TECHNICAL SPECIFICATIONS
ECO PRO
20/2
Output
min
101
kW
max
260
kW
Flow
min
8,5
kg/h
max
21,8
kg/h
Functioning
Two stages
Fuel
Light oil
Max Viscosity at 20°C
1,5 °E - 6 CSt - 41 sec; R1
Electrical power supply
230/50 o 60 single-phase
V/Hz
1 stage / 2 stage pump calibration
10 / 18
bar
Motor
250
W
Max. absorbed power
380
W
Condenser
8
μF
Trasformator (voltage / secondary current)
26 / 48
kV/mA
Electric protection rating
20
IP
Noise level *
74
dB(A)
60° nozzle with vacuum / half-empty cone
4,50
GPH
Peso
21
kg
* Sound pressure measured in the manufacturer’s combustion laboratory, with burner operating on a test boiler
and at maximum output..
INSTALLATION ON TO THE BOILER
4
3
2
1
5
6
Insert the flange
2
in the burner nozzle with the insulating gasket
4
and fitting the insulating
cord
5
. Insert the burner in the boiler so that the nozzle enters the combustion chamber ac
-
cording to the boiler manufacturer’s instructions. Tighten the 2 screws
1
to secure the burner.
Fix the flange
2
to the boiler with the 4 screws
3
. From inside the boiler, refit the post-ventila
-
tion terminal
6
with the screws supplied.