Normal situation

The level of the liquid being measured is below the high level

sensor (idOil-LIQ), the oil sensor (idOil-OIL) is in water and the

sludge sensor (idOil-SLU) is in water.

The indicator lights for voltage supply, sensor alarms and faults

are green.

 

Relays 1 and 2 are energised.

High liquid level alarm

The liquid level has reached the high liquid level sensor (idOil-

LIQ).

The alarm light of the high liquid level sensor is red.

 

The other indicator lights are green.

 

The buzzer sounds after an approximately 10 second delay.

 

Relay 1 is de-energised after a 10 second delay.

 

Relay 2 stays energised.

Oil alarm

The  oil  layer  has  reached  the  idOil-OIL  sensor's  alarm

switching point.

The alarm light of the oil sensor is red.

 

The other indicator lights are green.

 

The buzzer sounds after an approximately 10 second delay.

 

Relay 1 is de-energised after a 10 second delay.

 

Relay 2 stays energised.

Sludge alarm

The  sludge  level  has  reached  the  idOil-SLU  sensors's  alarm

switching point.

The alarm light of the sludge sensor is red.

 

The other indicator lights are green.

 

The buzzer sounds after an approximately 10 second delay.

 

Relay 1 is de-energised after a 10 second delay.

 

Relay 2 stays energised.

Fault alarm 1

There is a fault in the sensor or sensor cabling.

The voltage supply indicator light is green.

 

The indicator light of a faulty sensor circuit alarm blinks red and

the fault indicator light is red.

 

The buzzer sounds after an approximately 10 second delay.

 

Relay 1 stays energised.

 

Relay 2 is de-energised after a 10 second delay.

Fault alarm 2

There is a short circuit in the sensor or sensor bus.

The voltage supply indicator light is green.

 

The sensor alarm and fault indicator lights are red.

 

The buzzer sounds after an approximately 10 second delay.

 

Relay 1 stays energised.

 

Relay 2 is de-energised after a 10 second delay.

Alarm has stopped

Once  the  alarms  have  stopped,  the  sensor  alarm  indicator

lights  are  green,  the  buzzer  goes  silent  and  the  relays  are

energised after a 10 second delay.

Installation and Operating Instructions | idOil-20

21/34

DOC001600-EN-5

Summary of Contents for idOil-20

Page 1: ...idOil 20 Oil Separator Alarm Device Installation and Operating Instructions EN DOC001600 EN 5 10 12 2018...

Page 2: ...ensor 3 3 4 Dimensions idOil SLU sludge sensor 4 Installation 4 1 Installing the control unit 4 2 Sensor installation 4 2 1 Installing the idOil LIQ high liquid level sensor 4 2 2 Installing the idOil...

Page 3: ...Oil control unit 9 2 Technical specifications idOil LIQ high liquid level sensor 9 3 Technical specifications idOil OIL oil sensor 9 4 Technical specifications idOil SLU sludge sensor 10 Appendices 10...

Page 4: ...an issue that requires special attention during installation and when using the device in an explosive atmosphere Informative markings and symbols This marking highlights essential information This ma...

Page 5: ...counter to the product s purpose of use Labkotec cannot be held liable for any damage caused by using the device in violation of its purpose of use 2 3 Transport and storage Check the packaging and i...

Page 6: ...fe electrical systems i and or IEC EN 60079 14 Explosive atmospheres Electrical installations design selection and erection must all be followed If it is possible that static electricity can cause haz...

Page 7: ...OIL oil sensor Sludge layer detection idOil SLU sludge sensor 1 Control unit idOil 20 2 Cable connector LCJ1 3 3 High liquid level sensor idOil LIQ 4 Oil sensor idOil OIL 5 Sludge sensor idOil SLU A A...

Page 8: ...Sludge sensor to detect the thickness of the sludge layer Accessories Type name Description LCJ1 1 Cable connector for one sensor LCJ1 2 Cable connector for two sensors LCJ1 3 Cable connector for thr...

Page 9: ...re 3 High liquid level sensor idOil LIQ structure and dimensions mm 3 3 3 Dimensions of the idOil OIL oil sensor A Measuring electrode B Reference electrode S Alarm switching point Figure 4 Oil sensor...

Page 10: ...4 Dimensions idOil SLU sludge sensor T Sensor gap S Alarm trigger point Figure 5 Sludge sensor idOil SLU structure and dimensions mm Installation and Operating Instructions idOil 20 10 34 DOC001600 E...

