54
Troubleshooting
For troubleshooting, use the following:
Alarm status screen
Wiring diagram
Plumbing & Refrigeration Diagram
Troubleshooting table (below)
Issue
Possible Cause
Corrective Measures
Clearance By
Unit does not start Power not applied. Electrical
connection not correct or no
mains connection
Check power supply and ensure proper
voltage in the line. Check connection,
insert mains plug.
Operator
Coolant level too low. Alarm
for low coolant will be active
Check coolant level and top off, if
necessary. Refer to Adding Coolant
Operator
Main switch not turned on
Turn main switch on
Operator
Unit running but
cooling capacity is
too low
Buckled or pinched coolant
hoses
Install the hoses with a larger radius to
avoid sharp bends.
Operator
Improperly placed unit
Required clearance with the wall of the
unit. Refer to
Operator
Blocked Condenser
Operator
Coolant level too low
Check coolant level and top up, if
necessary. Refer t
Operator
Disconnected coolant hoses Connect the coolant hoses. Refer to
Operator
Dirty coolant filter
Clean or replace filter. Refer to
Operator
No flow in cooling circuit
Refer to coolant high/low pressure alarm
condition or optional low flow alarm
condition.
Operator
Fan does not rotate
Check to determine if the fan is rotating. Operator
Ambient air temperature too
high
Operate unit within allowable ambient
temperature range.
Operator
Refrigeration circuit not
working properly
Confirm that all alarm conditions are
cleared.
Operator
Noise
Blocked cooling circuit
Ensure that cooling circuit is not blocked. Operator
Dirty coolant filter
Clean filter strainer. Refer to
Operator
Blocked Condenser
Operator
Summary of Contents for Nextreme Series
Page 1: ...Nextreme Recirculating Chiller Specification and User Manual Part Number 387004848 ...
Page 17: ...17 Component Locations Figure 2 Isometric Views of Unit Figure 3 Top View ...
Page 18: ...18 Figure 4 Front View Figure 5 Rear View Figure 6 Side View ...
Page 39: ...39 Figure 25 Sensor Wiring Low Voltage ...
Page 40: ...40 Plumbing Refrigeration Diagram Figure 26 Plumbing and Refrigeration Diagram ...
Page 43: ...43 Figure 31 Pump Performance of NRC5000 with Cooling Fluids Water and 40 EG W ...
Page 60: ...60 PCFLT Returns FLT fault or NO FAULTS FOUND PCFLT C Clears Fault Returns FLT Faults Cleared ...
Page 69: ...69 Declaration of Conformity ...