Digital OverVoltage Relay (GDR-C01) User's Manual V1.00
29 / 47
Kyongbo Electronics Co., Ltd.
T/S 1 in the above screen means No. 1 output connection.
Press
Key in T/S 1 screen, then it will exit this menu and convert to the upper menu.
Ÿ
System Config.
▶
T/S Output
▶
T/S 1
▶
1.CON Setting
It is a category to select in which condition to operate the output connection.
The types and meanings to connect output connection are as follows.
Connection
Description
OFF
Connection not used.
OVR
Output if OverVoltage element is in operation.
【
Table 6.4
】
T/S Connection Menus
Ÿ
System Config.
▶
T/S Output
▶
T/S 1
▶
2.RST Setting
It is a category to set which method should be used when the output connection is
recovered after the operation.
This relay has two methods, Self Mode and Manual Mode.
Self Mode is a function that the relay is automatically recovered after the operation,
and Manual Mode is a function that the relay is not automatically recovered, but
manually recovered. That is, it is not recovered until the user presses Reset (
)
Key, and is recovered when the Reset (
) Key is pressed.
Ÿ
System Config.
▶
T/S Output
▶
T/S 1
▶
3.DLY Setting
It is a category that can add to the recovery delay time on the recovery.
This menu is only applied when it is in Self Mode in the above 2. RST Setting, and
is not applied if it is in Manual Mode.
If DLY is set to 0.00, it recovers within 40ms, and if you want the recovery within
100ms, set it to be 0.06.
It can be set in the units of 0.01Sec from 0.00 to 60.00, and it recovers with the
error ratio of ±35ms if under 100ms, and the error ratio of ±5% if 100ms or more.
6.2.5.3
System Config.
▶
Password Setting
It is a category to change the Password Setting, and the password is set as 4
digits using the numbers from 0 to 9.
Select 3.Password category in Config., then the following screen appears.