background image

 

___________________________________________________________________________________________ 

EA440

 

SECTION 6 : TROUBLE SHOOTING 

SYMPTOM 

POSSIBLE CAUSES 

SOLUTIONS 

Voltage does not 

build up 

Engine speed is too low 

Please refer to the Generator Manual 

wires are not connected well 

Please refer to Figure 2 

Defective Generator 

Please refer to the Generator Manual 

Low output voltage 

External VR broken 

Check wiring and testing VR 

Terminal 1&2 not linked 

Please linked terminal 1&2 

Terminal 3&2 no sensing input 

Please refer to Figure 2 

Under frequency 

Please refer to the Generator Manual 

Defective Generator 

Please refer to the Generator Manual 

Over output voltage 

AVR adjustment not well 

Please refer to voltage adjustment page 

Defective Generator 

Please refer to the Generator Manual 

 

Appearance and specifications of products are subject to change for improvement without prior notice. 

Summary of Contents for EA440

Page 1: ...Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA440 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX440 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ...c residual volts at power input terminal Environment Operating Temperature 40 to 70 C Soft Start Ramp Time Storage Temperature 40 to 85 C 2 seconds 10 Relative Humidity Max 95 Vibration 3 3 Gs 100 2K Hz Static Power Dissipation Max 12 watts Dimensions 150 0 L x 135 0 W x 48 0 H mm Weight 418 g 2 115 0 135 0 130 0 150 0 21 5 48 0 5 5 STABILITY DROOP TRIM VOLT UFRO LED C B A C A 90KW C B 90 550KW B ...

Page 3: ...rn the external trimmer to midway position 3 Turn the stability trimmer on the AVR board to midway position 4 Connect a voltmeter to generator output voltage terminals 5 Start generator set and run on no load at nominal frequency 50 53 Hz or 60 63 Hz 6 If the red Led is illuminated refer to the under frequency roll off adjustment 7 Carefully turn volt trimmer clockwise until rated voltage is reach...

Page 4: ...commended see Figure 4 Field SW R V F F BATT G T S R WARNING Overly field flashing may damage the AVR or generator excitation winding Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 5 PARALLEL FUNCTION 5 1 Parallel Compensation 5 1 1 W...

Page 5: ...e Generator Manual Low output voltage External VR broken Check wiring and testing VR Terminal 1 2 not linked Please linked terminal 1 2 Terminal 3 2 no sensing input Please refer to Figure 2 Under frequency Please refer to the Generator Manual Defective Generator Please refer to the Generator Manual Over output voltage AVR adjustment not well Please refer to voltage adjustment page Defective Gener...

Reviews: