background image

Mighty Max Hydronic Boiler

Page 9

2G-3. System Pressure Requirements

The Model HH boilers are designed to operate

on closed, pressurized systems. Maintain a minimum
of 12 psi (81.8 kPa) on the system where boiler supply
water temperature is 200°F (93°C) or less. If higher
temperatures are required, the minimum system
pressure should be at least 15 psi (102.2 kPa) above
the water vapor pressure corresponding to the elevated
water temperature.

The Model HH boilers are not suitable for open

systems unless the supply water temperatures are
kept below 180°F (82°C), and a minimum of 5 psi
(34.1 kPa) static head is maintained at the boiler.

2G-4. Hot/Chilled Water Systems

When a boiler is connected to an air

conditioning system where the same water is used for
heating and cooling, you must prevent chilled water
from entering the boiler. When changing such a
system from cooling to heating, allow the chilled
water to circulate through the building, after the
chiller has been turned off, for a period long enough
for the water to warm up to at least 105°F (41°C)
before the water flows into the boiler. It is equally
important to prevent hot water from entering the
chiller. The system shown in Figure 6 is suggested to
make sure the system water is neither too hot nor too
cold when a changeover takes place. When a boiler is
connected to heating coils located in air handling units
(where they may be exposed to refrigerated air
circulation), install a flow control valve or other
automatic means to prevent gravity circulation of
chilled water through the boiler. Chilled water in the
boiler will create condensate on the boiler tubes.
Boilers installed in violation of the foregoing may
void the warranty
.

2G-5. Combined Space Heating/Potable

Water Heating Systems

When using the Mighty Max boiler as a source

of heat for a combined space heating/potable water
heating system, be sure to follow the instructions of
the space heating system.

Do not use water piping, fittings, valves, pumps,

and any other components which are not compatible
with potable water.

Do not connect the heater, which will be used to

supply potable water, to any heating system or
components previously used with a nonpotable water
heating system.

Do not add boiler treatment or any chemicals to

the heating system piping, since the piping contains
water for potable use.

Do not use solder containing lead in the potable

water lines.

Some jurisdictions may require a backflow

preventer in the cold water line. In such cases,

pressure relief valve may discharge water due to
expansion. An expansion tank approved for potable
water will eliminate this condition. Follow the
manufacturer's instructions for installation of the
expansion tank.

3-Way Valve No. 1
Change-Over
(Heating and Cooling)

3-Way Valve No. 2
To By-Pass
Both Heater and
Chiller

To
System

From
System

By-Pass

To Boiler
and
Chiller

From
Boiler

Valve Motors
2-Pos
3-Wire - 24V

115/24V
Transformer

DPDT Manual or Automatic
Change-Over Switch
DPDT - Set at Change-Over
Temperature

Clock Timer
Auto-Resetting
Set at 15 Minute SPDT

Suggested Wiring Diagram For

Tempering System Water at

Changeover From Heating To Cooling

Figure 6. Boiler-Chiller Installation.

From
Chiller

2H. Piping of System to Boiler

1.

Be sure to provide gate valves at the inlet and
outlet to the boiler so it can be readily isolated
for service.

2.

The pressure relief valve installed in the tapped
opening provided in the outlet header must be
piped, but not fastened, to a drain or floor sink.
The drain pipe must be the same size as the valve
outlet and must pitch downward from the valve. If
the PRV supplied with the boiler is not factory
installed, install it in the front header consistent
with the ANSI/ASME Boiler and Pressure Vessel
Code, Section IV. Pay special attention to relief
valve settings in installations where the boiler is
located on the ground floor of a tall building, or
where the operating temperature of the boiler is
above 210°F (99°C). In both instances, the static
pressure of the system is elevated and could cause
the relief valve to leak and bring considerable raw
water into the system. Where no special setting of
the relief valve is ordered, the factory will furnish
a 75 psi (511.5 kPa) setting. Never reduce the
relief valve opening. If necessary, install the relief
valve in a Tee immediately past the boiler outlet.

Summary of Contents for Mighty Max HH0320M

Page 1: ...e technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property...

Page 2: ...tion Air 15 2M 3 Conversion for Ducted Combustion Air 15 2M 4 Combustion Air Piping 16 2N Electrical Wiring 16 SECTION 3 Operating Instructions 3A Start Up Requirements 16 3B Hi Limit checkout 18 3C V...

Page 3: ...ion and maintenance instruction for the Mighty Max hydronic boiler Model HH sizes 320M 400M 520M 625M 775M and 1000M Review all application and installation procedures completely before proceeding wit...

Page 4: ...lated or otherwise protected from any source of corrosive chemical fumes such as trichlorethylene perchlorethylene chlorine etc Install the boiler so that the gas ignition system components are protec...

Page 5: ...nnected to the common venting system properly vents when tested as outlined above return door windows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of...

