ATS-PLC
7
Step8
:
Setting exerciser parameter if needed. (Refer to
2.7.5.4)
Step9
:
Setting all the necessary protections for both
Normal and Standby source. (Refer to 2.7.5.5)
Step10
:
Power on Normal side AC volt input and set
the ATS-PLC under Manual mode.
Step11
:
Operate testing.
Manually start the genset and transfer the load from
Normal to Standby source by press touch key.
Step12
:
Manually transfer the load go back to Normal
Source and stop the genset by press touch key.
Step13
:
Repeat Step 11 & 12 to make sure the ATS
works or not.
Step14
:
Set the ATS-PLC on AUTO mode and finished
the quick start procedure.