background image

ITALY   TERMO - BUILT IN - DSA  

7095703 - IT-EN-DE-FR 

 

21

With the lower register, the passage of primary air in the lower part of the cooker is regulated through the ash drawer and the grill in the 

direction of the fuel. The primary air is necessary for the combustion process. The ash drawer must be emptied regularly, so that the ash 

cannot block the primary air intake for combustion. The primary air also keeps the flame alive. 

The primary air register must be open a little during wood combustion, as otherwise the wood burns too quickly and the thermocooker may 

overheat. 

SECONDARY Air Register 

(upper knob on the furnace door  

Picture 1 at page 53

 pos. 

B

).

This knob must be open (i.e. turned completely to the right), in particular for the combustion of wood (see paragraph 

9.1

). The secondary 

air, passing between the double glass of the fire door, heats up and triggers the dual combustion, keeping the glass clean at the same time 

(register open). 

AUTOMATIC Thermostat 

(placed in the upper right-hand part of the back 

Picture 1 at page 53

 pos. 

C

)

The thermostat has the task of automatically increasing or decreasing combustion. 

Dependent on the position chosen, the thermostat will act on the valve which regulates the intake of air into the furnace, placed on the 

back of the cooker. Turn it in a clockwise direction from 0 to 5 to make up the fire and in an anti-clockwise direction to reduce combustion. 

As this is an extremely precise device, it is advisable to turn it carefully and never force the knob.

FLUE GAS Register 

Picture 1 at page 53 

Pos.

D

)

(Conversion from the cooker

 HOTPLATE USE

 – 

OVEN USE

 function to the cooker 

HEATING 

function)

In the central part of the instrument panel, there is the flue gas register, which can be recognised from its enamelled, labelled knob. 

When the register is positioned to the 

LEFT 

(on the pan symbol), the combustion gases flow above and around the oven (oven function 

– 

HOTPLATE USE – OVEN USE

); when positioned to the 

RIGHT

 (on the water symbol), the gases flow near the boiler, increasing the 

temperature evenly, favouring water heating inside it (cooker function 

HEATING USE

). 

IGNITION Register 

Picture 1 at page 53 

pos. 

E

).

On the front of the cooker, between the protective handrail and the flue gas register, there is the ignition register control lever, which can 

be recognised by a chrome-plated knob. 

This register must 

only 

be used to facilitate the ignition of fuel in the cooker. Pull the lever outwards from the cooker (register open).

IMPORTANT

 : during normal cooker operation, the register lever must remain completely inserted (pushed inwards on the cooker). In this 

way avoiding excessive fuel consumption and poor thermocooker output (register closed). 

6.  FLUE

Essential requirements for correct appliance operation:

•  the internal section must preferably be circular; 

•  the appliance must be thermally insulated and impermeable and built with suitable materials which are resistant to heat, combustion 

products and any condensation; 

•  there must be no narrowing and vertical passages with deviations must not be greater than 45°;

•  if already used, it must be clean;

•  the technical data from the instruction manual must be respected; 

If the flues are of a square or rectangular section, the internal edges must be rounded with a radius of not less than 20 mm. 

For the rectangular section, the maximum ratio between the sides must be ≤ 1.5.

A section which is too small causes a reduction in draught. A minimum height of 4 m is advisable. 

The following materials are 

FORBIDDEN

 and compromise the good operation of the appliance: asbestos cement, galvanised steel, rough 

and porous internal surfaces. 

Picture 8 at page 55

 shows some example solutions.

The minimum section must be 4 dm

2

 (for example 20x20 cm) for appliances whose pipe dimensions are less than 200 mm, or 6.25 

dm

2

 (for example 25x25 cm) for appliances with a diameter of more than 200 mm

.

The draught created by your flue must be sufficient but not excessive.

A section of the flue which is too large can present a volume which is too large to heat and therefore cause operating difficulties  for the 

appliance; to avoid this, it is necessary to intubate the appliance for its entire height. A section which is too small causes a reduction in 

draught.

The flue must be at a suitably distance from flammable or combustible material using suitable insulation or an air space. 

It is FORBIDDEN to pass system piping or air ducts inside the flue. It is also forbidden to create moveable or fixed openings on the flue 

itself, for the connection of further different appliances. 

6.1.  CHIMNEY POT

The flue draught depends on the suitability of the chimney pot.

It is therefore essential that, if built in a handcrafted way, the exit section is more than twice the internal section of the flue (

Picture 9 at page 55

).

As it must always go past the ridge of the roof, the chimney pot must ensure exhaust even in the presence of wind(

Picture 10 at page 56

).

The chimney pot must meet the following requirements:

•  have an internal section equivalent to that of the chimney.

•  have a useful exit section of double the internal section of the flue.

•  be built so as to prevent rain, snow or any foreign body entering the flue. 

•  be easy to inspect, for any maintenance and cleaning operations. 

6.2.  CONNECTION TO THE CHIMNEY

Products with automatic door closing (type 1) must operate, for safety reasons, with the furnace door closed (except during the fuel loading 

Summary of Contents for ITALY TERMO Built In DSA

Page 1: ...SVORSCHRIFTEN BEI DEN AUSR STUNGEN Um die Sicherheitsvorschriften zu beachten ist es notwendig unsere Produkte vorsichtig nach den in diesem Handbuch enthaltenen Anweisungen zu installieren und anzuwe...

Page 2: ......

Page 3: ...e materials which will get in touch with food are suitable for alimentary use according to the a m CE regulation KONFORMIT TSERKL RUNG DES HERSTELLERS Betreff Fehlen von Asbest und Kadmium Wir best ti...

Page 4: ...IT EN DE FR PRIMA DELL INSTALLAZIONE ESEGUIRE LE SEGUENTI VERIFICHE BEFORE THE INSTALLATION PERFORM THE FOLLOWING CHECKS VOR DER AUFSTELLUNG FOLGENDE PR FUNGEN AUSF HREN AVANT L INSTALLATION IL FAUT R...

Page 5: ...NE INSTALLATION LAY OUT ALLGEMEINES INSTALLATIONSSCHEMA THERMOK CHE INSTALLATION SCHEME 47 14 SCHEDA TECNICA TECHNICAL DATA SHEET TECHNISCHES DATENBLATT FICHE TECHNIQUE 52 EN CONTENTS 1 TECHNICAL DATA...

Page 6: ...ALLAZIONE INSTALLATION LAY OUT ALLGEMEINES INSTALLATIONSSCHEMA THERMOK CHE INSTALLATION SCHEME 47 14 SCHEDA TECNICA TECHNICAL DATA SHEET TECHNISCHES DATENBLATT FICHE TECHNIQUE 52 DE INHALTSVERZEICHNIS...

Page 7: ...dit con maniglie in mm Peso in Kg Distanze di sicurezza antincendio Capitolo SICUREZZA Diametro 200 mm utilizzabile con canna fumaria non inferiore a 6 m Per edifici il cui isolamento non corrisponde...

Page 8: ...ella stanza dove sar installato vi sia una ventilazione adeguata presenza di presa d aria vedi capitolo 7 evitare l installazione in locali con presenza di condotti di ventilazione collettivo cappe co...

Page 9: ...CUSTICO 7 ALLARME ACUSTICO 8 INDICATORE DI TEMPERATURA 9 INDICATORE DI PRESSIONE 10 SISTEMA DI CIRCOLAZIONE IMPORTANTE i sensori di sicurezza della temperatura devono essere a bordo macchina o a una d...

Page 10: ...di legno stoffe ecc Figura 2 a pagina 53 pos B Il prodotto deve funzionare esclusivamente con il cassetto cenere inserito I residui solidi della combustione ceneri devono essere raccolti in un conten...

Page 11: ...ll acqua al suo interno funzione cucina USO RISCALDAMENTO Registro ACCENSIONE Figura 1 a pagina 53 pos E Sulla facciata della cucina tra il corrimano di protezione e il registro fumi si trova la leva...

Page 12: ...na sensibile perdita di carico che dovr eventualmente essere compensata con un innalzamento della canna fumaria il tratto orizzontale non dovr comunque mai superare i 2 metri UNI 10683 2005 ogni curva...

Page 13: ...omunque essere assicurata una buona ventilazione dell ambiente Alla prima accensione Vi consigliamo di caricare una quantit ridotta di combustibile e di aumentare lentamente la resa calorifica dell ap...

Page 14: ...iodi di non utilizzo deve rimanere chiusa Il potere calorifico nominale della termocucina viene raggiunto con un tiraggio depressione minimo di 17 20 Pa 1 7 2 mm di colonna d acqua Bisogna pertanto us...

Page 15: ...bile le superfici di scambio in grado di cedere calore all acqua il registro fumi andr tenuto aperto in modo da favorire la fuoriuscita dei fumi caldi dopo aver scaldato la piastra in ghisa Onde evita...

Page 16: ...lasciare sempre 3 4 cm di cenere nel focolare ATTENZIONE le ceneri tolte dal focolare vanno riposte in un recipiente di materiale ignifugo dotato di un coperchio stagno Il recipiente va posto su di un...

Page 17: ...afety distances Chapter SAFETY 200 mm diameter can be used with flue of no less than 6 m For those buildings in which the thermal insulation does not correspond to the instructions on heat protection...

Page 18: ...sure that the floor can support the weight of the appliance and if it is made of flammable material provide suitable insulation Make sure that there is adequate ventilation by means of an air intake...

Page 19: ...tinues discharge should the valve be damaged 4 CLOSED EXPANSION Tank 5 PUMP CONTROL THERMOSTAT 6 NOISE ALARM ACTIVATION THERMOSTAT 7 NOISE ALARM 8 TEMPERATURE INDICATOR 9 PRESSURE INDICATOR 10 PUMP SY...

Page 20: ...resistant container The Product must never be on in the presence of gaseous emissions or vapours for example glue for linoleum petrol etc Never deposit flammable materials near the Product During comb...

Page 21: ...this way avoiding excessive fuel consumption and poor thermocooker output register closed 6 FLUE Essential requirements for correct appliance operation the internal section must preferably be circular...

Page 22: ...ion it is MANDATORY that in the place itself a sufficient quantity of air is introduced If windows and doors are airtight e g built according to energy saving criteria it is possible that the fresh ai...

Page 23: ...st be subjected to various start up cycles in order to allow all the materials and the varnish to complete the various elastic stresses in particular at the beginning it is possible to notice the emis...

Page 24: ...ive fuel consumption is avoided register closed The register regulation necessary in order to obtain nominal calorific output is the following Fuel PRIMARY air SECONDARY air Wood length 30cm circumfer...

Page 25: ...hermo fireplace is not used A possible no use during winter season must be faced by adding antifreeze substances After having performed the cleaning of the hearth of the stack and of the flue removing...

Page 26: ...ped with an airtight cover The recipient must be placed on fireproof flooring away from flammable materials until the ash is completely out and cool IMPORTANT if for whatever reason the grill is remov...

Page 27: ...heitsabst nde zur Brandverh tung Kapitel BRANDSCHUTZ Durchmesser 200 mm nutzbar mit Rauchabzug nicht unter 6 m F r Geb ude deren W rmed mmung nicht der W rmeschutzverordnung entspricht betr gt das Rau...

Page 28: ...ungsherds zu unterrichten damit er seinen ordnungsgem en Anschluss an den Rauchabzug und dessen Leistungsverm gen berpr fen kann Vor der Installation folgende Pr fungen ausf hren Pr fen dass der Boden...

Page 29: ...rieb ist W hrend der Winterzeit erfordert eine Zeit des Stillstands gegebenenfalls die Zugabe von Frostschutzmittel 3 2 GESCHLOSSENEM Ausdehnungsgef Die Anlage mit GESCHLOSSENEM Ausdehnungsgef muss VE...

Page 30: ...der Aufstellung des Ofens auf brennbarem Material muss man die im Kontakt mit dem Ger t stehenden entflammbaren Bauteilen mit einer Schicht aus feuerfesten Material ersetzen z B Keramik Stein Glas od...

Page 31: ...ten Kugelknopf erkennbar und gekennzeichnet ist Wird der Regler nach LINKS auf das Pfannensymbol gestellt flie en die Verbrennungsgase ber und um den Ofen K chenfunktion KOCHPLATTENVERWENDUNG OFENVERW...

Page 32: ...dukt mit dem Rauchabzug verbindet Bei der Verbindung sind diese einfachen aber u erst wichtigen Grunds tze zu beachten Auf keinen Fall darf ein Rauchkanal benutzt werden der einen geringeren Durchmess...

Page 33: ...ge vollst ndig mit Wasser gef llt ist dies w rde zu einer sehr schweren Besch digung der gesamten Einrichtung f hren BEI VOLLST NDIGEM ODER TEILWEISEN FEHLEN DES WASSERS KEINESFALLS DAS FEUER IM GER T...

Page 34: ...t durch die Garantie gedeckt 9 1 NORMALER BETRIEB ACHTUNG Auf keinen Fall darf das Feuer angez ndet werden bevor die Anlage vollst ndig mit Wasser gef llt ist dies w rde zu einer sehr schweren Besch d...

Page 35: ...werden Die Abgase treten nicht mehr vollst ndig aus intensiver Gasgeruch In diesem Fall sollten Sie den Rost h ufiger r tteln und die Verbrennungsluft erh hen Legen Sie dann eine geringere Brennstoffm...

Page 36: ...n deshalb nur durch mechanische Schocks St e oder heftiges Schlie en der T r usw verursacht werden Daher f llt die Auswechslung nicht unter die Garantie 11 3 REINIGUNG DES ASCHEKASTENS Alle Ausr stung...

Page 37: ...n m Profondeur de la cuisini re thermique avec poign es en m Poids en Kg Distances de s curit Chapitre S CURIT Diam tre de 200 mm utilisable avec conduit de fum e non inf rieur 6 m Pour des difices do...

Page 38: ...er que le sol puisse supporter le poids de l appareil et proc der son isolation dans le cas o il serait construit en mat riel inflammable s assurer que la pi ce o sera install l appareil soit suffisam...

Page 39: ...maximum admise pour l installation est de 3 bar m me que 30 m de colonne d eau des pression sup rieurs peuvent provoquer des d formations et des ruptures de la chaudi re 2 VANNE M LANGEUSE THERMOSTAT...

Page 40: ...mable Par exemple c ramique pierre vitre ou acier etc La partie de la paroi remplac e doit avoir la m me largeur du po le et en comptant du sol doit d passer la partie sup rieure du po le au moins de...

Page 41: ...ion s coulent au dessus et autour du four fonction cuisini re USAGE PLAQUE USAGE FOUR quand au contraire il se positionne droite sur le symbole de l eau les gaz s coulent pr s de la chaudi re en augme...

Page 42: ...ours horizontal du canal de fum e provoque une perte sensible de charge qui devra tre ventuellement compens e par un exhaussement du conduit de fum e la partie horizontale ne devra jamais d passer en...

Page 43: ...NS CE CAS LA GARANTIE SUR L APPAREIL NE SERAIT PLUS VALABLE IMPORTANT Au moment de la premi re mise feu il est in vitable qu une odeur d sagr able se diffuse elle est due au s chage des colles dans la...

Page 44: ...tomatique type 1 type A1 doivent obligatoirement fonctionner pour des raisons de s ret avec la porte du foyer ferm e exception faite pour la phase de remplissage du combustible ou l ventuelle liminati...

Page 45: ...t les raccordements la chemin e soient herm tiques 9 5 UTILISATION COMME UNE CUISINI RE NORMALE ATTENTION En aucun cas il ne faut allumer le feu avant que l installation ait t totalement remplie d eau...

Page 46: ...ter de le remplir compl tement pour ne pas surchauffer la grille Nous vous conseillons en outre de laisser toujours 3 4 cm de cendre dans le foyer ATTENTION Les cendres enlev es du foyer doit tre plac...

Page 47: ...Nordica S p a will be sanctioned from the laws IT LEGENDA EN KEY C Circolatore C Circulator CM Collettore Mandata CM Supply collector CR Collettore Ritorno CR Return collector F Flussostato F Flow sw...

Page 48: ...CL C Pumpe C Circulateur CM Kollektor Zulauf CM Collecteur refoulement CR Kollektor Rucklauf CR Collecteur d foulement F Flussmesser F Fluxostat M Manometer M Manom tre P Pumpe P Circulateur P1 Pumpe...

Page 49: ...DI ACQUA SANITARIA DA BOILER M Tubo di carico Load pipe Zufuhrrohr OFF ON 1 2 3 4 5 6 T 1 2 3 4 5 6 7 20 7 C V VECTS V V 6 bar VSP Bollitore CM CR VMTA S 9196632 16 02 2009 VDM VB VST T M V VEAC VSP 1...

Page 50: ...RMOPRODOTTO OFF ON 1 2 3 4 5 6 T 1 2 3 8 5 6 7 9 20 7 C T Boiler VSP 95 C M VMTA 9196627B 19 11 2009 VST TS 3 bar VR V VEC VR VEC VR VR VEC VSP 6 bar VB VMS CM CR V V TERMOPRODOTTO IMPIANTO a vaso chi...

Page 51: ...OTTO DSA LA NORDICA CON ABBINATA PRODUZIONE DI ACQUA SANITARIA DA ACCUMULO SANITARIO M OFF ON 1 2 3 4 5 6 T 3 3 5 6 7 7 12 11 10 20 21 20 A B C D 20 IT EN DE FR A ON OFF ON OFF ON OFF ON OFF B SET Val...

Page 52: ...4 Scarico fumi Smoke outlet Au enlufteintritt Sorties des fum es A ENTRATA Sistema integrato DSA INLET Integration System DSA EINGANG Integriert System DSA ENTR E System int gr DSA B Sonda valvola VST...

Page 53: ...Figura 1 Picture 1 Abbildung 1 Figure 1 Figura 2 Picture 2 Abbildung 2 Figure 2 ITALY TERMO BUILT IN DSA 7095703 IT EN DE FR 53 1 2 A 100 20 20 NO SI SI B 50 50 C A C B D E...

Page 54: ...gure 6 ITALY TERMO BUILT IN DSA 54 7095703 IT EN DE FR TERMOPRODOTTO 55 3 2 1 M R CB 3 7 4 5 6 D A B C A Chiusura ermetica Hermetic closure Hermetischer Fermeture herm tique B Tubo acciaio Inox Stainl...

Page 55: ...irkungsgrad 40 viter conduits de chemin e avec section rectangulaire interne dont le rapport soit diff rent du dessin Efficience 40 m diocre 1 Comignolo industriale ad elementi prefabbricati consente...

Page 56: ...f vom Dach depuis le toit 45 1 30 m 0 50 m oltre il colmo above the roof ridge vom First outre la ligne de fa te 1 30 m 2 00 m dal tetto from the roof vom Dach depuis le toit 60 1 20 m 0 50 m oltre il...

Page 57: ...ort d essai RRF 15 11 2729 EN 12815 Informazioni marcatura CE CE Marking information Auszeichnungsinformationen Informations marquage CE Vedi allegato See enclosure Siehe Beilage Voir annexe Condizion...

Page 58: ...zio ammessa Maximum operating pressure Maximale Betriebsdruck Pression hydrique de service maximum autoris e 3 bar Temperatura gas di scarico Flue gas temperature Abgastemperatur Temp rature gaz d cha...

Page 59: ......

Page 60: ...dend Die Firma beh lt sich vor ohne Vorank ndigung nderungen und Verbesserungen vorzunehmen La Maison constructrice n est pas tenue respecter ces donn es et ces mod les elle se r serve le droit d appo...

Reviews: