1Class Digital Earth Leakage Detector (GD8-L05A, GD8-L05R) User’s Manual(V1.00)
8/17
Kyongbo Electric Co., Ltd
2.6
Insulation Tests
Insulation Resistance
Over 5M
, 500Vdc
Commercial Frequency
Withstand Voltage
2.2kV, 50/60Hz, 1min
Impulse Withstand
Voltage
6kV, 1.2
50
s
2.7
Mechanical Tests
Vibration
Applying
Status
10~150
㎐
, 0.981
㎨
, axis 3, 1 octave/min, axis per 1
Non
Applying
Statsus
10~150
㎐
, 4.950
㎨
, axis 3, 1 octave/min, axis oper 20
Shock
Applying
Status
500g, 15 Times
Non
Applying
Statsus
50g(Shock acceleration), 5 times, In any direction
2.8
Temperature Tests
Temperature Range
-10
o
C ~ +50
o
C
2.9
Other Operating Conditions
Altitude
1000m or less
Condition where there is no abnormal vibration, shock, slope or influence
of the magnetic field.
Place where there is no explosive dust, flammable dust, or flammable
/ rusty gas, or salt