12
Pull-out shelves
•
Already built into cabinets
Shelves
•
Already built into cabinets
Please observe the maximum shelf load (see Annex 1)!
If the shelves are not installed in accordance with the assembly instructions then the
maximum shelf load cannot be guaranteed.
Collection trough / Perforated cover plate
The collection troughs in the base of the storeLAB
®
safety cabinet or the pull-out shelves are
intended to collect any liquid leakages inside the cabinet and are not additional support
surfaces for stored containers (see EN 14470-1).
If a perforated cover plate is used for the collection trough / pull-out shelf then this can be used
as additional support surfaces for stored containers.
8.
Storage amounts / Storing substances together
Valid national regulations must be observed.
9.
Ventilation
All safety cabinets have an air inlet and an air outlet connection. The outlet connection (suction
side, connection diameters attached annex 1) is connected to the exhaust system. The exhaust
air is led away through ducting to discharge into the atmosphere at a non-hazardous location.
Inlet air is taken from inside the room. Please observe the valid national rules, regulations and
laws concerning the stipulated rate of air exchange and exhaust air removal. The function of the
ventilation should be checked at regular intervals. (see 13.2)
Safety cabinets as per EN 14470-1 can also be operated without connection to a ventilation system.
(In Germany please observe the requirements of TRGS-510; elsewhere the relevant national rules,
regulations and laws.)
Please remember the following points for operation without connection to a ventilation system:
•
The cabinet must be grounded to avoid electrostatic charges.
•
The area 2.5 m around the safety cabinet up to a height of 0.5 m above floor level is
to be regarded as being a Zone 2 explosion- endangered area.
•
In accordance with the relevant accident prevention regulations (BGV A8), this Zone 2
explosion- endangered area must be clearly and visibly marked with the following
hazard symbol:
The locations of the air inlet and outlet connections are shown under Annex 1 (see drawings).
10.
Grounding
In accordance with BGR 132 (D), all safety cabinets are equipped with a grounding connection
on the cabinet roof as standard. If liquids are transferred within the cabinet then the interior of
the cabinet must be additionally grounded.
E
n
g
li
sh