background image

6

 

Pump Motor will run for a few seconds to fill carbonator 

tank

NOTE

6. 

Using a wrench, loosen lock nut on the regulator adjustment 

screw of the high pressure CO

2

 regulator connected to the 

source, then using a screwdriver back out lock nut screw all 

the way.

7.  Repeat Step 6 for both low pressure CO2 regulators on the 

regulator manifold routed to the unit and the syrup pumps.

8. 

Purge the water to fill carbonator tank by opening carbonator 

relief valve. Close relief valve once water begins to comes 

out of relief valve. 

9.  Activate each valve on the dispenser until a steady flow of 

water is achieved.

10. 

Unplug the unit then unplug the Pump Motor Connector from 

the control box. Use the wiring diagram on the unit control 

box for reference. 

11.  Turn on CO

2

 and using a screwdriver, adjust regulator to 75 

PSI (0.517 MPA) then tighten lock nut with wrench. 

12.  Adjust both of the low pressure regulators on the regulator 

manifold to 75 PSI (0.517 MPA) then tighten locknut with 

wrench.

13. 

Activate each valve until gas-out is achieved. 

14. 

Plug the Pump Motor Connector back into the control box 

then plug in unit. 

15. 

Re-attach bonnet and front plate.

16.  Activate each valve until a steady flow of carbonated water is 

achieved. 

 

DO NOT TURN ON CO

2

 SUPPLY AT THIS TIME

WARNING

A. CO

2

 Regulator

B. Screwdriver

C. Loosened Lock Nut

D. Regulator Adjustment Screw

A

B

C

D

 

Failure to disconnect the motor power supply will 

damage the carbonator motor, the pump and void the 

warranty

ATTENTION

A. Regulator Adjustment Screw

B. Adjust to 75 PSI (0.517 MPA)

C. Wrench

A

B

C

As Needed

• 

Keep exterior surfaces of dispenser (include drip tray and cup rest) clean using a clean, damp cloth.

Daily

• 

With a clean cloth and warm water, wipe off all of the unt’s exterior surfaces. 

DO NOT USE ABRASIVE 

SOAPS OR STRONG DETERGENTS.

Weekly

• 

Taste each product for off tastes.

• 

Remove the unit’s bonnet and check the level of water in the water bath. Replenish as required, and 

replace the bonnet.

Monthly

• 

Unplug the dispenser from the power source.

• 

Remove the bonnet and clean the dirt from the condenser using a soft brush. 

• 

Replace the bonnet and plug in the unit.

Every Six Months

• 

Clean and sanitize the unit using the appropriate procedures outlined in the Cleaning and Sanitizing     

section of this guide.

Yearly

• 

Clean water bath interior, including evaporator coils and refrigeration components.

• 

Clean the entire exterior of the unit.

SCHEDULED MAINTENANCE

Summary of Contents for 2500 REMOTE series

Page 1: ...trained personnel Applicable safety precautions must be observed Instruction warnings on the product being used must be followed Intended Use Check the dispenser name plate label located behind the sp...

Page 2: ...TINGS Water from Carbonator Inlet 3 8 barb Plain Water Inlet 3 8 barb Brand Syrup Inlets 3 8 barb ELECTRICAL 230 240 VAC 50 60 Hz 2 6 Amps PLAIN WATER SUPPLY Min Flowing Pressure 25 PSI 0 172 MPA Max...

Page 3: ...lled water and stir 1 The unit is designed to sit on a flat supported surface capable of supporting a minimum weight of 400 lbs 182 kg Select a location that is in close proximity to a properly ground...

Page 4: ...ing to length between the pump CO2 inlets then connect tubing to all pumps Installation to Dispenser 1 Determine the appropriate length of insulated python tubing required allowing additional length a...

Page 5: ...k CO2 inlet 2 Using tubing cutters cut line from CO2 inlet to figal syrup tank and install tee fitting then route appropriate tubing from second figal syrup CO2 inlet to tee fitting 3 Repeat step 2 fo...

Page 6: ...it 15 Re attach bonnet and front plate 16 Activate each valve until a steady flow of carbonated water is achieved DO NOT TURN ON CO2 SUPPLY AT THIS TIME WARNING A CO2 Regulator B Screwdriver C Loosene...

Page 7: ...ype and concentration of sanitizing agent recommended in the instructions by the manufacturer shall comply with 40 CFR 180 940 The solution must provide 100 parts per million PPM chlorine e g Sodium H...

Page 8: ...ard is functioning properly Remove tape and reconnect board If any non conformities are found the PCB must be replaced PN 52 1423 01 Terminal 3 to 4 There should be continuity Use a short copper wire...

Page 9: ...9 WIRING DIAGRAM WHITE 18 AWG COMP DECK OUTLET POWER CORD GND WHITE 18 AWG CARB OUTLET WHITE 18 AWG RECIRC OUTLET WHITE 18 AWG ON LIGHT RECIRC SWITCH WHITE 18 AWG CARB SWITCH BLACK 18 AWG...

Page 10: ...RB S1 S6 S5 S4 S3 S2 SODA OUT WATER OUT SODA RECIRC S1 S2 S3 S4 S5 S6 THERMO SODA W SODA S1 W S2 S3 S4 S5 S6 S6 S5 S4 S3 S2 S1 REFRIGERATION UNIT WATER IN CO2 IN OUT IN SYRUP OUT WATER IN RECIRC PUMP...

Page 11: ...11...

Page 12: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: