REGULATOR TANK  PRESSURE

REDUCED TO 5 PSIG (345 MBAR)

TANK

REGULATOR SECOND STAGE 5 PSIG (345 MBAR) INLET

300' (91.4m)

QUATITY 6 - 50,000 BTUH HEATERS (14,654 WATTS)

TOTAL LOAD = 300,000 BTUH (87,925 WATTS)

40'

(12.2M)

20'

(6M)

50'

(15.2M)

50'

(15.2M)

30'

(9.1M)

30'

(9.1M)

50'

(15.2M)

50'

(15.2M)

50'

(15.2M)

20'

(6M)

A

B

C

D

G

H

E

F

have an experienced gas installation agency size and
install all fuel gas piping.

Pipe sizing is critical to the proper operation of any gas
heating system.  However, piping is dependent on several
factors:

1. Total gas load expressed in BTUH.

2. The gas pressure to be supplied through the piping

system.  This pressure may be expressed in pounds
of pressure per square inch (P.S.I.) or (BAR) or inches
of water column or (MBAR).

3. Distance that the gas must travel to feed the

appliance furthest from the regulator.

This section will explain to you how to size piping for the
heaters through the use of pipe sizing tables and a typical
example.  In all cases with this example, we will be using
only pounds of pressure, expressed as 5 psig (345 BAR)
and not inches of water column.

INSTRUCTIONS

a. Determine total gas demand for entire system, by

adding up BTU/hr. input from appliance nameplates
and adding demand for any future appliances.

b. Measure the length of piping required from outlet of

first stage regulator to the appliance furthest away.

No other length is necessary to do the sizing.  In this

example the distance from first stage regulator to

appliance furthest away is 230 ft. (70.10 M)

c. Make a sketch of the piping system and installation.

See Fig. 1.

EXAMPLE 
(Refer tto FFig. 2

2)

IMPORTANT: If exact length is not on chart, use next longer

length.  Select the size of pipe that shows at least as much

capacity as needed for each piping section.

a. Section A to B of pipe must supply the complete gas

load of 300,000 BTUH (87930 WATTS) for the entire

building.  Looking at the 5 PSIG (345 MBAR) sizing

chart, the size of pipe used in conveying gas would

need to be sized at 1/2 inch (19 MM) diameter pipe.

Note that even though furthest distance from first

stage regulator to appliance is 230 ft. (70 M), we use

the 250 ft. (76 M) length.

b. Section B to C must supply the load of 200,000

BTUH (58620 WATTS).  Select 1/2 inch (12.7 MM)

pipe for Section B to C.

c. Section C to D must supply a load of 150,000 BTUH

(43960 WATTS).  Select 1/2 inch (12.7 MM) pipe for

Section C to D.

d. Section D to E must supply a load of 100,000 BTUH

(29310 WATTS).  Select 1/2 inch (12.7 MM) pipe.

e. Sections E to F must supply 50,000 BTUH (14650

WATTS)  Select 1/2 inch (12.7 MM) pipe.

f. Sections B to C must supply 100,000 BTUH (29310

WATTS).  Use 1/2 inch (12.7 MM) pipe.

g. The final section, G to H, needs only 50,000 BTUH

(14650 WATTS) for gas usage.  This section would

use 1/2 inch (12.7 MM) pipe.

FIG. 1

10

Summary of Contents for 346JX

Page 1: ...WI 54650 800 345 7200 608 783 5691 Fax 608 783 6115 ATTENTION ALL USERS This heater has been tested and evaluated by C S A International in accordance with Standard ANSI Z83 7z CSA 2 14 and is listed...

Page 2: ...l injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or...

Page 3: ...provement It reserves the right to change specifications and design without notice SECTION PAGE General Information 3 Heater Specifications 4 Safety Precautions 5 Installation Instructions General 8 P...

Page 4: ...de el l Ventilation Air Required to Support Combustion Burner Manifold Pressure Electrical Supply Volts Hz Phase Amp Draw Starting Amps Includes Igniter Dimensions Inches L x W x H Minimum Safe Dista...

Page 5: ...g gas a and n natural g gas h have m man m made o odorants a added s specifically f for d detection o of f fuel g gas l leaks If a a g gas l leak o occurs y you s should b be a able t to s smell t the...

Page 6: ...with our local fire safety authority if you have questions about applications 6 Do not operate the heater with panels removed 7 Forced air heaters shall not be directed toward any propane gas supply...

Page 7: ...and ASME vessels have left hand threads Always use a wrench to make the connection and removal of the P O L fitting Do not use pliers Check for gas leaks 29 This heater is equipped with a ground wire...

Page 8: ...top leak tighten suspect pipe connections After all connections are checked turn on main burner Stand clear while main burner ignites to prevent injury caused from hidden leaks which could cause flash...

Page 9: ...roducts and or animals should be protected by a separate back up control system that limits high and low temperatures and also activates appropriate alarms 27 Take time to understand how to operate an...

Page 10: ...let of first stage regulator to the appliance furthest away No other length is necessary to do the sizing In this example the distance from first stage regulator to appliance furthest away is 230 ft 7...

Page 11: ...5 53 3 M 200 61 M 225 68 6 M 250 76 2 M 275 83 8 M 300 91 4 M 350 107 M 400 12 2 M 1 2 751 681 626 583 547 516 490 468 430 400 12 7 MM 220 KW 200 KW 183 KW 171 KW 160 KW 151 KW 144 KW 137 KW 126 KW 11...

Page 12: ...observe and obey minimum clearance distances to combustible materials as stated in the specification section of this owner s manual and on the heater itself FIG 5 NOTE REGULATORS SHOULD ALWAYS BE MOUN...

Page 13: ...TOR NIPPLE VALVE MANUAL SHUT OFF GAS HOSE ADAPTER SEDIMENTTRAP TO CONTROL VALVE INLET REGULATORVENT GAS FLOW 13 MANUAL SHUT OFF VALVE HOSE AND REGULATOR ASSEMBLY 1 Always use approved pipe thread comp...

Page 14: ...stays lit See Fig 8 FIG 8 IMPORTANT On new installations there will be air trapped in the gas supply line feeding the appliance The air will gradually be purged out by gas when the heater is first li...

Page 15: ...sect nests snow or ice on a regulator can block vents and cause excess pressure at the appliance 1 Before cleaning shut off all gas supply valves and disconnect electrical supply 2 The heater should h...

Page 16: ...nd of heater on case assembly 4 Remove thermostat cover and disconnect motor leads from wire nut and thermostat 5 Remove nuts that secure square motor mounting plate to L bolts on housing 6 Remove fou...

Page 17: ...er tight and snug it in place DO NOT OVERTIGHTEN OR USE UNNECESSARY FORCE ON THE NUT WHEN TIGHTENING Do not use pliers when removing or replacing the thermocouple Doing so will round off the attachmen...

Page 18: ...gas control valve are shown in the heater specifications table See page 4 The inlet pressure may need adjustment as necessary to achieve proper outlet pressure g After pressure have been checked shut...

Page 19: ...econds to to warm up thermocouple allow thermocouple to heat up properly Loose thermocouple Tighten thermocouple Defective thermocouple Replace thermocouple Pilot light frame dirty Clean pilot light f...

Page 20: ...e chatters Defective solenoid in gas valve Replace gas valve Gas pressure too high Check nameplate on heater for correct type of gas and operating pressure Improper voltage Check voltage supply agains...

Page 21: ...oper cleaning checking for proper gas pressures etc With any pilot light assembly always make sure the thermocouple is completely installed within the pilot bracket by either its mounting clip or nut...

Page 22: ...HED LINE ELECTRICAL CONNECTION DIAGRAM MOTOR NEUTRAL CABINET MOTOR GROUND SOLENOID S HIGH LIMIT SWITCH MOTOR THERMOSTAT AIR PROVING SWITCH ELECTRICAL LADDER DIAGRAM IF ANY OFTHE ORIGINALWIRE AS SUPPLI...

Page 23: ...the dual purpose of igniting the main burner and heating the thermocouple Pilot Safety Control Valve A gas control valve which is held open by electrical power supplied by a pilot generator and which...

Page 24: ...PARTS SCHEMATIC Parts Identification 6 7 8 9 10 11 14 15 19 20 21 22 23 12 13 16 17 18 27 25 26 29 28 24 1 2 3 5B 5B 5A 30 4 24...

Page 25: ...8 12 Burner 08026 13 Pilot Assembly w Orifice 02729 14 Orifice Pilot 02689 15 Tubing Pilot w Nuts 03032 16 Thermocouple 03497 17 Shield Pilot 08205 18 Base 06472 19 Motor 22495 20 Mount Motor 09870 21...

Page 26: ...e d date o of p purchase b by the e end u user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months lat...

Reviews: