to figal syrup tank and install tee fitting then route appropriate tubing from second figal syrup CO2 inlet to tee fitting 3 Repeat step 2 fo...

Page 6: ...it 15 Re attach bonnet and front plate 16 Activate each valve until a steady flow of carbonated water is achieved DO NOT TURN ON CO2 SUPPLY AT THIS TIME WARNING A CO2 Regulator B Screwdriver C Loosene...

Page 7: ...ype and concentration of sanitizing agent recommended in the instructions by the manufacturer shall comply with 40 CFR 180 940 The solution must provide 100 parts per million PPM chlorine e g Sodium H...

Page 8: ...ard is functioning properly Remove tape and reconnect board If any non conformities are found the PCB must be replaced PN 52 1423 01 Terminal 3 to 4 There should be continuity Use a short copper wire...

Page 9: ...9 WIRING DIAGRAM WHITE 18 AWG COMP DECK OUTLET POWER CORD GND WHITE 18 AWG CARB OUTLET WHITE 18 AWG RECIRC OUTLET WHITE 18 AWG ON LIGHT RECIRC SWITCH WHITE 18 AWG CARB SWITCH BLACK 18 AWG...

Page 10: ...RB S1 S6 S5 S4 S3 S2 SODA OUT WATER OUT SODA RECIRC S1 S2 S3 S4 S5 S6 THERMO SODA W SODA S1 W S2 S3 S4 S5 S6 S6 S5 S4 S3 S2 S1 REFRIGERATION UNIT WATER IN CO2 IN OUT IN SYRUP OUT WATER IN RECIRC PUMP...

Page 11: ...11...

Page 12: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: