Operating Instruction BA_029_2019-08_10.00  Pressure transmitter PASCAL CV

Page 5/6

 

BTA-No. 029  1J2  Page 5

After all parameters have been entered, subsequent operation can be disabled as follows: 

-

  Press the "ZERO" and "SPAN" buttons at the same time (approx. 10 seconds). 

 

After write protection has been activated, the “ZERO” and “SPAN” LEDS flash in synchrony four 

times in succession.

Deactivating write protection: 

-

  Press the "ZERO" and "SPAN" buttons at the same time (approx. 10 seconds). 

 

After deactivation, the “ZERO” and “SPAN” LEDS flash in synchrony. 

Parameterizing of Switching Module 

Description of further function modules 

Please check the following table for further information concerning the operating menu of the switching module (grey marked). 

Various function modules can easily be added to PASCAL CV (see table). 

These modules for display and communicating can be exchanged or extended with ease on site without having to recalibrate or 

remove the device from the process (“plug and measure”). Automatic module detection renders programming redundant.  

Note: Modules may only be exchanged/added when the power supply has been switched off! 

parameter

basic module

function modules

variability

standard

4...20 mA PROFIBUS

switching 

module

display 

module

HART

®

-

module

 x  = configurable 

w = factory setting

BTA-No. 029 Rev. 0F3

Modifications reserved 

P. 7

zero point

RANGE / Zero

see instrument ranges

nominal range

x

x

x

x

x

ng span

RANGE / Span

see instrument ranges

nominal range

x

x

x

x

x

ng

DAMP

0.0...120.0 sec.

0.0 sec.

w

x

——

x

x

n-max-values

HI / LO

pressure and temperature 
ressetable

——

——

x

——

x

x

aracteristic

FUNC

linear, table

linear

w

——

——

x

x

nit

UNIT

bar, mbar, kPa, MPa, mmH2O, 
mH2O, kg/cm², psi

bar

w

x

——

x

x

ng circuit 

est

LOOP

3.55...22 mA

——

——

——

——

x

x

larm state

ALARM

< 3.6 mA, > 21.0 mA

< 3.6 mA

w

——

——

x

x

urrent trimming

I-CAL

-2 %...+ 5 %

——

——

——

——

x

x

imming P-CAL

zero point -50...+50% o.n.range
span -10...+10 % of nom. range

——

——

x

——

x

x

able function

TABLE

2...31 points in table

0 % = 4 mA

100 % = 20 mA

——

——

——

x

x

ystem info

INFO

software, serial number
revision level

——

——

x

——

x

x

actory data reset RESET

——

——

——

x

——

x

x

witch points

SWCH1(2)

0.0...100.0 % of nominal range

50 %

——

x

x

x

x

steresis

SWCH1(2)/Hyst.

0.0...100.0 % of nominal range

0,1 %

hyster.falling

——

x

w

x

x

witching function SWCH1(2)/SwTyp

breaker, maker 

breaker

——

x

w

x

x

write protection

——

ON, OFF

OFF

x

x

x

x

x

erating menus

display of display 

module

op

measuri

dampi

mi

ch

pressure u

measuri
t
a

c

pressure tr

t

s

f

s

hy

s

Setting and resetting the write protection (Operating menu: Write Protection)

Error code description

System Errors

W-DOG

ERROR

FLASH

ERROR

BrdGE

ERROR

SnSr

Error in sensor module or this basic module cannot 

nmbr

access the sensor.

bASE

The sensor module has been replaced or there is an error

ChkEr

 in the basic module.

SnSr

ChkEr

Four-Digit Error Code Display 

0

0

0

0

Fourth Digit in Error Code in PASCAL CV Display Module

0

No error.

1

Pressure outside nominal measuring range.

2

Temperature outside specified range.

3

Pressure outside nominal measuring range and temperature outside specified range.

4

Analog output limited to current value.

5

Pressure outside nominal measuring range and analog output limited to current value.

6

Temperature outside specified range and analog output limited to current value.

7

Pressure outside nominal measuring range; temperature outside specified range; 
and analog output limited to current value.

Third Digit in Error Code in PASCAL CV Display Module

0

No error.

8

General device error (always shown with other errors)

Second Digit in Error Code in PASCAL CV Display Module

0

No error.

2

A memory cell in the microprocessor is faulty.

First Digit in Error Code in PASCAL CV Display Module

0

No error.

1

Data in sensor module invalid.

2

Data in basic module invalid.

3

Data in sensor and basic module invalid or do not match.

4

Connected sensor not detected by basic module.

8

Measuring bridge / pressure sensor faulty.

Digits on a gray           background indicate errors that can only be remedied by the manufacturer.
All other issues can be remedied by the customer.

Device software not running correctly.

Device parameters invalid.

Bridge is faulty.

Error in sensor module (compensation table/ set-up data)