Lag Unit/s
8.I Lead Lag Connections
This commercial unit can be connected in Lead Lag
up to a total of 8 units (controllers). One as the Lead
control and up to 7 more as the Lag controllers.
For Lead Lag Connections, COM2 A, B, and C must
be connected together AND the MB2 A. B, and C must
also be connected together, as shown in Figure 21.
See page 71 for configuration setup within the
touchscreen display.