INSTALLATION
The maximum pressure during boiler heating is adjusted via the control panel.
After all the calibration operations have been completed, close and seal the pressure outlet used. Calibration of slow ignition
is electronic and adjustable (for optimisation and gas change) via the control panel.
The boilers leave the factory calibrated and set up to operate with G20 (natural gas) or G30/G31 (LPG).
BURNER PRESSURE CURVE -OUTPUT EFFICIENCY
DESCRIPTION
G20 (natural gas)
G30 (LPG)
G31 (LPG)
Nominal supply pressure
20
28 - 30
37
mbar
Pressure at nozzles
maximum
12,5
27,5
35,2
mbar
minimum
1,2
4
6
mbar
Flow rate
3,74
1,03
1,35
m
3
/h
Burner nozzles
1,35
0,82
0,82
Ø mm
Gas baffle
-
-
-
Ø mm
P.C.I. (*)
8127
29000
22000
kcal/m
3
Wobbe index
34,02
116,09
88
MJ/m
3
Burner pressure
outlet
ALMA 32 MBS W TOP
Slow ignition adjustment:
3 mbar for G20 (natural gas)
7.5 mbar for G30-G31 (LPG)
(*) Temperature: 15°C - Pressure: 1013 mbar.
Permitted adjustment range
(see parameter adjustment).