1Class Digital Earth Leakage Detector (GD8-L05A, GD8-L05R) User’s Manual(V1.00) 

 
 
 

 

                                                                          12/17                                   

Kyongbo Electric Co., Ltd 

No Contents 

Description 

Measurement 

display 

ZCT primary earth leakage current RMS of each power system line is displayed on 7-
segment. 

2

 

Circuit display 

Applied power system line is displayed on 7-segment when ZCT connection test and 
earth leakage detector operate test. 
Applied power system line is displayed when Earth leakage fault occurred.

 

Circuit selection 

Switch 

Applied power system line selection when ZCT connection test and operation test. 
The circuit switch for checking the earth leakage detector operated power system line after 
occuring of earth leakage fault. 

Connection status 

LED 

When press the test switch, turn on the LED(yellow), if connection of ZCT with earth 
leakage detector was correct. 

Test Switch 

The test switch that is tested the ZCT connection status and earth leakage detector 
operation of each circuit. 

Power LED 

Turn on the power LED(green) when earth leakage detector power supply voltage is 
supplied. 

Alarm LED 

Turn on the alarm LED(red) when earth leakage detector operated. 

Reset Switch 

The Auto/Manual switch set to manual, and even if the earth leakage of power system 
line became to recover when the earth leakage detector operated, the operation status is 
continuous. if you want to restore, use this switch. 

Auto LED 

Turn on the Auto LED(green) when Auto/Manual switch be Auto. 

10 

Manual LED 

Turn on the Manual LED(yellow) when Auto/Manual switch be Manual. 

11 

Auto/Manual 

Switch 

Auto 

If earth leakage power system line is recover, earth leakage detector 
operation status is recover automatically. 

Manual 

Operation status is continuous even if earth leakage power system line 
became recovered. If want to recover, must press the reset switch. 

12 

Buzzer ON LED

Turn on the ON LED(green) when Buzzer ON/OFF switch be ON. 

13 

Buzzer OFF LED

Turn on the OFF LED(yellow) when Buzzer ON/OFF switch be OFF. 

14 

Buzzer ON/OFF 

Switch 

Buzzer 

ON 

Alarm sound is operate when the earth leakage fault occurred on state of 
Buzzer ON. 

Buzzer 

OFF 

Alarm sound is not operate when the earth leakage fault occurred on state 
of Buzzer OFF. 

15 

Detection 

sensitive setting 

Switch 

The nominal operating current of each circuit can be control until 0.2-0.5-1.0A(3 level 
control). 

16 

  Fuse Holder 

Fuse for protection 

17 

 Power ON/OFF 
    Switch 

Use when want to power ON/OFF of the earth leakage detector. 

18 

Buzzer Buzzer 

for 

alarm 

19 

External relay 

contacts 

The external Relay a contacts(1a~8a) and COM contacts of the each circuit.

   

(GD8-L05R only) 

20 

External 

connection 

contacts 

· P+, P-    : Power supply voltage connection contacts. 
· Ta, Tc      : Dry contacts for output. 
· Z1~Z8    : ZCT secondary input contacts of each circuit. 
· Zc 

: ZCT secondary circuit common contacts. 

· F.G 

: Frame Ground 

 

Summary of Contents for GD8-L05A

Page 1: ...1Class Earth Leakage Detector User s manual TYPE GD8 L05A GD8 L05R 2017 02 13 Version 1 00 Kyongbo Electric Co Ltd ...

Page 2: ...to read the user manual carefully and use the product accordingly The user manual must be kept in a place where it can be easily seen by the product user WARNING CAUTION SYMBOLS Safety Precautions This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to properties only Be sure not to do Be sure to follow the instruction ...

Page 3: ...electric shock Do not perform any wiring work when the main cable is live It may cause an electric shock and a damage or a fire by the charged voltage of the converter Do not disassemble the product even if the power is not on except for wiring or maintenance It may cause an electric shock by the charged current in the product Let the electrical technician to perform wiring test run and maintenanc...

Page 4: ...duct or a fire P P F G terminals enclose surge protection circuit inside the ELD so do not withstand voltage test Prevent screws metal parts water or oil from entering the product It may cause a damage to the product or a fire Extract and insert Case on a leveled surface Otherwise it may cause a damage to the product Do not store the product in a humid or a dusty area It may cause a damage to the ...

Page 5: ... Output Contacts 2 4 Case 2 5 Ground Element 2 6 Insulation Tests 2 7 Mechanical Tests 2 8 Temperature Tests 2 9 Other Operating Conditions 2 10 ZCT 3 Functional Description 3 1 Construction 3 2 Functions 3 3 Product Structure Appended 1 Dimensioned Drawings Appended 2 Internal Block Diagram Appended 3 External Connection Appended 4 ZCT Dimensioned Drawings 6 6 6 6 7 7 7 8 8 8 8 9 10 10 10 11 13 1...

Page 6: ...h Leakage Detector The Earth Leakage Detector and ZCT are convenient handling through compatibility Display the measured values and leakage line 7 Segment Each circuit setting Current detect sensitivity Malfunction Prevented through over input protection and filter circuit Inspect the equipment of leakage circuit conveniently because can be select the restore method Can control for more Buzzer ins...

Page 7: ...terial Silver Alloy Trip contacts 1a 8a Continuous Flow Electricity Capacity 5A at AC 250V Closing Capacity 750VA Material Gold clad Silver Alloy Trip contacts 1a 8a is only GD8 L05R Type 2 4 Case Structure Non Drawing out Type Color Munsell No N1 5 black Material ABS Resin 2 5 Ground Element Operation Current 0 2 0 5 1A 3 level setting Operation to 53 75 Operation Time Operate within 1 0 sec by 7...

Page 8: ...us 10 150 0 981 axis 3 1 octave min axis per 1 Non Applying Statsus 10 150 4 950 axis 3 1 octave min axis oper 20 Shock Applying Status 500g 15 Times Non Applying Statsus 50g Shock acceleration 5 times In any direction 2 8 Temperature Tests Temperature Range 10 o C 50 o C 2 9 Other Operating Conditions Altitude 1000m or less Condition where there is no abnormal vibration shock slope or influence o...

Page 9: ... Φ100 Φ120 Φ150 Φ200 160 30 210 30 250 30 Temp 10 60 Rated Output When Zero sequence primary current 200mA Rated output voltage is 100mV Load Resistance 1 2 Insulation Resistance Between secondary coil and case over DC500V 5 Insulation Withstand Test Between secondary coil and case Input AC2200V 60Hz during 1min Shock wave Withstand voltage Between primary and case 1 2 50 6kV positive pole negativ...

Page 10: ... as over input protection circuit sample hold multiplexer and it measured the RMS current of fundamental frequency element through the DFT Discrete Fourier Transform and it has no effect by harmonic and DC offset 3 2 Functions Earth Dectecting Function This element can be fire accident spread minimization through alarm on expectation situation of fire accident when earth leakage occured on power s...

Page 11: ...etector GD8 L05A GD8 L05R User s Manual V1 00 11 17 Kyongbo Electric Co Ltd 3 3 Product Structure Front has the 7 segment 7 LEDs 5 Push button S W and 8 of 3 level S W such as Figure 1 And rear is see the Figure 2 Figure 1 Figure 2 ...

Page 12: ... the operation status is continuous if you want to restore use this switch 9 Auto LED Turn on the Auto LED green when Auto Manual switch be Auto 10 Manual LED Turn on the Manual LED yellow when Auto Manual switch be Manual 11 Auto Manual Switch Auto If earth leakage power system line is recover earth leakage detector operation status is recover automatically Manual Operation status is continuous e...

Page 13: ...1Class Digital Earth Leakage Detector GD8 L05A GD8 L05R User s Manual V1 00 13 17 Kyongbo Electric Co Ltd Appended 1 Dimensioned Drawings GD8 L05A R ...

Page 14: ...1Class Digital Earth Leakage Detector GD8 L05A GD8 L05R User s Manual V1 00 14 17 Kyongbo Electric Co Ltd Appended 2 Internal Block Diagram GD8 L05A GD8 L05R ...

Page 15: ...o Electric Co Ltd Appended 3 External Connection GD8 L05A GD8 L05R Caution 1 This Connection is Example User can set as needed 2 Dry contacts Ta Tc 1a 8a can be used if necessary But 1a 8a is GD8 L05R Type only 3 If connection is 3p4w 4wire penetrate to ZCT 4 Fuse capacity is 0 5 A 1 1 A 1 ...

Page 16: ...17 Kyongbo Electric Co Ltd Appended 4 ZCT Dimensioned Drawings ZCT ZL 02 03 05 06 08 10 12 unit mm Type Size ZL02 ZL03 ZL05 ZL06 ZL08 ZL10 ZL12 A Φ25 Φ30 Φ50 Φ65 Φ80 Φ100 Φ120 B 70 75 91 108 123 140 160 C 100 130 150 180 D 40 50 E 80 130 160 F 30 40 G 37 5 40 48 56 5 64 72 5 82 5 ...

Page 17: ... Manual V1 00 17 17 Kyongbo Electric Co Ltd ZCT ZL 15 20 unit mm Type Size ZL 15 ZL20 A 150 200 B 112 143 C 222 284 D 220 282 E 55 55 F 10 10 G 100 100 H 80 80 I 180 180 ZCT ZL 16 21 26 unit mm Type Size ZL16 ZL 21 ZL 26 A 240 290 340 B 160 210 260 C 110 D 30 E 50 ...

Reviews: