- 2
-
INSTALLATION
Reduced length in metres
Component
Accessories
80Ø male-female pipe
60Ø 45°elbow
80Ø 90° male-female elbow
Condensate trap
80Ø wind-resistant terminal for combustion products
80Ø air intake protection terminal
80/125 roof vent + TEE reducer for separate ducts
Horizontal
vent
Vertical
vent
Intake
1
1,2
1,5
/
/
2
/
1
3
/
/
1
3
/
/
Image
2,2
2,5
12
Table of reduced flue lengths after fitting pipes and accessories
1 - Fully define the layout of the split stack system, including the accessories and outlet terminals.
2 - Consult the following table and identify the metres by which the flue length is reduced with each component fitted
depending on the installation position.
3 - Check that the total sum of the reduced length is smaller than or equal to the maximum permitted value: 30 m.
WARNINGS
•
Use only and exclusively Lamborghini Caloreclima air intake/flue gas exhaust kits.