Tank Sizing

Installation

Instructions

ATTENTION

The following is supplied for informational purposes

only.

Consult your LP gas supplier for specific requirements.

A tank is propane storage container ranging in size from 150

gallons to 10,000 gallons or larger.  For agricultural heating

applications, the tank sizes typically used are either 500

gallons or 1,000 gallons with 1,000 gallons being the most

common.  The size and quantity of tanks will vary and is

dependent on the total heating load at the site.

In determining tank size and quantity, several factors apply:

Total heat load of the building

--- To determine total load, add up the heat input

(expressed in BTUH) for all gas-fired heaters, 

pressure washers, water heaters, etc., that will be

drawing vapor from the tanks.

--- The heat input rating is located on the dataplate.

The coldest outside air temperature at night that the

tank(s) will be exposed to.

Percentage of propane remaining in the tank prior to

refill.  Your fuel gas supplier will inform you at what

level a refill will normally occur.

IMPORTANT

Minimum vaporization of propane from liquid to vapor

occurs when temperatures are coldest and liquid level

of propane in the tank is lowest.

Size the quantity of tanks for the lowest temperature

you can expect in your area.

Refer to the following table to identify the heat output of

tanks at various temperatures and levels of fullness.

EXAMPLE

--- Select 1,000 gallon tank.
--- Total heat load is 1,500,000 BTUH (6-AB250

Heaters).

--- Coldest nighttime temperature is -10º F.
--- Tanks to be refilled by LP gas supplier when liquid

propane level is 30%.

A. In the 1,000 gallon tank sizing chart, locate -10º F.

outside temperature.

B. Locate the column which identifies 30% of propane

remaining in the tank prior to refill.

C. The intersection of these two variables identifies the

heat input.  In this example, a 1,000 gallon tank can

supply 276,500 BTUH.  (See shaded area in table.)

D. To determine the total number of tanks required:  

Total Heat Load of Building

Heat Output of 1,000 Gallon Tank

or

1,500,000 BTUH/Building

276,500 BTUH/Tanks

NOTE:

Always round up fractions or decimals.  See example.

(Example:  5.4 tanks = 6 tanks).  This will give you some extra

capacity especially in cold weather, in the event your LP gas

supplier cannot refill your tanks immediately.

= 5.4 Tanks

(6 Tanks)

August 1999

2.3-1

1

Tank Size

Outside

Percentage of Liquid Propane

(Gallons)

Temps.

Remaining Prior to Refill

(Heat Input Expressed in BTUH)

º 

F.

80%

70%

60%

50%

40%

30%

20%

10%

0

532,800

488,400

444,000

400,000

355,000

311,000

266,000 200,000

500

-5

399,600

366,300

333,000

300,000

262,500

233,250

199,500 150,000

-10

266,400

244,200

222,000

200,000

177,500

155,500

133,000 100,000

-15

132,200

122,100

111,000

100,000

88,750

77,750

66,500

50,000

0

949,000

870,100

791,000

712,000

633,000

553,000

474,000 356,000

1,000

-5

711,900

652,575

593,250

534,000

474,750

414,750

355,500 267,000

-10

474,600

435,050

395,500

356,000

316,500

276,500

237,000 178,000

-15

237,300

217,525

197,750

178,000

158,250

138,250

118,500

89,000

NOTE: For above table, multiply the results obtained by one of the following factors if nighttime temperatures will

not reach 0

º 

F.:

Temperature

Multiplier

+5

º 

F.

1.25

+10

º 

F.

1.50

+15

º 

F.

1.75

+20

º 

F.

2.00

Summary of Contents for Pilot Light Ignition

Page 1: ...Pilot Light Ignition Installation and Service Guide Agricultural Animal Confinement Building Heaters 150 22003...

Page 2: ...ay not necessarily depict the actual heater model and are intended for reference only It is very important when using the guide to pay particular attention to any Warning or Caution statements printed...

Page 3: ...ead to property damage personal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided within this guide can result in Death Serious bodily inju...

Page 4: ...uirements 2 8 Thermostat Wiring Models 346 348 377 379 408 410 2 9 1 AS040 2 9 2 AB200 and AB250 2 9 3 Indoor Installation Hanging Instructions 2 10 Air Diverters Two Piece 2 11 1 One Piece 2 11 2 Sec...

Page 5: ...safe clearances to combustibles burner manifold pressure maximum and minimum allowable inlet pressures etc Typical Location Interior or exterior of burner end access panel Part No Varies with design s...

Page 6: ...24 x 19 x 30 21 1 4 x 14 1 2 x 16 3 4 TOP SIDES BACK BLOWER OUTLET GAS L P Gas Supply 6 ft 1 83 m SUPPLY Natural Gas Supply N A 55 90 110 39 61 100 129 43 346 348 377 379 408 410 AS040 L P Natural L...

Page 7: ...l L P Natural Gas Gas Gas Gas M Mo od de el l Ventilation Air Required to Support Combustion Net Weight lbs Shipping Weight lbs Electrical Supply Volts Hz Phase Amp Draw Dimensions Inches L x W x H Mi...

Page 8: ...de headaches dizziness and difficulty in breathing Symptoms of improper combustion affecting livestock can be disease lower feed conversion or death Asphyxiation H Hazard Some p people c cannot s smel...

Page 9: ...e b For Canadian Installations and Applications CAN1 B149 1 or CAN1 B149 2 Installation Codes CSA C22 1 Part 1 Standard Canadian Electrical Code CSA C22 2 No 3 Electrical Features of Fuel Burning Equi...

Page 10: ...o not relight the heater until you are sure that all gas that may have accumulated has cleared away In any event do not relight the heater for at least 5 minutes 15 Non hanging heater installations th...

Page 11: ...te alarms 6 Take time to explain to your customer how to operate and maintain the heater by using this Service Guide Make sure your customer knows how to shut off the gas supply to the building and al...

Page 12: ...measured in inner diameter I D Piping planning and installation must be done by an experienced qualified LP gas installation agency b The minimum pipe size normally used in many situations is 1 2 in n...

Page 13: ...ld use 1 2 inch pipe Fig 2 EXAMPLE Perform pipe sizing for building Total heat load is 1 500 000 BTUH Quantity 6 250 000 BTUH heaters Building is 300 ft long x 40 ft wide Section BTUH LP Gas Pipe Size...

Page 14: ...erature is 10 F Tanks to be refilled by LP gas supplier when liquid propane level is 30 A In the 1 000 gallon tank sizing chart locate 10 F outside temperature B Locate the column which identifies 30...

Page 15: ...y be subjected to abrasive action or physical damage due to vehicular traffic or other causes it must be placed not less than two feet below grade or otherwise protected against such physical damage R...

Page 16: ...the installation may not be obtained It is almost impossible to set all regulators at the identical pressure Therefore the regulator delivering the highest outlet pressure will backpressure the other...

Page 17: ...stions 6 The heater s gas regulator with pressure relief valve should be installed outside of building Any regulators inside the buildings must be properly vented to the outside Local state and nation...

Page 18: ...ak d detectors Make certain that a sediment trap is installed at the gas valve inlet to prevent foreign materials pipe compound pipe chips and scale from entering the gas valve Debris blown into the g...

Page 19: ...ed three wire electrical supply consisting of separate hot neutral and ground leads shall be connected to each electrical outlet that supplies each heater Proper voltage must be supplied to each heate...

Page 20: ...s to squeeze the strain relief and wire bundle together to allow installation of the strain relief back into the junction box 6 Connect the black thermostat cord lead to the lead labeled power supply...

Page 21: ...l supply and close all fuel supply valves to the inlet of the heater 2 Remove the motor access panel located on the back of the case assembly 3 Remove the electrical enclosure cover 4 Remove the elect...

Reviews: