5. TECHNICAL DATA AND CHARACTERISTICS
Table. 9 - Key of figures cap. 5
5.1 General view and main components
fig. 18 - General view TAURA D 24 MCS
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F11
DHW sensor fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
A16
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
F20
Combustion control fault
Fan fault
Check the fan and fan wiring
Faulty baffle
Check the baffle and replace it if nec-
essary
Flue obstructed or not correctly
sized
Check the flue
A21
Poor combustion fault
Fault F20 generated 6 times in the
last 10 minutes
See fault F20
A23
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
A24
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary
F34
Supply voltage under 180V. Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Water pressure switch damaged
or not connected
Check the sensor
F39
External probe fault
Probe damaged or wiring shorted
Check the wiring or replace the sen-
sor
Probe disconnected after activat-
ing the sliding temperature
Reconnect the external probe or disa-
ble the sliding temperature
A41
Sensor positioning
Delivery sensor or DHW sensor
detached from the pipe
Check the correct positioning and
operation of the sensors
F42
Heating sensor fault
Sensor damaged
Replace the sensor
F43
Exchanger protection acti-
vation.
No system H
2
O circulation
Check the circulating pump
Air in the system
Vent the system
F50
Gas valve fault
Modulating Operator wiring dis-
connected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
A51
Poor combustion fault
Inlet/exhaust flue obstruction
Check the flue
Fault
code
Fault
Possible cause
Cure
5
Sealed chamber
29
Fume outlet manifold
7
Gas inlet
32
Heating circulating pump
8
Domestic hot water outlet
36
Automatic air vent
9
Cold water inlet
38
Flowswitch
10
System delivery
42
DHW temperature sensor
11
System return
44
Gas valve
14
Safety valve
56
Expansion tank
16
Fan
72
Room thermostat (not supplied)
19
Combustion chamber
74
System filling cock
20
Burner assembly
81
Ignition and detection electrode
21
Main nozzle
114
Water pressure switch
22
Burner
138
External probe
26
Combustion chamber insulation
139
Room unit
27
Copper exchanger for heating and hot
water
187
Fume baffle
28
Fume manifold
278
Double sensor ( Heating)
56
29
187
42
28
27
19
26
36
16
5
20
21
22
81
114
14
10
8
7
38 9
11
32
44
74
278