Installation and Operation Manual
6
DX6LN PARAGON ERC-2 Controller Settings
Set the Paragon ERC-2 controller parameters as described in table below:
CloC = Set to local time
SEt = 32
dSPL = rSP°
CLHr = 12HR
°dSP = F°
dFtP = ELEC
EFAN = yES
CFAN = on
dFin = TdAy
CoFF = 0:00
Con = 0:00
Alrd = 0:00
CPrn = NA
nodF = 6
dEF1 = 00:00
dEF2 = 04:00
dEF3 = 08:00
dEF4 = 12:00
dEF5 = 16:00
dEF6 = 20:00
dEFd = 25
Fand = 0:00
Pudn = 0:00
DriP = 0:00
diF° = 1
tDEF = NA
dEF° = 47°
Fan = NA
ALLo = 27
ALHi = 60
Condensate Evaporation Pan Heater
The Condensate Evaporation Pan Heater has the following features:
•
Electrical Rating: 208V / 60Hz / 1 Phase, 6 ft case: 7.21A, 1500 W, 8 ft case: 14.42A, 3000W
12 ft case: 14.42A, 3000W
•
Condensate Dissipation Rate: 6 ft case: 9.3 gallons per day, 8 ft case: 18.5 gallons per day
12ft case: 18.5 gallons per day
•
3.75 Gallon Pan: (A) 6 ft: 1 pan, (B) 8 ft: 2 pans, (C) 12 ft: 2 pans
• Evaporation pan heater is UL Listed.
Buck and Boost Transformer (Optional)
A 1.5 KVA Buck & Boost transformer is an available option. The primary and secondary of the Buck & Boost trans-
former can be interconnected for use as an autotransformer to slightly step up or down voltages. When used as an
autotransformer to slightly adjust voltage, the Buck & Boost Transformer can carry loads in excess of its nameplate
rating.
Example: With the transformer wired to provide 208V output with 195V input, the load capacity of the transformer is
19.5 KVA.
When the Buck & Boost transformer option is chosen, the transformer is factory wired to provide 208V output with
195V input
.
The transformer connections can be rewired in the field to provide alternative buck and boost percent-
ages. Wiring instructions are provided on the transformer cover. Transformer is UL listed.