15
1-30 Sec *5 Sec
*1.98 V/C
*2.45 V/C
*0.5 Amps
*90 VAC / 180
*Indicates Default Value
ESCR Battery Charger
Configure Mode
Settings
Operation
Function
*Manual
7 Days
14 Days
30 Days
Auto - AC Fail
Auto - Low DC
Adjustable
Volts/Cell
Temperature
Compensation
Enable
*Disable
Alarm Settings
Alarm Delay
Low VDC
High VDC
Low DC Current
AC Failure
Limit Current
Adjustable 50-
110%
*105%
Equalize Hours
Equalize Timer
Equalize Cycle
Factory Settings
Restore Default
(Except Basic
Settings)
1-144
*8 Hours
Configure/OK
Output Voltage and
Current
Number of Cells
12 Volt 10 Amp
24 Volt 10 Amp
*12 Volt 20 Amp
Basic Output
*6L 9NC 10NC (12V Mode)
*12L, 18NC, 20NC (24V Mode)
Float Voltage
Equalize Voltage
Adjustable
Volts/Cell
2.12-2.3 V/C *2.25 for LA
1.39-1.45 V/C *1.40 for NC
2.25-2.4 V/C *2.33 for LA
1.5-1.6 V/C *1.55 for NC
The flow chart below shows the available and default settings of each option in configure mode.
Table 9 - Configure Mode Flow Chart