33
GB
0,00
1,00
2,00
3,00
4,00
5,00
6,00
7,00
8,00
mbar
0
200
300
400
500
600
kW
TECHNICAL DATA
Model
LMB TWIN 600
Type
Two-stage
Functioning
Intermittent
Regulation
Valve two stage
Maximum heat output
KW
600
Minimum heat output
KW
215
NO
x
class
-
2
Gas category
-
G20
Maximum gas flow rate (15°C - 1013.5 mbar)
m
3
/h
64
Minimum gas flow rate (15°C - 1013.5 mbar)
m
3
/h
23
Electric protection rating
IP
x0D
Motor electric power supply (three phase)
V / Hz
400 / 50-60
*
Auxiliary electric power supply (single phase)
V / Hz
230 / 50
Motor nominal electric power
W
1100
Transformer (voltage/secondary current)
KV / mA
15 / 48
Functioning temperature (min/max)
°C
0 / 40
Noise
dbA
81
Weight of the burner body (without ramp)
Kg
32
U
M
* It is possible the 60 Hz power supply only with suitable electric motor.
WORK CURVE
The work range was obtained at an ambient temperature of 15°0, at an atmospheric pressure of 1013.5 mbar (at
0 metres above sea-level) and with the adjustments recommended in this instruction.