8.5 75H Heater Maintenance Schedule and Log
Location:
Have this record available when calling for support.
Unit ID:
Service
Schedule
Initial and Date of Service:
Clean ash from heat exchanger, flue,
damper, and draft gauge probe
Every 1,000 hours of
operation
or Annually
Remove and clean in-tank fill strainer
As needed.
Drain fluid (water) from bottom of tank
Check monthly, drain as
necessary.
Remove and clean in-tank fuel pickup
strainer
As needed - indicated by
vacuum gauge.
Clean fuel tank
As needed or required by
code.
Clean fan
Annually
Clean nozzle line assembly
Annually
Check retention head & electrode settings
Annually
Clean solenoid valve
Annually
Check air compressor pressure
performance, replace filter.
Annually
Clean cad cell lens
Annually
Check/replace burner gasket
Annually
Test fire furnace after maintenance and
check for proper burner adjustment
After Annual Maintenance
Gauge Readings (After Maintenance)
Pump Vacuum Reading:
Pump Pressure Reading:
Draft Gauge Reading:
Hour Meter Reading:
Service Company:_______________________________
Contact: ___________________________
Address: ______________________________________
Phone: ____________________________
* This schedule is the minimum recommended. If you see smoke or have trip-outs then the unit must be shut down and serviced immediately. Increase the maintenance as your situation requires.
Summary of Contents for MX 75
Page 2: ......
Page 41: ...8 Appendices 8 1 Wiring Diagram ...
Page 42: ......
Page 43: ...34 Call 1 888 370 6531 for Technical Support 8 2 Primary Control Instructions ...
Page 44: ...35 Call 1 888 370 6531 for Technical Support Not used with RES 75 kBTU h units ...
Page 45: ...36 Call 1 888 370 6531 for Technical Support No latch up with RES 75 kBTU h units ...
Page 46: ...37 Call 1 888 370 6531 for Technical Support ...
Page 54: ...45 Call 1 888 370 6531 for Technical Support 9 ...