background image

9600 CB & HWG Service Manual

Page 9

1B. Start Up Procedures

1.

Make sure that the system is properly filled, com-
pletely purged of air and system valves are open.

2.

Open system gas cock(s) and gas control knob on
gas valve (if closed).

3.

Set the room thermostat, aquastat or storage tank
aquastat to call for heat.

4.

Turn on electrical power to the unit.

5.

The green light on the boiler control will light and
the internal circulator and blower will start. After
a 15 second prepurge the igniter will come on for
20 seconds and then the gas valve will open and
ignition will occur (for more details see
“Sequence of Operation”).

Note

: Air in new gas lines may prevent ignition.

The boiler control will make a total of three attempts
for ignition before lockout. To reset the control, switch
off the power switch for 10 seconds.

1C. Checkout Procedures

1.

Check burner input rate:
Allow burner to operate for at least 5 minutes
before checking the input. On most LP
installations it will be impossible to check the
input, however, checking combustion as in step 2
below will guarantee proper burner operation. To
check the input (where possible) time the gas
meter to determine the time required for 4 cubic
feet of gas to pass through it. No other equipment
supplied by the gas meter should be operating
when the timing is done. Table 1 can be used to
convert the time to input rate.

Due to the effects of altitude and other minor
variances, it is possible that the input rate will
differ slightly from the rating plate value.

2.

Check combustion (see Figure 7).
It is important to check the combustion with a
CO2 or O2 tester (Bacharach for example) to
ensure maximum efficiency and reliability. Insert

the tester sample tube through the exhaust
terminal and at least 6" (152mm) into the flue
pipe. The unit must operate for 5 minutes before
taking a sample. Take a sample and determine the
CO2 or O2
CO2 - 8% to 8.5% (natural gas)
O2 - 7% to 6%
CO2 - 9% to 9.8% (propane gas)
If the burner is not operating in this range it
should be adjusted (see Burner Adjustment).

3.

Burner Adjustment
The Heatmaker 9600 CB & HWG burner system
is a pre-mixed forced combustion system. Outside
air is drawn through the air orifice (located in the
rubber hose in the air induction system) and
mixed with the gas which is drawn in downstream
of the air orifice. All the air required for complete
combustion comes into the system in this manner.
The gas is metered through the gas orifice located
in the gas orifice union.
Adjusting the burner is limited to changing the
gas orifice to achieve proper combustion. The air
orifice cannot be altered and the gas valve
pressure should not be changed.
Before changing the gas orifice to adjust the
burner, make the following checks:
a.

Gas valve supply pressure is between 4 and
14 in. W.C. (2.3 and 8.1 oz / in²)

b.

The differential pressure on the outlet side
of the gas valve (manifold pressure) is
between -0.05 and -0.35 in. W.C.

If a. and b. are correct proceed as follows:
When measuring CO2 (natural gas units),

readings below 8% generally indicate lean mixture (not
enough gas). Reading above 9 1/4% indicate a rich
mixture (too much gas). Readings for LP units are
higher; below 9 1/4% is lean and above 10 3/4% is
rich. If the readings are below the minimum values,
install a larger gas orifice. If the readings are above the
maximum value install a smaller orifice.

Figure 7. Checking Combustion.

Table 1. Time-to-Input Rate Conversion.

Time (4CF)

Input Rate (Natural Gas)

57 sec

252,600 BTU/hr

58

248,300

59

244,000

70

205,700

71

202,800

72

200,000

74

194,600

80

180,000

82

175,600

84

171,400

94

153,200

96

150,000

98

146,900

EXHAUST
TERMINAL

COMBUSTION
TESTER
SAMPLE
TUBE

1/4 IN. PER FT.

9600 CB

Summary of Contents for HWG-M2-250

Page 1: ...r installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss...

Page 2: ...h 10 1G BoilerControl 10 1H Stack Switch 11 1I Igniter 11 1J Transformer 11 1K Unit Pump 11 1L Blower 11 1M GasValve 11 1N TimeDelayRelay TDR 11 1O OperatingControl 11 1P VentTCO 12 1Q IntakeTCO 12 1R...

Page 3: ...ondensation temperature of the water vapor in the flue gases A circulator is built into the unit to provide enough head to circulate water through the H X s and to a secondary heating loop or separate...

Page 4: ...pical D Combustion Coil Outlet E Hot Water Outlet To Tank or System 160 170 F Typical 160 FTHERMOSTAT Figure 2a Water Flow through a Heatmaker 9600 HWG Before S N 394 068 CB Before S N 795 0014 THERMO...

Page 5: ...urner 8 Secondary Heat Exchanger 9 Primary Heat Exchanger 10 Return From Primary Loop 11 Gas Valve 12 Flow To Primary Loop A Secondary Heat Exchanger Inlet B Secondary Heat Exchanger Outlet C Primary...

Page 6: ...ow Through Heatmaker 9600 43 INTAKE TERMINAL 50 WALL PLATE AIR INTAKE 45 WALL PLATE 44 EXHAUST TERMINAL EXHAUST AIR ORIFICE GAS ORIFICE GAS 1 COMBUSTION COIL 2 ECONOMIZER 7 FLAMEHOLDER 46 EXHAUST ASSE...

Page 7: ...9600 CB HWG Service Manual Page 7 Figure 4 Cut Away View of Heatmaker 9600 Figure 5 Control Box...

Page 8: ...nd input desired Part Description Part 23 Jacket Front Removeable 10 402 24 Jacket Top 10 406 25 Jacket Bottom 10 010 26 Control Boiler Integrated 2400 224 27 Transformer 40 VA 2400 006 28 Time Delay...

Page 9: ...minal and at least 6 152mm into the flue pipe The unit must operate for 5 minutes before taking a sample Take a sample and determine the CO2 or O2 CO2 8 to 8 5 natural gas O2 7 to 6 CO2 9 to 9 8 propa...

Page 10: ...ostatically controlled device which keeps the primary heat exchanger H X from operating in the condensing mode When return water from the storage tank or the system is below 130 F 54 C the diverting v...

Page 11: ...d unplug the power wires from the blower motor Disconnect intake exhaust vents and remove top jacket Remove the six bolts and nuts from the blower discharge flange and the four nuts from the blower in...

Page 12: ...n the gas valve The gas supply to the boiler must be shut off before making this connection The Heatmaker boiler is designed to operate with supply pressures of 4 14 in W C 8 1 oz in2 with the boiler...

Page 13: ...se the flame signal The control then causes a restart and if the flame signal is sensed on the restart then the burner will operate again The intermittent sending and losing of the flame signal by the...

Page 14: ...solution is no longer foamy 7 Shut off pump and disconnect from hose Carefully drain solution from hoses and connect city water to lower hose to flush combustion coil Flush for approximately 5 minutes...

Page 15: ...on and no indicator lights are flashing check for an open vent TCO operating control or safety limit switch For additionaltroubleshootinginformationrefertothe trouble shooting flow charts on the page...

Page 16: ...VOLTAGE 120 VAC BETWEEN BLACK AND WHITE WIRES AT BACK OF 120 VAC CONNECTORON BOILERCONTROL DIDBOILERRUNTHROUGHA COMPLETE CYCLE AS DE SCRIBED IN SEQUENCE OF EVENTS PAGE 20 TESTLIMIT CIRCUIT PAGE 17 PUM...

Page 17: ...OHMSCALE CONTINUITY CONTINUITY CONTINUITY NOCONTINUITY OHMS NOCONTINUITY TESTING LIMIT CIRCUIT YOU MUST COMPLETE PAGE 16 FIRST NOTE AFTER COMPLETEING LIMIT CIRCUIT TESTING PLUG IN CONTROL PLUG AND REC...

Page 18: ...EAVESETC AGAINST VENTTERMINAL CYCLE BOILER MANY TIMES TO TRY TO CREATE A MALFUNCTION CLEAR BLOCKAGE AND RECYCLEBOILER CHECKSTACKSWITCH BLOCKAGE EXISTS NO BLOCKAGE NO YES YES NO RED PURGE LIGHT FLASHIN...

Page 19: ...TSTACKSWITCH TUBES AND CHECK FOR CONTINUITYBETWEENSTACK SWITCHTERMINALSWITH BLOWEROPERATING CHECKFORVENTOBSTRUCTIONS CLEAROBSTRUCTIONS RECONNECTTUBES ELEC TRICALWIRESTOSTACK SWITCH START BOILER RUN TH...

Page 20: ...SSURETAP ON GAS VALVE PRESSURE DURING BLOWER OPERATIONWITHOUTGASFLOW VALVE FLAME LIGHT NOT LIT IS 4 IN W C CHECK FOR VOLTAGE 120 VAC ATBLOWERWIRECONNECTOR WITHIN5MINS AFTERGREEN LIGHT BLOWER O K REPLA...

Page 21: ...G LITE CHECKCOMBUSTION CHECKIGNITER IGNITEROK CHECK FOR GAS FLOW IS METER MOVING REPLACE IGNITER REPLACEINTEGRATEDBOILERCONTROLP N2400 224 INSTALL CORRECT ORIFICES BOILERCYCLESTHROUGHTHREECYCLESAFTER...

Page 22: ...L PLUG CN6 THERE IS 120 VAC AT CIRCULATOR PLUG CN5 TURNUPT STATORAQUASTATOR CORRECTSTATPROBLEM NO YES NO YES SEETROUBLESHOOTING CHART PAGE 16 THERE IS 120 VAC AT PUMP REPLACEBOILER CONTROLP N2400 224...

Page 23: ...23 Figure 9 9600 Ladder Diagram Figure 10 9600 Wiring Diagram Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify pr...

Page 24: ...sure of 9 3 Remove blower and inspect flameholder burner for hole 4 Check that the blower flanges and gas piping are sealed D OCCASIONAL LOCKOUTS Requires interruption of power to re start or reset of...

Reviews: