320
EN
cod. 3541V620 - Rev. 00 - 05/2021
ALHENA TECH H
VALUE CHECK, the FRONT PANEL must be CLOSED
and the INTAKE/FUME EXHAUST DUCTS completely
assembled. Also, the boiler must not be in OFF mode
(see detail C of fig. 11) and there must be no heating
or DHW circuit request.
Calibration procedure [AUTO SETUP]
1. Access the
parameters menu[TSP]
.
2. Select parameter
b27
with the
and
heating
buttons and set it to
5
with the
and
DHW
buttons.
Confirm with the button
.
Return to the
main menu[MENU]
.
3. Access the
installer menu [Service]
>enter the
Password 1234
(see fig. 17).
Now the
menu for calibration[Auto Set-
up]
is also displayed.
4. Select it and confirm with the button
.
5. The procedure starts automatically find-
ing the optimal ignition point.
6. After ignition, the burner goes to the vari-
ous powers (max, med, min) indicated by
point
(fig. 38).
7. At the end of the sequence the display re-
turns to the Service menu
8. If the ignition sequence described in point
“6”
is not successful, the display shows
the message
max_err
at point
and an
error code at point
(fig. 38).
9. Exit with the button and unlock the
boiler.
Repeat the sequence from point
“1”
.
fig. 38
The
calibration procedure [Auto Setup]
can only be performed if parameter
b27
is set to
5
.
Parameter
b27
can be set manually to the value
5
, or by:
• changing the parameter "
gas type
"
b03
.
• setting parameter
P67
to
1
.
• changing the value of parameter
P68
.
• doing “
Restore Factory Values
” with the parameter
b29=10
(after carrying out this operation,
disconnect and reconnect the power supply for about ten seconds).
In each of the above cases,
b27
automatically changes to
5
.
It is necessary to perform the
calibration procedure [Auto Setup]
in the following cases:
• after replacing the PCB
• after changing the gas
(b03)
• setting parameter
P67
to
1
• after changing the value of parameter
P68
• after setting parameter
b27
to
5
for replacement of components such as the electrode, burner,
gas valve, fan or for installations with maximum flue resistance
• when fault conditions
A01
,
A06 occur or in other faults when required
(see table 11. Re-
spect the sequence of fault solutions).
a
a
c
AUTO SETUP
Step:
Power:
CH temp:
Alarm:
max ...
-- %
22°
none
a
c
Summary of Contents for ALHENA TECH H
Page 45: ...45 IT cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Page 103: ...103 ES cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Page 160: ...160 RO cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Page 217: ...217 PL cod 3541V620 Rev 00 05 2021 ALHENA TECH H wygl d 48 wygl d 49 wygl d 50 5 6 6...
Page 231: ...B 231 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H...
Page 232: ...232 EL B CE IT ES RO PL GR cod 3541V620 Rev 00 05 2021 A ALHENA TECH H 8 8...
Page 238: ...238 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H FH Fh 2 10 0 FH 2 Stop...
Page 249: ...249 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 3 27 27 b09 1 1 2bar 0 7bar F37 3...
Page 250: ...250 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 2 2 1 2 2 B 2009 142 5 C 15 C A 2 3 B...
Page 253: ...253 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 2 5 B B 3 mm 3A...
Page 254: ...254 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H B HAR H05 VV F 3x0 75 mm2 8 mm B 230 V...
Page 262: ...262 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H B 2 7 B 0 5 lt B 37...
Page 271: ...271 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 1 41 2 41 B 1 42 42 OK NO 1 1...
Page 273: ...273 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 43 2 43 3 44 4 5 45 43 44 45 1 2 3 4 5...
Page 274: ...274 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H A B 1 2 5 49 2 6 50 5 46 47 1...
Page 275: ...275 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 48 49 50 5 6 6...
Page 276: ...276 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 2 3 4 51 52 1 1 2 2 3 3 4...
Page 277: ...277 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 2 venturi 3 53 54 A 1 2 55 2 1 1 1 2...
Page 330: ...330 EN cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Page 343: ......