■ IDOCR Setting Method
① After selecting ‘DOCR (67)’ in Protection Relay Element Setting Method ④, press the RIGHT (
) Key.
② Select ‘IDOCR1’ or ‘IDOCR2’ by using UP (
) and DOWN (
) keys and press the RIGHT (
) key to
enter the setting screen.
③ Use the UP (
), DOWN (
) KEY to move the category you want to set, and then enter the ENTER ( )
KEY to pop up the password input screen. (initial password 0000)
④ Use the UP (
), DOWN (
) KEY to change the setting value and then press the ENTER ( ) KEY.
⑤ After completing the setting, press the LEFT (
) KEY to check whether the setting has been changed.
After selecting ‘Yes’ or ‘No’, the setting is completed when the ENTER key is pressed.
ENTER
ENTER
LCD Display
Category
Description
FUNCTION
Whether to use the function
Setting Range : ENABLED, DISABLED
DIRECTION
Operation Direction Setting
Setting Range : Forward, Reverse
PICK-UP
Current Pick-up Setting
Setting Range : 0.50 ~ 100.00A (0.01A STEP)
RCA
Reference Phase Angle Setting
- Setting Range : 0 ~ 359° (1° STEP)
MODE
INST/DT Setting
Setting Range : INST, DT
TIME DELAY
Operation Delay Time Setting
Setting Range : 0.04 ~ 60.00s (0.01s STEP)
VT LOSS BLK
Setting whether to use the voltage loss block function
Setting Range : ENABLED, DISABLED
BLOCK
Protection Blocking Condition Setting
- Setting Range : EASYLOGIC OPERAND
WAVEFORM
Whether to Record Waveforms
- Setting Range : ENABLED, DISABLED