12
For HELP, call La-Z-Boy
®
Spas at 1.800.465.2933.
ELECTRICAL SPECIFICATIONS
Important:
Qualified and licensed electricians must perform all electrical hookups.
The following specifications must be followed in order to ensure proper performance
and safety.
Starting an incorrectly wired
spa / hot tub
could cause severe damage
to the mechanical equipment or even bodily harm. Have your licensed
electrician verify GFCI wiring with the schematics on page 13-14 prior to
starting the
spa
/ hot tub or call your dealer.
Failure to abide by specifications listed may result in damage to the
equipment and will void the warranty.
Test the GFCI before each use of the spa / hot tub.
All spa / hot tubs must be wired with a Siemens breaker (or according to IEEE wire
regulations for export models). Failure to do so will cause equipment damage and will
not be covered under your guarantee. All spa / hot tubs must be protected with an over
current protective device with built-in GFCI in the service panel.
Volts
(V)
Freq.
(Hz)
Phase
Rating
(A)
GFCI
(A)
Wire size from GFCI
to Main Panel*
# of
Terminals
on plug
240 60 1 40 50
8-3 plus ground (less than 130’)
6-3 plus ground (up to 130’)
4
240
60
1
48
60
6-3 plus ground
4
Table 1 – Wire Size Chart
* Use only solid copper wire.
WARNING
CAUTION