BA_078_en_10.01 Level transmitter PASCAL Ci4 LEVEL
Page 21/36
6.5.3.2
"Density" submenue
You can view, change or teach in the density in this submenue. You can also select the
density unit.
Menue item
Description
Description
View / change the density
Teach-in
Teach-in the density
Unit
Select the unit for the density
Table 9: "Density" submenue
Teaching-in the density
You can also teach-in the density on
the tank. A basic requirement is that
the height offset is correctly set and
the fill height (relative to the level ze-
ro) can be determined with sufficient
accuracy.
The device calculates the density
from the measured pressure and the
entered fill height and suggests the
density to be saved.
Figure 19: Teaching-in the density
6.5.3.3
"Height offset" submenue
You can view, change or teach-in the height offset in this submenue. You can also set the
unit for the height offset (and the fill height).
Menue item
Description
View / change
View / change the height offset
Teach-in
Teach-in the height offset
Unit
Select the unit for the height
Table 10: "Height offset" submenue