Re-Transfer Delay 

This setting is used to set the time the inverter will attempt to retransfer from the Alternate Source back 

to the Primary Source. The inverter must be in Auto Re-Transfer Mode for this setting to have any effect. 
The Re-transfer Delay may be adjusted from 0 to 20 seconds in 1-second increments, with 20 being the 
default.  

Load Window High

 

The  upper  allowable  limit  for  the  Load  Voltage  signal  may  be  set  in  terms  of  percent.  The  maximum 

allowable upper setting is +30% and the minimum allowable upper setting is +10%. The default is +20%. 
The setting is adjustable in 1% increments.  

Load Window Low

 

The  lower  allowable  limit  for  the  Load  Voltage  signal  may  be  set  in  terms  of  percent.  The  maximum 
allowable lower setting is -30% and the minimum allowable lower setting is -10%. The default is -20%.  
The setting is adjustable in 1% increments.  
 

3.1.3 

Utility Settings 

 

Utility Voltage High 

The maximum allowable/acceptable limit on the Utility Voltage defaults to the Output Voltage setting plus 
10% (

EX:

 The default setting for a 120VAC output inverter is 132VAC RMS

). Once the voltage is out of 

range, the utility source will be deemed unavailable and the inverter will transfer to the inverter source if 
available. 

Utility Voltage Low 

The minimum allowable/acceptable limit on the Utility Voltage defaults to the Output Voltage setting minus 
10% (

EX:

 The default setting for a 120VAC output inverter is 108VAC RMS

). Once the voltage is out of 

range, the utility source will be deemed unavailable and the inverter will transfer to the inverter source if 
available. 

Utility Delay 

This setting is used to set the amount of time the Utility Voltage must be within the upper and lower limits 
described above for the logic to consider the Utility Voltage to be within tolerance. The Utility Delay may 
be adjusted from 0 to 10 seconds in 1-second increments, with 10 being the default.  

 

3.1.4 

Inverter Settings 

Inverter Voltage High 

The maximum allowable/acceptable limit on the Inverter Voltage defaults to the Output Voltage setting 

plus 10% (

EX:

 The default setting for a 120VAC output inverter is 132VAC RMS

). Once the voltage is out 

of range, the inverter source will be deemed unavailable and the inverter will transfer to the utility source 
if available. 

Inverter Voltage Low 

The minimum allowable/acceptable limit on the Inverter Voltage defaults to the Output Voltage setting 

minus 10% (

EX:

 The default setting for a 120VAC output inverter is 108VAC RMS

). Once the voltage is out 

of range, the inverter source will be deemed unavailable and the inverter will transfer to the utility source 
if available. 

Inverter Delay 

This setting is used to set the amount of time the Inverter Voltage must be within the upper and lower 

limits described above for the logic to consider the Inverter Voltage to be within tolerance. The Inverter 
Delay may be adjusted from 0 to 10 seconds in 1-second increments, with 10 being the default.  
 

3.1.5 

Communications 

The communication settings menu changes depending on the type of communication protocol used in the 

inverter.  For  details  on  connection  and  operation  instructions,  refer  to  the  communication  instruction 
manual included with the inverter.  

 
 

 

Summary of Contents for Option 22D

Page 1: ...lamarchemfg com 106 Bradrock Dr Des Plaines IL 60018 1967 CPN 108859 Instruction Drawing Number P25 LOPT22D 1 Tel 847 299 1188 Fax 847 299 3061 Revision A01 Rev Date 01 21 ECN 22782 Operation Manual...

Page 2: ...roll through the information Status Indicator LEDs Auto Manual Retransfer LED is ON solid when the inverter is set to automatically transfer back to preferred source when available LED is ON blinking...

Page 3: ...ut DC voltage falls below the specified voltage threshold of the alarm for longer than the specified alarm delay setpoint The alarm will clear once the input DC voltage rises above the Low DC Voltage...

Page 4: ...V C Volts per Cell 3 Adjusting Parameters All equipment is shipped from the factory fully tested and set per model number Do not make any adjustments unless the equipment has been powered up and the s...

Page 5: ...e available The currently used source can be changed in this mode by pressing the Test Transfer button when in the main screen NOTE When in Manual Retransfer Mode the user will have to press the Test...

Page 6: ...ailable and the inverter will transfer to the inverter source if available Utility Delay This setting is used to set the amount of time the Utility Voltage must be within the upper and lower limits de...

Page 7: ...transfer time The higher the Hit Counter value the slower the transfer time will be Only adjust if absolutely necessary 3 1 9 Alarm Settings The Alarm Settings menu provides access to adjust basic set...

Page 8: ...8 Document Control and Revision History Part Number 108859 Instruction Number P25 LOPT22D 1 Issue ECN 16282 12 03 22782 01 21 16282 12 03...

Reviews: