background image

Page 20

LAARS HEATING SYSTEMS

Caution

This appliance is equipped with an ignition
device which automatically lights the burner.
Do not try to light the burner by hand.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any
phone in your building.

Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.

If you don't smell gas, go to the next step.
7.

Turn on manual gas valves.

8.

Rest all safety devices (manual resets on high
limit, low water cutoff, etc.).

9.

Replace control access panel.

10.

Turn on all electric power to the boiler.

11.

Set thermostat to desired setting.

12.

If the boiler will not operate, follow the
instructions to turn off gas to boiler and call your
service technician or gas supplier.
a.

Turn off main electrical switch.

b.

Close all manual gas valves.

3D-1. Setting Temperature Controls

The temperature control differential is factory

set at 15°F. This setting can be adjusted from 1 to
30°F to suit your application. Adjustment is made by
taking the cover off the temperature controller and
turning the potentiometer marked “DIFF”, which is
located just below and to the left of the controller’s
setpoint dial.

To set the temperature and high-limit controls:

a.

Set the temperature controller at the system
design temperature.

b.

For boilers with the temperature controller bulb
at the boiler inlet, set the high-limit 40°F to 50°F
above temperature controller setting.

c.

For boilers with the temperature controller bulb
at the boiler outlet, set the high-limit 15°F to
25°F above temperature controller setting.

3E. To Shut Down System

To shut down the boiler, turn off all manual gas

valves and electrical disconnect switch.

NOTE: There is a filter which needs to be cleaned
prior to setting pressures. See Section 4D-2 “Filter
Service” before proceeding.

3F. Venturi Combustion Flow System

Verifying proper operation of the combustion

flow system has two aspects - air flow and gas flow.
Air flow is checked by measuring pressures at service

taps on the venturi. Gas flow is checked by evaluating
venturi pressures and the regulator offset pressure.

In a venturi flow system the difference between

various pressures is far more important than their
“gauge” value relative to the room. The gas pressure
offset and the gas orifice pressure differential are
especially important concepts. The following section
describes this setup procedure.

3F-1. Pressure Measurement Ports

Air flow enters the venturi through the filter box

and blower assembly. It is pushed through a
converging section and into the throat, where pressure
is reduced substantially. Gas flow is pulled into the
throat through an orifice. The orifice is located
between the throat and the regulator. Air and gas are
combined in the throat and mix thoroughly as they
proceed through the venturi tailpipe to the burner.

Service taps are provided at three places. One is

located on the chamber with the gas connection, this
tap is called the gas plenum tap. The other is located
above the gas plenum tap, this port is called the
venturi inlet tap. The third tap, gas orifice tap, is
located on the red orifice holder directly before the
gas connects to the venturi. These taps have service
plugs in them. Do not remove any of the plastic
fittings or plastic tubing. To evaluate system operation
requires accurate measurement at these taps. An
inclined manometer with a zero to 6 inches water
column range is ideal. Other instruments may be used,
but the “positive/negative” nature of the readings must
be well understood. Gas pressure offset measurements
are at very low levels (0.4" WC), the instrumentation
must be capable of determining it accurately.

3F-2. Venturi Adjustment

Note that an equalizer tube is connected from a

port on the side of the venturi inlet to the port of the
regulator. This is a very important component which
allows the regulator to track air pressure even when
abnormal conditions occur, such as blockage of the
combustion air. Before firing, confirm that this tube
and the venturi pressure switch tubes are in place and
firmly connected.

The field checkout involves measuring gas and

venturi pressures, and observing the flame through the
sight glass. If necessary, the gas input rate can be
measured by timing the gas meter.

Install shutoff valves at the gas orifice (regulator

outlet) tap (red), at the venturi inlet tap and at the gas
plenum tap. Do not remove any of the plastic fittings
or plastic tubing. After installing the shutoff valves,
be certain they are closed.

a. Unfired Venturi Differential Pressure

NOTE: Turn off the main manual gas valve.

Summary of Contents for Mighty Max HH0320M

Page 1: ...e technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property...

Page 2: ...tion Air 15 2M 3 Conversion for Ducted Combustion Air 15 2M 4 Combustion Air Piping 16 2N Electrical Wiring 16 SECTION 3 Operating Instructions 3A Start Up Requirements 16 3B Hi Limit checkout 18 3C V...

Page 3: ...ion and maintenance instruction for the Mighty Max hydronic boiler Model HH sizes 320M 400M 520M 625M 775M and 1000M Review all application and installation procedures completely before proceeding wit...

Page 4: ...lated or otherwise protected from any source of corrosive chemical fumes such as trichlorethylene perchlorethylene chlorine etc Install the boiler so that the gas ignition system components are protec...

Page 5: ...nnected to the common venting system properly vents when tested as outlined above return door windows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of...

Page 6: ...au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou aux codes d installation CAN CGA B149 Si la grosseur d une section du syst me devrait tre modifi ppour respecter les valeurs minimales des tableaux...

Page 7: ...n Used On Canadian Unit or U S Unit Requiring CSD 1 Code Automatic Main Gas Valves NOTE The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to...

Page 8: ...h the boiler expressed in ft of H2O Shaded area is the recommended flow and temperature rise Minimum inlet temperature is 105 F Table 5 Temperature Rise TEMPERATURE RISE IN DEGREES F C MODEL 10 F 6 C...

Page 9: ...he heater which will be used to supply potable water to any heating system or components previously used with a nonpotable water heating system Do not add boiler treatment or any chemicals to the heat...

Page 10: ...diation units for one 1 hour 10 Recheck the water level in the expansion tank If the water level exceeds 1 4 of the volume of the expansion tank open the tank drainer and drain to that level 11 Shut d...

Page 11: ...nting and Combustion Air Options Vertical Venting Category I Combustion Air In Through Louvers Side View Wall NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion...

Page 12: ...er Jacket Blank Plate On Flue Collector Blank Plate On Boiler Jacket Top Panel 1 Removal of Blank Plate and Adapter Plate From Boiler 3 Blank Plate Placement Over Stack Top Opening Blank Plate Flue Co...

Page 13: ...al vents must be installed in accordance with the special code requirements for Category I Fan Assisted Appliances These requirements can be found in the latest edition of ANSI Z223 1 NFPA 54 Appendix...

Page 14: ...2m horizontally from or 3 feet 0 9m above such openings 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas code requires that it be at least 12 inches 305mm above g...

Page 15: ...of the Laars side wall terminal Locate the terminal within 10 feet 3 0m of the boiler vent exhaust terminal but no closer than 3 feet 0 9m centerline distance Do not locate the air inlet terminal near...

Page 16: ...in the wiring diagram supplied with the boiler see Figure 12 3 Electrically interlock the pump and boiler so the boiler cannot come on unless the pump is running 4 Connect all field installed devices...

Page 17: ...rvicing controls wiring errors can cause improper and dangerous operation Verify proper operation after operation servicing ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avan...

Page 18: ...back up to its original setting and the hi limit is reset 3C Venturi and Gas Pressure Regulator System 3C 1 Overall Operation The gas control system of the Mighty Max boiler is similar to that of a ca...

Page 19: ...ake a pressure reading This reading is called the gas pressure offset Using the regulator only adjust the gas pressure offset according to the installation s altitude in Table 5 0 4 w c at sea level R...

Page 20: ...sures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following section descri...

Page 21: ...rence in pressure between the venturi inlet tap and the outlet of the gas regulator see Figure 17 This measurement is taken by connecting the positive side of the manometer to the venturi inlet tap an...

Page 22: ...wc at sea level Use the blower shutter to adjust the gas orifice differential 6 By adjusting the gas orifice differential the gas offset pressure will change Therefore you must repeat steps 3 5 until...

Page 23: ...vicing the heat exchanger 1 Disconnect the 120 Vac electrical supply to the heater 2 Turn off the gas supply by closing the manual gas valve on the heater 3 Disconnect and remove the wires and conduit...

Page 24: ...may need to be cleaned daily Failure to do so could result in lower heat output and potential unsafe operation SECTION 5 Troubleshooting 5A Sequence of Operation To troubleshoot the heater properly y...

Page 25: ...Mighty Max Hydronic Boiler Page 25 Figure 20 Troubleshooting Chart...

Page 26: ...irculating water and the foregoing items check out okay the trouble may be in the boiler control system IMPORTANT Disconnect power to the boiler before removing or replacing any component or wire conn...

Page 27: ...mbly 320M 20254901 400M 20254902 Item Description Part Number 520M 625M 20260100 U S 20260101 Canada 775M 20260200 U S 20260201 Canada 1000M 20265600 U S 20265601 Canada Gas Valve 320M 425M V2003900 5...

Page 28: ...Page 28 LAARS HEATING SYSTEMS Front View Right Side View 36 10 8 9 5 20 7 12 13 11 3 6 21 14 15 38 4 1 2...

Page 29: ...Mighty Max Hydronic Boiler Page 29 Front View Rear View Right Side View Left Side View 31 32 17 30 23 26 27 28 25 37 25 33 16 18 35 29 19 34 39...

Page 30: ...Left 20152900 30 Panel Access 320M 20157401 400M 20157402 520M 20157403 625M 20157404 775M 20157405 1000M 20157406 Item Description Part Number 31 Panel Back 320M 20157201 400M 20157202 520M 20157203...

Page 31: ...Mighty Max Hydronic Boiler Page 31...

Page 32: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: