Installation Instructions

GENERAL

Direct fired heaters discharge combustion by-products with

the heated air in to the area being heated.  These include

CO, CO

2

, NO, NO

2

, and Ethylene.  These gases can result in

harm to the worker or the plants.

The GreenGro greenhouse heater has been specifically

developed for very low levels of these combustion by-

products.  However, it is necessary to have an exchange of

air within the greenhouse to avoid accumulation of these

gases to a harmful level over an extended period of

operating time.

Greenhouses have a natural air leakage factor.  This natural

leakage is influenced by the design and physical condition

of the greenhouse as well as wind conditions and other

factors.  This natural leakage factor can not be relied upon

as being sufficient to provide the necessary air exchange

within the greenhouse.  Proper installation of the GreenGro

greenhouse heater must include provision for adequate air

exchange as follows:

Indoor M

Mounted H

Heater:

-- An exhaust fan capable of providing at least 

300 cfm of discharge air.

-- An inlet shuttered louver of at least 120 sq. in. area.

-- The inlet shutters must be electromachanically

operated and electrically interlocked with the heater

such that the heater can not operate if the inlet

shutters do not open when heating is required.

Outdoor M

Mounted H

Heater:

-- An exhaust shuttered louver of at least 120 sq. in.

area.

-- The exhaust shutter must be electromechanically

operated and electrically interlocked with the heater

such that the heater can not operate if the exhaust

shutters do not open when heating is required.

1. Read all safety precautions and follow L. B. White

recommendations when installing this heater.  If

during the installation or relocating of heater, you

suspect that a part is damaged or defective, call a

qualified service agency for repair or replacement.

2. Make sure the heater is properly positioned before use

and is hung level.  Observe and obey all minimum safe

distances of the heater to the nearest combustible

materials.  Minimum safe distances are given on the

heater nameplate and on page 4 of this manual.

3. The heater may be used either indoors or outdoors.

For heaters intended for outdoor installation, the

heater is to be installed at least 18 inches above the

ground or to a height that would prevent snow

blockage of heater’s air inlet.  Refer to instructions

provided in the optional L.B. White outdoor mounting

and ducting kit, part number 23578.

4. The heater must have the proper gas regulator installed

for the application.  A regulator must be connected to

the gas supply so that gas pressure at the inlet to the

gas valve is regulated within the range specified on the

dataplate at all times.  Contact your gas supplier, or the

L.B. White Co., Inc. if you have any questions.

5. The heater’s gas regulator (with pressure relief valve)

should be installed outside of building.  Any regulators

inside the buildings must be properly vented to the

outside.  Local, state and national codes always apply

to regulator installation.  Natural gas regulators with

vent limiting device may be mounted indoors without

venting to outdoors.

6. All gas pressure regulators must be installed in strict

accordance with the manufacturer’s safety instructions.

These instructions accompany each regulator.

7. Insure that all accessories that ship within the heater

have been removed from inside of heater and

installed.  This pertains to air diverters, hose,

regulators, etc.

8. Make certain that a sediment trap is installed at the

gas valve inlet to prevent foreign materials (pipe

compound, pipe chips and scale) from entering the

gas valve.  Debris blown into the gas valve may cause

that valve to malfunction resulting in a serious gas

leak that could result in a possible fire or explosion

causing loss of products, building, or even life.  A

properly installed sediment trap will keep foreign

materials from entering the gas valve and protect the

safe functioning of that important safety component.  

9. Any heater connected to a piping system must have

an accessible, approved manual shut off valve

installed within six feet (6 ft.) of the heater it serves.  

10. Check all connections for gas leaks using approved

gas leak detectors.  Gas leak testing is performed as

follows:  

-- Check all pipe connections, hose connections,

fittings and adapters upstream of the gas

control with approved gas leak detectors.  

-- In the event a gas leak is detected, check the

components involved for cleanliness and

proper application of pipe compound before

further tightening.  

-- Furthermore tighten the gas connections as

necessary to stop the leak.  

-- After all connections are checked and any

leaks are stopped, turn on the main burner.  

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that

could cause flashback.  

7

WARNING

Fire aand EExplosion H

Hazard

Do not use open flame (matches, torches, candles,

etc.) in checking for gas leaks.  

Use only approved leak detectors.  

Failure to follow this warning can lead to fires or

explosions.

Fires or explosions can lead to property damage,

personal injury or loss of life.

Summary of Contents for FUEL HD120

Page 1: ...idence in our products and welcome any suggestions or comments you may have call us toll free at 1 800 345 7200 Owner s Manual and Instructions GreenGro Plus Greenhouse Heaters ATTENTION ALL USERS Thi...

Page 2: ......

Page 3: ...nal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage o...

Page 4: ...nce or if you have any questions about the use of the equipment or its application The L B White Co Inc has a policy of continuous product improvement It reserves the right to change specifications an...

Page 5: ...et and exhaust outlet do not open when heating is required HD120 Propane Natural Gas Gas M Mo od de el l Indoor Mounting Air Exchange Requirements 1 Burner Manifold Pressure In W C Net Weight lbs Ship...

Page 6: ...ans leading to serious injury or death Symptoms of carbon monoxide poisoning can include headaches dizziness and difficulty in breathing Asphyxiation H Hazard Some p people c cannot s smell w well S S...

Page 7: ...high limit switch and an air proving switch Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features are fully functioning 6 Do n...

Page 8: ...mber 23578 4 The heater must have the proper gas regulator installed for the application A regulator must be connected to the gas supply so that gas pressure at the inlet to the gas valve is regulated...

Page 9: ...Manual Make sure you know how to shut off the gas supply to the building and also to the individual heater Contact your fuel gas supplier if you have any questions 17 Any defects found in performing...

Page 10: ...chain hanging kit part number 08748 Refer to the following instructions and illustrations 1 Assemble eyebolts and chain according to the illustration and tighten all eyebolts securely See Fig 2 FIG 2...

Page 11: ...THERMOSTAT GROUND BROWN RED RED YELLOW YELLOW WHITE BLACK WHITE BLACK GREEN 8 9 10 HI LO YELLOW BLUE RED NIPPLE HOSE ADAPTER TEE NIPPLE CAP TO GAS CONTROL...

Page 12: ...ctrical connection jumper between relays in building control to allow staging transition of gas control valve D Heat V Vent B Building C Control C Connections Using N Non P Powered C Contacts Remove j...

Page 13: ...er at terminals 1 and 2 Remove black leads at terminals 3 and 4 to selector switch Remove white leads at terminal 6 to selector switch Add neutral s of control contacts at terminal 5 HEAT MODE Add con...

Page 14: ...4 The direct spark ignition DSI control board within this heater is self diagnostic The board works in conjunction with a light emitting diode L E D built into the selector switch The L E D will flash...

Page 15: ...Periodic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage 1 The area surrounding the heater shall be kept clear and free from combustible...

Page 16: ...on FIG 9 AIR PROVING SWITCH Service Instructions 1 Close the fuel supply valve to the heater and disconnect the heater s electrical supply before servicing unless it is necessary to have the valve ope...

Page 17: ...R AND FLAME SENSOR BLOWER OUTLET OF HEATER AIR PROVING SWITCH ARM OF FLAPPER AIR PROVING SWITCH ARM FANWHEEL PIVOT POINT OF FLAPPER EDGE OF FLAPPER PIVOT POINT OF FLAPPER FLAPPER 31 7 MMTO 34 9 MM 1 E...

Page 18: ...om the switch which indicates the contacts of the switch have opened Check for lack of electrical continuity across the switch terminals to verify contacts have opened 5 Allow the switch cool down for...

Page 19: ...let pressure gauges agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that specified o...

Page 20: ...s Page A Motor Does Not Run 24 B Motor Hums Does Not Run 24 Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing...

Page 21: ...Are 24 Volts Supplied from Transformer No No No No No Yes Is Proper Voltage Supplied to Transformer No Yes Yes No See One Time Flash L E D Light is Defective Replace Ignition Control Check Dataplate...

Page 22: ...ns Yes Repair Air Proving Switch One T T ime Flash P P attern Begins Immediately After C C ondition Occurs Is Air Proving Switch Stuck Closed Check Continuity Is Airflow Switch Binding Repair Yes Yes...

Page 23: ...Proving Switch No Is Fan Loose On Motor Shaft Yes Tighten Fan Blade Set Screw Is Proper Voltage Supplied to Fan Motor No Yes Defective Motor or Capacitor Replace Motor or Capacitor Is Ignition Module...

Page 24: ...curs T T he Module H H as Gone i i nto S S afety Lockout Is Proper Fuel Supplied to Heater Inlet Connect Proper Fuel Supply to Heater Open All Gas Shutoff Valves Yes No Is Proper Gas Pressure Supplied...

Page 25: ...onnections Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No VENTI...

Page 26: ...TER MALFUNCTION CHECK FOR PROPER OPERATION AFTER SERVICING WARNING THIS HEATER MAY START AT ANY TIME FAN MOTOR TRANSFORMER AIR PROVING SWITCH BLUE BLUE HIGH VOLTAGE IGNITION LEAD IGNITER FLAME SENSOR...

Page 27: ...lexible connector used to convey gas from supply line in building to heater Heat Chamber Metal fire box within the heater that provides an area where burner flame mixes with combustion air thereby pro...

Page 28: ......

Page 29: ...Switch High Limit 05566 18 Chamber Heat 23566 19 Case Assembly with Doors and Latches 2 20465 20 Latch Assembly 20959 21 Harness Wiring 23534 22 Control Ignition 22461 23 Transformer 120 24 v 81218 2...

Page 30: ...date o of p purchase by t the e end u user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later t...

Reviews: