background image

Page 24

LAARS HEATING SYSTEMS

Other maintenance requirements include:

1.

Periodic cleaning of filters, when supplied.

2.

Lubrication of moving parts (when applicable),
with the correct type and amount of lubricant.

3.

Periodic examination of the venting system.

4.

Periodic cleaning of vent terminal screens,
where applicable.

5.

Cleaning flue gas passageways.

4D. Filter

4D-1. Filter Function

A filter has been designed into the operation of

this Mighty Max boiler. Its function is to filter the
combustion air before it is delivered to the burner
system. The filter is manufactured out of a
polyurethane foam and may be cleaned with a mild
soap and water solution. Clean the filter only after the
filter has been removed from the filter housing (see
Figure 19).

4D-2. Filter Service

(The filter does not need cleaning if this is a first

time heater start-up).

1.

Turn the heater off using the toggle switch.

2.

Remove the door panel and bonnet from the
jacket.

3.

Remove the screws on the filter housing to
expose the filter as shown in Figure 19.

Caution

The filter has arrows which indicate the
direction of the air flow. Failure to install the
filter correctly may cause blower failure and
dangerous operation.

The filter must be inspected for contamination

one week after start-up. Depending upon the severity
of contamination, a suitable cleaning schedule may be
developed. The factory recommends cleaning the filter
at least once every 30 days. In high contamination
areas, such as construction sites, factories, etc., the
filter may need to be cleaned daily. Failure to do so
could result in lower heat output and potential unsafe
operation.

SECTION 5
Troubleshooting

5A. Sequence of Operation

To troubleshoot the heater properly you must

first understand the sequence of operation of the
heater:
1.

Upon a call for heat a 24 Vac signal is sent
through fusible links and high limit(s) to the
ignition control “TH” terminal.

2.

The “IND” terminal of the ignition control is
energized for a 15 second pre-ignition purge
period during which the combustion blower
purges the combustion chamber.

3.

After the purge period there is a 20 to 35 second
igniter heat up period. The glow of the igniter
can be seen through the boiler sight glass.

4.

Then there is a seven second trial for ignition.
During this time the gas valves are energized and
the main burner ignites. The gas valves will
remain energized throughout the call for heat as
long as the ignition control igniter senses a
stable flame.

5.

After the call for heat is satisfied the ignition
control closes the gas valves and operates the
blower for a thirty (30) second post purge cycle.
This clears the combustion chamber of
combustion products.

The ignition is attempted three times. If ignition

is not successful, the control shuts down and “locks
out”. It remains in the lockout condition until the
boiler is turned off then back on or 120 Vac power to
the boiler is interrupted.

Figure 19. Filter Exposed for Cleaning.

4.

Inspect the filter for discoloration due to
contamination or any other forms of debris. If
contamination or debris exists, wash the filter in
a soap/water solution then rinse with water only.
It is important that the filter be dry before
placing it back in the filter housing.

Summary of Contents for Mighty Max HH0320M

Page 1: ...e technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property...

Page 2: ...tion Air 15 2M 3 Conversion for Ducted Combustion Air 15 2M 4 Combustion Air Piping 16 2N Electrical Wiring 16 SECTION 3 Operating Instructions 3A Start Up Requirements 16 3B Hi Limit checkout 18 3C V...

Page 3: ...ion and maintenance instruction for the Mighty Max hydronic boiler Model HH sizes 320M 400M 520M 625M 775M and 1000M Review all application and installation procedures completely before proceeding wit...

Page 4: ...lated or otherwise protected from any source of corrosive chemical fumes such as trichlorethylene perchlorethylene chlorine etc Install the boiler so that the gas ignition system components are protec...

Page 5: ...nnected to the common venting system properly vents when tested as outlined above return door windows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of...

Page 6: ...au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou aux codes d installation CAN CGA B149 Si la grosseur d une section du syst me devrait tre modifi ppour respecter les valeurs minimales des tableaux...

Page 7: ...n Used On Canadian Unit or U S Unit Requiring CSD 1 Code Automatic Main Gas Valves NOTE The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to...

Page 8: ...h the boiler expressed in ft of H2O Shaded area is the recommended flow and temperature rise Minimum inlet temperature is 105 F Table 5 Temperature Rise TEMPERATURE RISE IN DEGREES F C MODEL 10 F 6 C...

Page 9: ...he heater which will be used to supply potable water to any heating system or components previously used with a nonpotable water heating system Do not add boiler treatment or any chemicals to the heat...

Page 10: ...diation units for one 1 hour 10 Recheck the water level in the expansion tank If the water level exceeds 1 4 of the volume of the expansion tank open the tank drainer and drain to that level 11 Shut d...

Page 11: ...nting and Combustion Air Options Vertical Venting Category I Combustion Air In Through Louvers Side View Wall NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion...

Page 12: ...er Jacket Blank Plate On Flue Collector Blank Plate On Boiler Jacket Top Panel 1 Removal of Blank Plate and Adapter Plate From Boiler 3 Blank Plate Placement Over Stack Top Opening Blank Plate Flue Co...

Page 13: ...al vents must be installed in accordance with the special code requirements for Category I Fan Assisted Appliances These requirements can be found in the latest edition of ANSI Z223 1 NFPA 54 Appendix...

Page 14: ...2m horizontally from or 3 feet 0 9m above such openings 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas code requires that it be at least 12 inches 305mm above g...

Page 15: ...of the Laars side wall terminal Locate the terminal within 10 feet 3 0m of the boiler vent exhaust terminal but no closer than 3 feet 0 9m centerline distance Do not locate the air inlet terminal near...

Page 16: ...in the wiring diagram supplied with the boiler see Figure 12 3 Electrically interlock the pump and boiler so the boiler cannot come on unless the pump is running 4 Connect all field installed devices...

Page 17: ...rvicing controls wiring errors can cause improper and dangerous operation Verify proper operation after operation servicing ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avan...

Page 18: ...back up to its original setting and the hi limit is reset 3C Venturi and Gas Pressure Regulator System 3C 1 Overall Operation The gas control system of the Mighty Max boiler is similar to that of a ca...

Page 19: ...ake a pressure reading This reading is called the gas pressure offset Using the regulator only adjust the gas pressure offset according to the installation s altitude in Table 5 0 4 w c at sea level R...

Page 20: ...sures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following section descri...

Page 21: ...rence in pressure between the venturi inlet tap and the outlet of the gas regulator see Figure 17 This measurement is taken by connecting the positive side of the manometer to the venturi inlet tap an...

Page 22: ...wc at sea level Use the blower shutter to adjust the gas orifice differential 6 By adjusting the gas orifice differential the gas offset pressure will change Therefore you must repeat steps 3 5 until...

Page 23: ...vicing the heat exchanger 1 Disconnect the 120 Vac electrical supply to the heater 2 Turn off the gas supply by closing the manual gas valve on the heater 3 Disconnect and remove the wires and conduit...

Page 24: ...may need to be cleaned daily Failure to do so could result in lower heat output and potential unsafe operation SECTION 5 Troubleshooting 5A Sequence of Operation To troubleshoot the heater properly y...

Page 25: ...Mighty Max Hydronic Boiler Page 25 Figure 20 Troubleshooting Chart...

Page 26: ...irculating water and the foregoing items check out okay the trouble may be in the boiler control system IMPORTANT Disconnect power to the boiler before removing or replacing any component or wire conn...

Page 27: ...mbly 320M 20254901 400M 20254902 Item Description Part Number 520M 625M 20260100 U S 20260101 Canada 775M 20260200 U S 20260201 Canada 1000M 20265600 U S 20265601 Canada Gas Valve 320M 425M V2003900 5...

Page 28: ...Page 28 LAARS HEATING SYSTEMS Front View Right Side View 36 10 8 9 5 20 7 12 13 11 3 6 21 14 15 38 4 1 2...

Page 29: ...Mighty Max Hydronic Boiler Page 29 Front View Rear View Right Side View Left Side View 31 32 17 30 23 26 27 28 25 37 25 33 16 18 35 29 19 34 39...

Page 30: ...Left 20152900 30 Panel Access 320M 20157401 400M 20157402 520M 20157403 625M 20157404 775M 20157405 1000M 20157406 Item Description Part Number 31 Panel Back 320M 20157201 400M 20157202 520M 20157203...

Page 31: ...Mighty Max Hydronic Boiler Page 31...

Page 32: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: