4
Parameter
Default Value
Delay
(secs.)
Lead Acid
Nickel Cadmium
Re-Transfer Mode
Automatic
20
Preferred Source
Inverter
Load Window High
+20%
Load Window Low
-20%
Utility Voltage High
+10%
10
Utility Voltage Low
-10%
Inverter Voltage High
+10%
10
Inverter Voltage Low
-10%
Low DC Voltage
1.98 V/C
1.20 V/C
5
Low DC Voltage Reset
2.10 V/C
1.25 V/C
Low DC Voltage Shutdown
1.73 V/C
1.10 V/C
5
Low DC Voltage S.D. Reset
2.05 V/C
1.35 V/C
High DC Voltage Shutdown
2.45 V/C
1.60 V/C
5
High DC Voltage S.D. Reset
2.40 V/C
1.55 V/C
Current Limit
150% of Nominal Output Current
Transfer Time
1 Millisecond
Hit Counter
8
Table 1
–
Inverter Factory Default Values
NOTE:
V/C
–
Volts per Cell.
3
Adjusting Parameters
All equipment is shipped from the factory fully tested and set per model number. Do not make any
adjustments unless the equipment has been powered-up and the settings have been determined to be
incorrect. If the settings have been determined to be incorrect, adjustments may be made as detailed
below.
3.1
Settings Menu
In the Settings Menu, the user can access and change various parameters. Access menus by pressing the
ENTER/MENU button on the front panel. Navigate using the UP, DOWN, ENTER, and BACK buttons. To
enter a submenu, use the ENTER button. To exit a submenu, use the BACK button. To exit the Settings
Menu, continue to press the BACK button until prompted to exit and save settings. Follow the prompts as
desired.
NOTE:
It is important to be aware that transfers are disabled in the calibration modes.