TITAN
115
EN
cod. 3541Z410 - Rev 01 - 09/2022
Configuration - Parameters Menu
19 parameters are available, indicated by the letter
“b”
, which are not modifiable from Remote Timer Control.
Table 4- Parameters - Configuration
Notes
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is mo-
dified.
Parameter
Description
Range
b01
Gas type selection
Natural Gas/LPG
Natu-
ral gas
b02
Boiler type selection
1 =
Heating only
2 =
Combi with storage tank with double pump
3 =
Combi with storage tank with diverter valve
4 ÷ 9 =
Not used
1
b03
System water pressure protection selection
0 = Pressure switch
1 = Flow switch 1 sec
2 = Flow switch 3 sec
3 = Flow switch 5 sec
4 = Flow switch 10 sec
5 = Pressure transducer
0
b04
Fan max. frequency in DHW
0-255 Hz
210 Hz
b05
Fan max. frequency in heating
0-255 Hz
210 Hz
b06
Fan min. frequency in DHW/heating
0-255 Hz
60 Hz
b07
Fan min. Frequency Offset
0-255 Hz
40 Hz
b08
Variable output Relay operation selection
0=Burner lit
1=Legionella pump
2=Boiler room ventilation
3=Motor-operated shutoff valve
0
b09
Post-Ventilation
0-120 seconds
30
b10
Boiler room pre-ventilation
1-15 minutes
1
b11
Boiler room post-ventilation
1-15 minutes
1
b12
Fume sensor
OFF = Deactivated,
ON = Enabled
OFF
b13
Not implemented
0 ÷ 90 °C
45
b14
Fumes Max Temperature
0-125°C
110
b15
Fan type selection
--
--
b16
Pump antiblock operation time
0-20 seconds
5
b17
High voltage input
0
= Remote reset
1
= Disable all modules
2
= Not used
3
= Enable heating request
0
b18
Password
0 ÷ 999
418
b19
Module Activation
ON-OFF
ON