Page 6: ...au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou aux codes d installation CAN CGA B149 Si la grosseur d une section du syst me devrait tre modifi ppour respecter les valeurs minimales des tableaux...

Page 7: ...n Used On Canadian Unit or U S Unit Requiring CSD 1 Code Automatic Main Gas Valves NOTE The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to...

Page 8: ...h the boiler expressed in ft of H2O Shaded area is the recommended flow and temperature rise Minimum inlet temperature is 105 F Table 5 Temperature Rise TEMPERATURE RISE IN DEGREES F C MODEL 10 F 6 C...

Page 9: ...he heater which will be used to supply potable water to any heating system or components previously used with a nonpotable water heating system Do not add boiler treatment or any chemicals to the heat...

Page 10: ...diation units for one 1 hour 10 Recheck the water level in the expansion tank If the water level exceeds 1 4 of the volume of the expansion tank open the tank drainer and drain to that level 11 Shut d...

Page 11: ...nting and Combustion Air Options Vertical Venting Category I Combustion Air In Through Louvers Side View Wall NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion...

Page 12: ...er Jacket Blank Plate On Flue Collector Blank Plate On Boiler Jacket Top Panel 1 Removal of Blank Plate and Adapter Plate From Boiler 3 Blank Plate Placement Over Stack Top Opening Blank Plate Flue Co...

Page 13: ...al vents must be installed in accordance with the special code requirements for Category I Fan Assisted Appliances These requirements can be found in the latest edition of ANSI Z223 1 NFPA 54 Appendix...

Page 14: ...2m horizontally from or 3 feet 0 9m above such openings 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas code requires that it be at least 12 inches 305mm above g...

Page 15: ...of the Laars side wall terminal Locate the terminal within 10 feet 3 0m of the boiler vent exhaust terminal but no closer than 3 feet 0 9m centerline distance Do not locate the air inlet terminal near...

Page 16: ...in the wiring diagram supplied with the boiler see Figure 12 3 Electrically interlock the pump and boiler so the boiler cannot come on unless the pump is running 4 Connect all field installed devices...

Page 17: ...rvicing controls wiring errors can cause improper and dangerous operation Verify proper operation after operation servicing ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avan...

Page 18: ...back up to its original setting and the hi limit is reset 3C Venturi and Gas Pressure Regulator System 3C 1 Overall Operation The gas control system of the Mighty Max boiler is similar to that of a ca...

Page 19: ...ake a pressure reading This reading is called the gas pressure offset Using the regulator only adjust the gas pressure offset according to the installation s altitude in Table 5 0 4 w c at sea level R...

Page 20: ...sures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following section descri...

Page 21: ...rence in pressure between the venturi inlet tap and the outlet of the gas regulator see Figure 17 This measurement is taken by connecting the positive side of the manometer to the venturi inlet tap an...

Page 22: ...wc at sea level Use the blower shutter to adjust the gas orifice differential 6 By adjusting the gas orifice differential the gas offset pressure will change Therefore you must repeat steps 3 5 until...

Page 23: ...vicing the heat exchanger 1 Disconnect the 120 Vac electrical supply to the heater 2 Turn off the gas supply by closing the manual gas valve on the heater 3 Disconnect and remove the wires and conduit...

Page 24: ...may need to be cleaned daily Failure to do so could result in lower heat output and potential unsafe operation SECTION 5 Troubleshooting 5A Sequence of Operation To troubleshoot the heater properly y...

Page 25: ...Mighty Max Hydronic Boiler Page 25 Figure 20 Troubleshooting Chart...

Page 26: ...irculating water and the foregoing items check out okay the trouble may be in the boiler control system IMPORTANT Disconnect power to the boiler before removing or replacing any component or wire conn...

Page 27: ...mbly 320M 20254901 400M 20254902 Item Description Part Number 520M 625M 20260100 U S 20260101 Canada 775M 20260200 U S 20260201 Canada 1000M 20265600 U S 20265601 Canada Gas Valve 320M 425M V2003900 5...

Page 28: ...Page 28 LAARS HEATING SYSTEMS Front View Right Side View 36 10 8 9 5 20 7 12 13 11 3 6 21 14 15 38 4 1 2...

Page 29: ...Mighty Max Hydronic Boiler Page 29 Front View Rear View Right Side View Left Side View 31 32 17 30 23 26 27 28 25 37 25 33 16 18 35 29 19 34 39...

Page 30: ...Left 20152900 30 Panel Access 320M 20157401 400M 20157402 520M 20157403 625M 20157404 775M 20157405 1000M 20157406 Item Description Part Number 31 Panel Back 320M 20157201 400M 20157202 520M 20157203...

Page 31: ...Mighty Max Hydronic Boiler Page 31...

Page 32: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: