MagnaTherm Boilers and Water Heaters
Page 89
16
Internal fault:
Safety relay test failed due to safety
relay OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
17
Internal fault:
Safety relay test failed due to safety
relay not OFF
L
18
Internal fault:
Safety relay test failed due to feedback
not ON
L
19
Internal fault:
Safety RAM write
L
20
Internal fault:
Internal fault: Flame ripple and overflow
H
21
Internal fault:
Flame number of sample mismatch
H
22
Internal fault:
Flame bias out of range
H
23
Internal fault:
Bias changed since heating cycle starts
H
24
Internal fault:
Spark voltage stuck low or high
H
25
Internal fault:
Spark voltage changed too much during
flame sensing time
H
26
Internal fault:
Static flame ripple
H
27
Internal fault:
Flame rod shorted to ground detected
H
28
Internal fault:
A/D linearity test fails
H
29
Internal fault:
Flame bias cannot be set in range
H
30
Internal fault:
Flame bias shorted to adjacent pin
H
31
Internal fault:
SLO electronics unknown error
H
32-46 Internal fault:
Safety Key 0 through 14
L
47
Flame Rod to ground leakage
H
48
Static flame (not flickering)
H
49
24 VAC voltage low/high
H
1. Check the module and display connections.
2. Check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.