Page 11: ...astening holes 4 5 mm 4 pcs Installation dimensions 160 x 110 mm Figure 6 Installing the idOil control unit 4 2 Sensor installation idOil sensors can be installed in zone 0 explosive atmospheres Do no...

Page 12: ...the discharge pipe 1 idOil LIQ high liquid level sensor A Air B Oil C Water L Standard liquid level S Sensor switching point X Liquid alarm limit maximum surface level Figure 9 Installing the idOil LI...

Page 13: ...ion depth depends on the following separator type separator shape maximum allowed sludge layer thickness The sensor must always be immersed in liquid The alarm is activated when the sludge layer reach...

Page 14: ...is de energised The legends for the connection diagrams can be found in the section following the diagrams 5 1 Connection diagrams 5 1 1 Connection with a single sensor cable connector Figure 12 Conne...

Page 15: ...nnector Figure 13 Connection with a two sensor cable connector 5 1 3 Connection with a three sensor cable connector Figure 14 Connection with a three sensor cable connector Installation and Operating...

Page 16: ...3 sensor 3 connection 1 14 sensor 3 connection 2 The sensor connection is a polarity free digital bus which means that it does not matter which sensor terminal the wires are connected to 3 Relay outpu...

Page 17: ...are separated with separator walls on the protection plate The separator walls must not be removed The protection plate covering the connectors must be reinstalled after connecting the cables Install...

Page 18: ...n function is initiated and the fault indicator light flashes green Once a sensor has been identified the indicator light of the sensor in question becomes green When all connected sensors have been i...

Page 19: ...ngs Relay 1 Connected sensors All sensors connected to the control unit function function upon sensor alarm relay is restored when alarm is reset no Relay 2 Connected sensors All sensors connected to...

Page 20: ...dicator lights for alarm and or fault situations are switched on After the alarm delay 10 s The buzzer lets out an alarm sound The relays are switched to the alarm position Relay 1 is de energised in...

Page 21: ...d the idOil SLU sensors s alarm switching point The alarm light of the sludge sensor is red The other indicator lights are green The buzzer sounds after an approximately 10 second delay Relay 1 is de...

Page 22: ...7 3 Changing the buzzer settings The buzzer operation can be switched on and off as follows DANGER OF ELECTRICAL SHOCK Please observe the safety instructions below Cut off the control unit s voltage s...

Page 23: ...e active If this is the case all indicator lights are green Activating the test function Press the reset test button continuously for 3 seconds To indicate the activation of the test the indicator lig...

Page 24: ...e cut or loose or the alarm indicator lights of all sensors and the fault indicator light are red short circuit Explanation The sensor cable is short circuited cut or disconnected from the connector T...

Page 25: ...tion Max 8 VA Sensors Digital Labkotec idOil sensors Relay outputs 5 A 250 V AC 30 V DC 100 VA Potential free changeover contacts Indicator lights LED lights for alarm and fault states Electrical safe...

Page 26: ...iagram Appendix A VTT 17 ATEX 005X IECEx VTT 17 0003X II 1 G Ex and IIB T5 Ga Ta 25 C 60 C Ui 16 V Ii 80 mA Po 400 mW Ci 5 2 nF Li 1 6 mH Manufacturing year Please see the serial number on the type pl...

Page 27: ...Enclosure Enclosure class IP 68 Materials PP AISI 304 316 PA NBR CR Silicon Weight 900 g incl 5 m cable Temparature Operation 0 C 60 C Environment 25 C 60 C Supply voltage approx 12 V DC Cable 2 x 0 7...

Page 28: ...10 Appendices 10 1 APPENDIX A System digram Installation and Operating Instructions idOil 20 28 34 DOC001600 EN 5...

Page 29: ...Installation and Operating Instructions idOil 20 29 34 DOC001600 EN 5...

Page 30: ...Installation and Operating Instructions idOil 20 30 34 DOC001600 EN 5...

Page 31: ...10 2 APPENDIX B EU Declaration of Conformity Installation and Operating Instructions idOil 20 31 34 DOC001600 EN 5...

Page 32: ...Installation and Operating Instructions idOil 20 32 34 DOC001600 EN 5...

Page 33: ...Installation and Operating Instructions idOil 20 33 34 DOC001600 EN 5...

Page 34: ...Installation and Operating Instructions idOil 20 34 34 DOC001600 EN 5...

Reviews: