Digital Integrated Protection Relay
K-PAM 5500 Series
9
Num
Category
Pin Number
Description
①
Output Contact
Terminal
(For CB Trip/Alarm)
T1
1
1a_NO
•For Close CB
•Contact Capacity : AC 250V 16A / DC 125V 30A
2
1b_NC
3
1_COM
4
2a_NO
•For Open CB
•Contact Capacity : AC 250V 16A / DC 125V 30A
5
2b_NC
6
2_COM
7
3a_NO
•For Alarm
•Contact Capacity : AC 250V 5A / DC 125V 10A
8
4a_NO
9
5a_NO
10
6a_NO
•For System Error
•Contact Capacity : AC 250V 5A / DC 125V 10A
11
6b_NC
12
3~6_COM
•3~6 Output Contact Common Terminal
②
Input Contact
Terminal
T2
1
D/I 1
•Input contact for breaker closing state
2
D/I 2
•Input contact for breaker open state
3
D/I 3
•User defined Input Contact
4
D/I 4
5
D/I 5
6
D/I 6
7
COM
•Input Contact Common Terminal
③
Aux Power Input Terminal
T3
1
+
•Relay Aux Power Input (AC /DC 110V ~ 220V)
2
-
④
Frame Ground
T3
3
Aux. FG
•Enclosure ground connection
⑤
Ethernet TP(RJ-45)
T5
-
-
•Modbus TCP (Option)
⑥
Analog Input
Terminal
T6
1
A/I #1
•DC 4~20mA Input Terminal (Option)
2
A/I #2
3
COM
⑦
CT/ZCT/VT Input Terminal
T4
1
IA+
•3Phase CT Input
2
IA-
3
IB+
4
IB-
5
IC+
6
IC-
7
IN+
•NCT Input
8
IN-
9
IZ+
•ZCT Input
10
IZ-
11
VA+
•3Phase VT Input
12
VA-
13
VB+
14
VB-
15
VC+
16
VC-
17
VN+
•EVT Input
18
VN-
⑧
RS-485 Terminal
T4
19
+
•Serial RS-485 communication terminal for
communication with the host system
20
-
21
COM
⑨
Frame Ground
T4
22
FG
•Enclosure ground connection