![Kyoritsu Electrical Instruments Works KEW3431 Instruction Manual Download Page 23](http://html.mh-extra.com/html/kyoritsu-electrical-instruments-works/kew3431/kew3431_instruction-manual_2017203023.webp)
̶ 21 ̶
8-4 LED insulation status indicator
KEW3431 has insulation status check function. In an insulation
measure-ment, the measured value is compared to the pre-set
reference value, and either red or green LED lights up according to
the result. This function can be turned off. See 10. How to disable
LED insulation status indicator & auto-lighting in this manual for
detail.
Reference values for each range
Nominal voltage
250V
500V
1000V
Reference value
0.25M
0.5M
1M
Reference values are determined based on the resistance value to
provide 1mA with the nominal voltage. The color of LED indicates
the result as follows.
Compared result
LED insulation status
indicator
> reference value
Solid green
< reference value
Solid red
LED insulation status indicator
Fig. 8-7