1. GENERAL INSTRUCTIONS

Carefully read the instructions contained in this instruction booklet.

After boiler installation, inform the user regarding its operation and give him this
manual, which is an integral and essential part of the product and must be kept with
care for future reference.

Installation and maintenance must be carried out by professionally qualified person-
nel, according to current regulations and the manufacturer's instructions. Do not car-
ry out any operation on the sealed control parts.

Incorrect installation or inadequate maintenance can result in damage or injury. The
Manufacturer declines any liability for damage due to errors in installation and use
or failure to follow the instructions.

Before carrying out any cleaning or maintenance operation, disconnect the unit from
the power supply using the system switch and/or the special cut-off devices.

In case of a fault and/or poor operation, deactivate the unit and do not attempt to
repair it or directly intervene. Contact professionally qualified personnel. Repair/re-
placement of the products must only be carried out by professionally qualified using
original spare parts. Failure to comply with the above could affect the safety of the
unit.

This unit must only be used for its intended purpose. Any other use is considered
improper and therefore dangerous.

The packing materials are potentially hazardous and must not be left within the
reach of children.

The images given in this manual are a simplified representation of the product. In
this representation there may be slight and insignificant differences with respect to
the product supplied.

2. OPERATING INSTRUCTIONS

2.1 Introduction

TAURA D MCS

 is a high-efficiency heat generator for heating and domestic hot water

production, running on natural gas, equipped with an open-flue burner with electronic ig-
nition, sealed chamber with forced ventilation, and microprocessor control system, de-
signed for installation indoors or outdoors in a partially protected place (in compliance
with EN 297/A6) for temperatures to -5°C.

2.2 Control panel

Panel

fig. 1 - Control panel

Panel key fig. 1

1

DHW temperature setting decrease button

2

DHW temperature setting increase button

3

Heating system temperature setting decrease button

4

Heating system temperature setting increase button

5

Display

6

"Sliding Temperature" Menu - Summer/Winter mode selection - Reset button

7

Unit On/Off - Economy/Comfort mode selection button

10

Summer mode

11

Multifunction

12

Eco (Economy) mode

15

Burner lit and actual power level (flashing during combustion fault function)

16

Service Tool connection

17

Water gauge

Indication during operation

Heating

During the heating demand (generated by Room Thermostat or Remote Temperature
Control), the display (detail 11 - fig. 1) shows the actual heating delivery temperature
and, during heating standby time, the message 

“d2”

Domestic hot water (DHW)

During the DHW demand (generated by drawing domestic hot water), the display (detail
11 - fig. 1) shows the actual hot water outlet temperature alternating with the message

“SA”

 (DHW) and, during DHW standby time, the message 

“d1“

.

Fault

In case of a fault (see cap. 4.4) the display (detail 11 - fig. 1) shows the fault code and,
during safety standby times, the messages 

“d3”

 and 

“d4”

.

2.3 Lighting and turning off

Connection to the power supply

During the first 5 seconds the display will also show the card software release.

Open the gas cock ahead of the boiler.

The boiler is now ready to function automatically whenever domestic hot water is
drawn or in case of a heating demand (generated by Room Thermostat or Remote
Temperature Control).

Turning the boiler off and lighting

Press the 

on/off

 button (detail 7 - fig. 1) or 5 seconds.

fig. 2 - Turning the boiler off

When the boiler is turned off, the PCB is still powered. Domestic hot water and heating
are disabled. The antifreeze system remains activated. To relight the boiler, press the

on/off

 button (detail 7 fig. 1) again for 5 seconds.

fig. 3

The boiler will be immediately ready to operate whenever domestic hot water is drawn
or in case of a heating demand (generated by Room Thermostat or Remote Temperature
Control)

B

The antifreeze system does not work when the power and/or gas to the unit are
turned off. To avoid damage caused by freezing during long idle periods in win-
ter, it is advisable to drain all water from the boiler, DHW circuit and system; or
drain just the DHW circuit and add a suitable antifreeze to the heating system,
complying with that prescribed in sec. 3.3.

2.4 Adjustments

Summer/Winter Switchover

Press the 

summer/winter

 button (detail 6 - fig. 1) for 2 seconds.

The display activates the Summer symbol (detail 10 - fig. 1): the boiler will only deliver
domestic hot water. The antifreeze system remains activated.

To deactivate the Summer mode, press the 

summer/winter

 button (detail 6 - fig. 1)

again for 2 seconds.

Heating temperature adjustment

Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a min. of
30°C to a max. of 85°C; it is advisable not to operate the boiler below 45°C. 

fig. 4

Hot water temperature adjustment

Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of
40°C to a max. of 50°C.

fig. 5

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.

ECO/COMFORT selection

The unit has a function that ensures a high domestic hot water delivery speed and max-
imum comfort for the user. When the device is activated (COMFORT mode), the water
contained in the boiler is kept hot, thereby ensuring immediate availability of hot water
on opening the tap, without waiting times.

The user can deactivate the device (ECO mode) by pressing the 

eco/comfort

 button

(detail 7 - fig. 1). In ECO mode the display activates the ECO symbol (detail 12 - fig. 1).
To activate the COMFORT mode, press the 

eco/comfort

 button (detail 7 - fig. 1) again.

bar

5

1

2

10 15 7

11 3

4 12 16 6

17

| |

||

||

|||

||

||

||

|

| ||

||

|||

|||

|||

Summary of Contents for TAURA D 24 MCS

Page 1: ...NS D UTILISATION D INSTALLATION ET D ENTRETIEN INSTRUC IUNI DE UTILIZARE INSTALARE I NTRETINERE D 24 MCS 24 5 30 24 5 24 5 30 700 400 D 32 MCS 700 400 110 85 763 700 63 110 120 60 61 59 80 5 145 A B C...

Page 2: ...itaria il display part 11 fig 1 visualizza l attuale temperatura d uscita dell acqua calda sanitaria alter nata alla scritta SA sanitario e durante il tempo di attesa sanitario la scritta d1 Anomalia...

Page 3: ...i foratura Il fissaggio alla parete deve garantire un sostegno stabile ed efficace del generatore A Se l apparecchio viene racchiuso entro mobili o montato affiancato lateralmen te deve essere previst...

Page 4: ...collegamento con tubi separati Aria Fumi Tabella 4 Tipologia Per il collegamento dei condotti separati montare sull apparecchio il seguente accesso rio di partenza fig 12 Accessorio di partenza per c...

Page 5: ...cnici in base al tipo di gas Collegare un idoneo manometro alla presa di pressione B posta a valle della val vola gas Attivare la modalit TEST vedi cap 4 1 Premendo il tasto Eco Comfort per 2 secondi...

Page 6: ...scald circolatore b03 Selezione tipo camera combustione 0 Camera Stagna controllo combustione senza PF 0 Camera Stagna con controllo combustione 1 Camera Aperta con TF 2 Camera Stagna con PF 3 Camera...

Page 7: ...Verificare la corretta programmazione dei parametri ed eseguire le eventuali perso nalizzazioni richieste curva di compensazione potenza temperature ecc 4 3 Manutenzione Controllo periodico Per manten...

Page 8: ...a di rete anomala Problemi alla rete elettrica Verificare l impianto elettrico F37 Pressione acqua impianto non corretta Pressione troppo bassa Caricare impianto Pressostato acqua non collegato o dann...

Page 9: ...G20 m3 h 2 73 3 64 Portata gas min G20 m3 h 0 88 1 22 Ugelli bruciatore G31 n x 11 x 0 79 15 x 0 79 Pressione gas alimentazione G31 mbar 37 37 Pressione gas max al bruciatore G31 mbar 35 0 35 0 Press...

Page 10: ...32 MCS A GPL B METANO Perdite di carico prevalenza circolatori fig 24 Perdite di carico prevalenza circolatori TAURA D 24 MCS fig 25 Perdite di carico prevalenza circolatori TAURA D 32 MCS A Perdite...

Page 11: ...Schema elettrico fig 26 Circuito elettrico A Attenzione Prima di collegare il termostato ambiente o il cronocomando re moto togliere il ponticello sulla morsettiera 81 1kW L N 230V 50 Hz 16 N L 32 L...

Page 12: ...lternada con la indicaci n SA sanitaria adem s del c digo d1 durante el tiempo de espera Anomal a En caso de anomal a v ase cap 4 4 la pantalla 11 fig 1 muestra el c digo de fallo y d3 y d4 durante el...

Page 13: ...ble A Si el aparato se instala dentro de un mueble o se adosa a otros elementos ha de quedar un espacio libre para desmontar la carcasa y realizar las actividades normales de mantenimiento 3 3 Conexio...

Page 14: ...os separados aire humos Tabla 4 Tipo Para conectar los conductos separados montar en el equipo el siguiente accesorio ini cial fig 12 Accesorio inicial para conductos separados Antes de efectuar la in...

Page 15: ...te 2 segundos se accede al modo Calibra ci n de la v lvula del gas La tarjeta se dispone en la configuraci n del par metro q02 y al presionar la te clas del agua sanitaria muestra el valor actualmente...

Page 16: ...ea bit r mica 2 instant nea monot rmica 3 Solo calef v lv 3 v as 4 Solo calef bomba de circulaci n b03 Selecci n del tipo de c mara de com busti n 0 c mara estanca control combusti n sin PH 0 c mara e...

Page 17: ...ta Verificar la programaci n de los par metros y efectuar los ajustes necesarios curva de compensaci n potencia temperaturas etc 4 3 Mantenimiento Control peri dico Para que el aparato funcione correc...

Page 18: ...ctrica F35 Frecuencia de red an mala Problemas en la red el ctrica Controlar la instalaci n el ctrica F37 Presi n del agua de la ins talaci n incorrecta Presi n demasiado baja Cargar la instalaci n Pr...

Page 19: ...mo gas G20 m3 h 2 73 3 64 Caudal m nimo gas G20 m3 h 0 88 1 22 Inyectores quemador G31 n x 11 x 0 79 15 x 0 79 Presi n de alimentaci n gas G31 mbar 37 37 Presi n m xima en el quemador con G31 mbar 35...

Page 20: ...de carga altura manom trica bombas de circulaci n fig 24 P rdidas de carga altura manom trica bombas de circulaci n TAURA D 24 MCS fig 25 P rdidas de carga altura manom trica bombas de circulaci n TA...

Page 21: ...el ctrico fig 26 Circuito el ctrico A Atenci n Antes de conectar el termostato de ambiente o el reloj programa dor a distancia quitar el puente de la regleta de conexiones 81 1kW L N 230V 50 Hz 16 N...

Page 22: ...e message SA DHW and during DHW standby time the message d1 Fault In case of a fault see cap 4 4 the display detail 11 fig 1 shows the fault code and during safety standby times the messages d3 and d4...

Page 23: ...ng the drilling points on the wall is avail able by request The wall fixing must ensure stable and effective support for the gener ator A If the unit is enclosed in a cabinet or mounted alongside a sp...

Page 24: ...te pipes Air Fumes Table 4 Typology For connection of the separate ducts fit the unit with the following starting accessory fig 12 Starting accessory for separate ducts Before installation check the b...

Page 25: ...to the pressure point B downstream of the gas valve Activate the TEST mode see cap 4 1 Press the Eco Comfort button for 2 seconds to access the gas valve Calibration mode The card goes to the setting...

Page 26: ...switch 0 Sealed Chamber with combustion control 1 Open Chamber with fume thermostat 2 Sealed Chamber with fume pressure switch 3 Sealed Chamber combustion control with fume thermostat on recuperator...

Page 27: ...power temperatures etc 4 3 Maintenance Periodical check To ensure correct operation of the unit over time have qualified personnel carry out a yearly check providing for the following The control and...

Page 28: ...pressure switch damaged or not connected Check the sensor F39 External probe fault Probe damaged or wiring shorted Check the wiring or replace the sen sor Probe disconnected after activat ing the slid...

Page 29: ...5 Max gas delivery G20 m3 h 2 73 3 64 Min gas delivery G20 m3 h 0 88 1 22 Burner nozzles G31 no x 11 x 0 79 15 x 0 79 Gas supply pressure G31 mbar 37 37 Max gas pressure at burner G31 mbar 35 0 35 0 M...

Page 30: ...S A LPG B NATURAL GAS Circulating pump head pressure losses fig 24 Circulating pump head pressure losses TAURA D 24 MCS fig 25 Circulating pump head pressure losses TAURA D 32 MCS A Boiler pressure lo...

Page 31: ...5 Wiring diagram fig 26 Electrical circuit A Attention Before connecting the room thermostat or the remote timer con trol remove the jumper on the terminal block 81 1kW L N 230V 50 Hz 16 N L 32 L N T...

Page 32: ...n r e par le pr l vement d ECS l afficheur 11 fig 1 visualise la temp rature de sortie de l ECS altern e l indication SA sanitaire et pen dant le temps d attente sanitaire l indication d1 Anomalie En...

Page 33: ...Raccordements hydrauliques Avertissements B L vacuation de la soupape de s ret doit tre raccord e un entonnoir d coulement ou une tuyauterie de r cup ration pour viter le d gorgement d eau au sol en c...

Page 34: ...s par s fig 11 Exemples de raccordements avec des conduits s par s Air Fum es Tableau 4 Typologie Pour le raccordement avec des conduits s par s l accessoire suivant doit tre mont au d part de l appar...

Page 35: ...dans le tableau des ca ract ristiques techniques en fonction du type de gaz utilis Relier un manom tre la prise de pression B mont e en aval de la vanne gaz Valider le mode TEST voir cap 4 1 Appuyer 2...

Page 36: ...ateur b03 S lection type chambre de combu stion 0 Chambre tanche contr le de combu stion sans PF 0 Chambre tanche avec contr le de combustion 1 Chambre ouverte avec TF 2 Chambre tanche avec PF 3 Chamb...

Page 37: ...ture d un robinet d eau chaude le circulateur de chauffage s arr te et que l on ait une production r guli re d eau sanitaire V rifier la programmation correcte des param tres et effectuer les personna...

Page 38: ...F35 Fr quence de r seau anor male Probl mes au r seau lectrique V rifier l installation lectrique F37 Pression eau installation incorrecte Pression trop basse Remplir l installation Pressostat non re...

Page 39: ...gaz mini au br leur G20 mbar 1 5 1 5 D bit gaz maxi G20 m h 2 73 3 64 D bit gaz mini G20 m h 0 88 1 22 Gicleurs br leur G31 nbre x 11 x 0 79 15 x 0 79 Pression gaz alimentation G31 mbar 37 37 Pression...

Page 40: ...RA D 32 MCS A GPL B M THANE Pertes de charge pression circulateurs fig 24 Pertes de charge pression circulateurs TAURA D 24 MCS fig 25 Pertes de charge pression circulateurs TAURA D 32 MCS A Pertes de...

Page 41: ...5 Sch ma lectrique fig 26 Circuit lectrique A Attention Avant de brancher le thermostat d ambiance ou la chronocom mande distance d faire le pontage sur le bornier 81 1kW L N 230V 50 Hz 16 N L 32 L N...

Page 42: ...lde menajere alternativ cu mesajul SA ap cald menajer i n intervalul de a teptare pentru ap menajer mesajul d1 Anomalie n caz de anomalie vezi cap 4 4 pe afi aj det 11 fig 1 apare codul de defec iune...

Page 43: ...inclus ntr un corp de mobilier sau montat l ng piese de mobilier trebuie asigurat spa iul pentru demontarea carcasei i pentru de sf urarea activit ilor normale de ntre inere 3 3 Racordurile hidraulice...

Page 44: ...Racordarea cu tuburi separate fig 11 Exemple de racordare cu conducte separate Aer Gaze ar se Tabel 4 Tipologie Pentru racordarea conductelor separate monta i pe aparat urm torul accesoriu de por nir...

Page 45: ...ie de tipul de gaz Racorda i un manometru la priza de presiune B pozi ionat n aval de valva de gaz Activa i modul TEST vezi cap 4 1 Ap s nd pe tasta Eco Comfort timp de 2 secunde se intr n modul Calib...

Page 46: ...lectarea tipului de camer de ardere 0 Camer etan cu control ardere f r PF presostat gaze arse 0 Camer etan cu control ardere 1 Camer deschis cu TF termostat gaze arse 2 Camer etan cu PF presostat gaze...

Page 47: ...ld menajer s fie preparat n condi ii normale Verifica i programarea corect a parametrilor i efectua i eventualele personaliz ri necesare curb de compensare putere temperaturi etc 4 3 ntre inerea Contr...

Page 48: ...nea apei din instala ie nu este corect Presiune prea sc zut Umple i instala ia Presostatul ap nu este conectat sau este defect Verifica i senzorul F39 Anomalie sond extern Sond defect sau scurtcircuit...

Page 49: ...64 Debit gaz min G20 m3 h 0 88 1 22 Duze arz tor G31 nr x O 11 x 0 79 15 x 0 79 Presiune gaz alimentare G31 mbar 37 37 Presiune gaz max la arz tor G31 mbar 35 0 35 0 Presiune gaz min la arz tor G31 mb...

Page 50: ...arcin n l ime de pompare pompe de circula ie fig 24 Pierderi de sarcin n l ime de pompare pompe de circula ie TAURA D 24 MCS fig 25 Pierderi de sarcin n l ime de pompare pompe de circula ie TAURA D 32...

Page 51: ...5 5 Schem electric fig 26 Circuitul electric A Aten ie nainte de a racorda termostatul de camer sau cronocomanda la distan scoate i puntea de pe panoul de borne 81 1kW L N 230V 50 Hz 16 N L 32 L N T...

Page 52: ...7 A6 5 C 2 2 1 1 1 2 3 4 5 6 7 10 11 12 Eco 15 16 17 11 1 d2 11 1 SA d1 cap 4 4 11 1 d3 d4 2 3 5 7 1 5 2 7 1 5 3 B sez 3 3 2 4 6 1 2 10 1 6 1 2 30 C 85 C 1 3 4 45 C 4 1 40 C 50 C 1 2 5 ECO COMFORT COM...

Page 53: ...6 A 1 1 2 7 1 0 F37 1 7 A B 7 3 3 1 3 2 90 396 EN 297 pr A6 5 C A 3 3 B B 25 Fr 1 F 10 CaCO3 3 4 3 5 B Y 3 3 A B HAR H05 VV F 3x0 75 2 8 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4 5 6 8 9 10 7 2...

Page 54: ...6 B C1X C1X C3X C3X C3X C1X C1X C3X 60 100 80 125 5 10 90 1 0 5 45 0 5 0 25 0 2 TAURA D 24 MCS 43 TAURA D 32 MCS 45 0 3 TAURA D 24 MCS 43 TAURA D 32 MCS 45 2 5 3 10 C1X 50 C3X C12 C5X C6X EN 1856 1 B2...

Page 55: ...15 45 15 35 50 35 48 80 0 5 1KWMA38A 0 5 0 5 1 0 1 1KWMA83A 1 0 1 0 2 0 2 1KWMA06K 2 0 2 0 4 0 45 1KWMA01K 1 2 2 2 45 1KWMA65A 1 2 2 2 90 1KWMA02K 2 0 3 0 90 1KWMA82A 1 5 2 5 90 1KWMA70U 1 5 2 5 1KWM...

Page 56: ...0 50 1 60 R B I A S 65 24 b07 b02 1 0 20 5 b02 2 5 b02 3 5 b02 4 5 P01 0 40 10 P02 1 20 C 5 C P03 0 10 2 P04 0 20 6 P05 31 85 C 85 C P06 0 100 100 P07 b02 1 0 0 1 2 5 2 10 2 20 b02 2 0 0 1 2 5 2 10 2...

Page 57: ...Reset Service Reset 20 20 Hi History 11 H1 H10 Service Reset Service Reset 20 20 rE History 3 Eco comfort History Service Service Re set 20 20 4 2 cap 5 4 3 17 1 4 4 11 1 A RESET 6 1 1 RESET F 8 t01...

Page 58: ...F04 F05 A06 F07 A09 F10 1 F11 F14 2 A16 F20 A21 F20 10 F20 A23 A24 F34 180 F35 F37 F39 A41 F42 F43 H 2O F50 A51 5 29 7 32 8 36 9 38 10 42 11 44 14 56 16 72 19 74 20 81 21 114 22 138 26 139 27 187 28 2...

Page 59: ...60 C 93 0 93 1 30 90 5 91 0 92 42 EEC NOx 3 150 NOx G20 x 11 x 1 35 15 x 1 35 G20 20 0 20 0 G20 12 0 12 0 G20 1 5 1 5 G20 3 2 73 3 64 G20 3 0 88 1 22 G31 x 11 x 0 79 15 x 0 79 G31 37 37 G31 35 0 35 0...

Page 60: ...11 Rev 00 5 4 22 TAURA D 24 MCS 23 TAURA D 32 MCS A GPL B 24 TAURA D 24 MCS 25 TAURA D 32 MCS A 1 2 3 B A A B 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H 2 O A 3 2 1 0 1 2 3 4 5 6 7 0 500 1 00...

Page 61: ...TAURA D MCS 61 RU cod 3541A220 01 2011 Rev 00 5 5 26 A 81 1kW L N 230V 50 Hz 16 N L 32 L N T T 278 T 42 4 3 2 1 44 38 114 ABM01 72 139 138...

Page 62: ...declares that this unit complies with the following EU directives Gas Appliance Directive 2009 142 Efficiency Directive 92 42 Low Voltage Directive 73 23 amended by 93 68 Electromagnetic Compatibilit...

Page 63: ......

Page 64: ...GHINI si riserva il diritto di apportare senza obbligo di preavviso tutte le modifiche che ritiene pi opportuno per l evoluzione del prodotto The illustrations and data given are indicative and are no...

Reviews: